13.7.11

 

Feedback Control Parameters

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameter

 

 

 

Function / Title

Bank

Mask

 

Adjustment Range

 

Multiplier

 

 

 

 

 

 

 

 

 

0190

 

FEEDBACK CONTROL

0 / 1

0060

0020: No feedback

(0)

 

 

SELECTION

 

 

0040: PID control

(1)

 

 

 

 

 

 

 

 

0060: Speed feedback

(2)

 

0191

 

 

 

FEEDBACK INPUT

0 / 1

001C

0004:

RR input

(1)

 

 

 

 

SIGNAL

 

 

0008:

IV input

(2)

 

 

 

 

 

SELECTION

 

 

000C:

RX input

(3)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0010:

PG feedback

(4)

 

 

 

 

 

 

 

 

0014:

RS232C input

(5)

 

 

 

 

 

 

 

 

0018:

Communication/12-bit binary

 

 

 

 

 

 

 

 

 

 

interface board

(6)

 

 

 

1,

 

 

 

 

001C:

BIN input

(7)

 

0192

 

2

 

PROPORTIONAL

0 / 1

00FF

0001 00FF (0.01 2.55)

 

0.01

 

 

 

 

GAIN

 

 

 

 

 

 

0193

 

 

 

INTEGRAL GAIN

0 / 1

FFFF

0001 8CA0 (0.01 360.00)

 

0.01

0194

 

 

 

ANTI-HUNTING

0 / 1

00FF

0000 00FF (0.0 25.5)

 

0.1

 

 

 

 

GAIN

 

 

 

 

 

 

0195

 

 

 

LAG TIME

0 / 1

00FF

0000 00FF (0 255)

 

1

 

 

 

 

CONSTANT

 

 

 

 

 

 

0196

 

 

 

PID LOWER LIMIT

0 / 1

FFFF

0 Fmax

 

0.01

 

 

 

 

FREQUENCY

 

 

 

 

 

 

0197

 

PID

DEVIATION LIMIT

0 / 1

0080

0000: No PID deviation limit

(0)

 

 

SELECTION

 

 

0080: PID deviation limited

(1)

 

0198

 

 

 

PID DEVIATION

0 / 1

00FF

0000 0032 (0 50)

 

1

 

 

1

 

UPPER LIMIT

 

 

 

 

 

 

0199

 

 

PID DEVIATION

0 / 1

00FF

0000 0032 (0 50)

 

1

 

 

 

 

 

 

 

 

LOWER LIMIT

 

 

 

 

 

 

019A

 

PG

INPUT: NUMBER OF

0 / 1

FFFF

0001 270F (1 9999)

 

1

 

 

PULSES

 

 

 

 

 

 

019B

 

PG INPUT: NUMBER OF

0 / 1

0001

0000: Single-phase input

(1)

 

 

PHASES

 

 

0001: Two-phase input

(2)

 

019C

 

DROOPING CONTROL

0 / 1

0002

0000: OFF

(0)

 

 

ENABLE

 

 

0002: ON

(1)

 

019D

 

1

 

DROOPING

0 / 1

00FF

0000 0064 (0 10.0)

 

0.1

 

 

 

 

CONTROL AMOUNT

 

 

 

 

 

 

019E

 

OVERRIDE CONTROL

0 / 1

0007

0000: OFF

(0)

 

 

SELECTION

 

 

0001: FCRR

(1)

 

 

 

 

 

 

 

 

0002: FCIV

(2)

 

 

 

 

 

 

 

 

0003: FCRX

(3)

 

 

 

 

 

 

 

 

0004: FCPG

(4)

 

 

 

 

 

 

 

 

0005: FCPNL

(5)

 

 

 

 

 

 

 

 

0006: FCOPT

(6)

 

 

 

 

 

 

 

 

0007: FCMLT

(7)

 

019F

 

 

 

OVERRIDE

0 / 1

0038

0000: Reference

(0)

 

 

 

 

MULTIPLIER

 

 

0008: KRR

(1)

 

 

 

 

 

INPUT SELECTION

 

 

0010: KIV

(2)

 

 

 

7

 

 

 

 

 

 

 

 

 

 

 

0018: KRX

(3)

 

 

 

 

 

 

 

 

0020: KBIN

(4)

 

01A0

 

 

 

OVERRIDE CHANGE

0 / 1

FFFF

FC18 03E8 (-100.0 100.0)

 

0.1

 

 

 

 

MULTIPLIER

 

 

 

 

 

 

01A1

 

 

 

Reserved

 

 

0203

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

84