13.7.3

Fundamental Parameters #1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameter

 

Function / Title

 

Bank

Mask

 

Adjustment Range

 

Multiplier

 

 

 

 

 

 

 

 

 

0026

MAXIMUM OUTPUT

(*)

0 / 1

FFFF

0BB8 9C40 (30.00400.00)

 

0.01

 

FREQUENCY

 

 

 

 

 

 

0027

BASE FREQUENCY #1

 

0 / 1

FFFF

09C4 9C40 (25.00400.00)

 

0.01

0028

BASE FREQUENCY

 

0 / 1

0030

0000: Input voltage level

(0)

 

VOLTAGE SELECT

(*)

 

 

0020: Automatic setting

(1)

 

 

 

 

 

 

 

 

0030: Stationary setting

(2)

 

0029

MAXIMUM OUTPUT

 

0 / 1

FFFF

0000

0258 (0 600)

 

1

 

VOLTAGE #1

 

 

 

 

 

 

 

002A

REVERSE OPERATION

 

0 / 1

0020

0000: Reverse allowed

(0)

 

DISABLE SELECT

 

 

 

0020: Reverse not allowed

(1)

 

002B

UPPER LIMIT FREQUENCY

0 / 1

FFFF

0000

~ Fmax

 

0.01

002C

LOWER LIMIT FREQUENCY

0 / 1

FFFF

0000

UL, Fmax

 

0.01

002D

VOLTS PER HERTZ

 

0 / 1

000F

0000: Constant torque

(1)

 

PATTERN

(*)

 

 

0001: Variable torque

(2)

 

 

 

 

 

 

 

 

0002: Auto. torque boost

(3)

 

 

 

 

 

 

 

 

0006: #3 w/ auto. energy savings

(4)

 

 

 

 

 

 

 

 

000A: Vector control

(5)

 

 

 

 

 

 

 

 

000E: #5 w/ auto. energy savings (6)

 

002E

1, 2

 

VOLTAGE BOOST

0 / 1

FFFF

0000

012C (0.0 30.0)

 

0.1

 

 

 

#1

 

 

 

 

 

 

 

002F

ACCELERATION TIME #1

0 / 1

FFFF

0001

EA60 (0.01~ 600.00)

 

0.01

 

 

 

 

 

 

 

0001

EA60 (0.1~ 6000.0)

 

0.1

0030

DECELERATION TIME #1

0 / 1

FFFF

0001

EA60 (0.01~ 600.00)

 

0.01

 

 

 

 

 

 

 

0001

EA60 (0.1~ 6000.0)

 

0.1

0031

ACC/DEC PATTERN #1

 

0 / 1

0030

0000: Linear

(0)

 

SELECTION

 

 

 

0010: Self-adjusting

(1)

 

 

 

 

 

 

 

 

0020: S-Pattern #1

(2)

 

 

 

 

 

 

 

 

0030: S-Pattern #2

(3)

 

0032

ACCEL/DECEL PATTERN

 

0 / 1

00FF

0003

~ 00FD (0 50) (Note 1)

 

1

 

ADJUST LOW

 

 

 

 

 

 

 

0033

ACCEL/DECEL PATTERN

 

0 / 1

00FF

0003

~ 00FD (0 50) (Note 1)

 

1

 

ADJUST HIGH

 

 

 

 

 

 

 

Note 1:

Parameter data = (desired setting x 5 + 3), converted to hexadecimal

 

 