Pinnacle & Stardance Direct Vent - Rear Vent Gas Heaters
Alcove Installation | 9" |
| 9" | |
|
| (230mm) |
| (230mm) |
|
| Max. Mantel |
| Max. Mantel |
| 6" | Width | 6" | Width |
|
|
| ||
| (150mm) |
| (150mm) |
|
| Sidewall/ | See | Sidewall/ | See |
| Trim | Fig. 6 | Trim | Fig. 6 |
|
| 2¹⁄₂" |
| 2¹⁄₂" |
| PDV20 | SDVR | (63mm) | |
| (63mm) | |||
|
| Rear Wall | ||
ST381 | Rear Wall |
| ||
| ST381a | |||
Fig. 5 | Alcove installation. |
|
|
|
Mantel Clearances
Hearth Requirements
Combustible
Mantel or Trim
Materials
A
B
3" (75mm) Min.
Noncombustible Materials
ST382
The PDV20 and SDVR Heaters must be installed on rigid flooring. When the heater is installed directly on any combustible surface other than wood flooring, a metal or wood panel extending the full width and depth of the unit must be used as the hearth. There are no other hearth requirements.
Gas Specifications
|
|
| Max. | Min. |
|
|
| Input | Input |
Model | Fuel | Gas Control | BTU/h | BTU/h |
PDV20RN | Nat | Millivolt | 21,000 | 15,500 |
PDV20 and SDVR
A (Max.) | B (Min.) |
9” | 10¹⁄₂” |
(230mm) | (270mm) |
7¹⁄₂” | 9” |
(190mm) | (230mm) |
6” | 7¹⁄₂” |
(152mm) | (190mm) |
4¹⁄₂” | 6” |
(114mm) | (152mm) |
3” | 4¹⁄₂” |
(76mm) | (114mm) |
1¹⁄₂” | 3” |
(38mm) | (75mm) |
A = Depth of Mantel and/or Top Trim
B = Height from Top of Heater
Fig. 6 Mantel / top trim clearances.
PDV20RP | Prop | Millivolt | 21,000 | 16,500 |
PDV20RFN | Nat | Comfort Control | 21,000 | 15,500 |
PDV20RFP | Prop | Comfort Control | 21,000 | 16,500 |
SDVRRN | Nat | Millivolt | 21,000 | 15,500 |
SDVRRP | Prop | Millivolt | 21,000 | 16,500 |
SDVRRFN | Nat | Comfort Control | 21,000 | 15,500 |
SDVRRFP | Prop | Comfort Control | 21,000 | 16,500 |
Weight: Fully assembled 350 lbs.
Gas Inlet and Manifold Pressures
| Natural | LP (Propane) |
Inlet Minimum | 5.5” w.c. | 11.0” w.c. |
Inlet Maximum | 14.0” w.c. | 14.0” w.c. |
Manifold Pressure | 3.5” w.c. | 10” w.c. |
6 | 20007066 |