Wiring the RS 485 Modbus Connector for Data Communication
Modbus versus Xanbus
Connecting the Conext ComBox with other Modbus Devices
The RS 485 Modbus connection and Xanbus cable connection provide data communication from the network and devices to the Conext ComBox. Communication with Modbus devices is handled through the RS 485 or 10/100 Ethernet connection on the Conext ComBox while communication with Xanbus components occurs through the Xanbus ports of
In the Modbus implementation, the Conext ComBox acts as a slave to an RS 485 master device. The RS 485 connection to the Conext ComBox allows communication between the Xanbus network and the master device. This enables Conext devices to link to
If a Modbus device, including the Conext ComBox, is installed as the last device in a daisy chain, a 120 ohm terminator must be used because they do not have an internal terminator for the RS 485 network. When inserting two wires in one terminal, as in the case of
Note: Turn off all Modbus and other devices prior to wiring the connectors.
Modbus
Device 1
RS 485
Connect the RS 485 connector to the RS 485 port.
See NOTE below.
Modbus
Device 2
Modbus Device 3
D1
D0 Shield
24 V
Power
Supply
Terminator
RS 485 | Modbus |
Device 4 | |
Terminator |
|