Table A-3 Physical Specifications of the Inverter
Parameter | PowerHub 1800 |
|
|
Dimensions (H x W x L) | 14.75" × 8.0" × 16.0" |
| (37.5 cm × 20 cm × 41 cm) |
|
|
Weight | 28.6 lb (13.0 kg) |
|
|
Operating Temperature | 0 °C (32 °F) to 40 °C (104 °F) |
|
|
Storage Temperature | |
|
|
Table A-4 Physical Specifications of the Battery Box
Parameter | Battery Box1 |
Dimensions (H x W x L) | 14.0" × 13.875" × 20.5" |
| (35.6 cm × 35.2 cm × 52.7 cm) |
|
|
Weight | 29 lb (13.2 kg) |
|
|
Operating Temperature | 0 °C (32 °F) to 40 °C (104 °F) |
|
|
Storage Temperature | |
|
|
Battery Charger Specifications
Charging | The Battery Charger uses a |
Process | battery (or batteries) in operational condition. This process is illustrated in |
| Figure |
Bulk Stage | The bulk stage will start upon connection of AC and with the unit turned |
| on. The constant current mode is limited to 40 A or 10 A depending on |
| setting. The voltage setpoint for this stage is 14.2 Vdc. The Charger will |
| transition to the Absorption Stage upon reaching the bulk voltage |
| setpoint. |
Absorption | In the Absorption Stage, the constant voltage mode is limited to 14.2 Vdc. |
Stage | The current will drop as batteries voltage rises. Upon dropping to 4 A, the |
| unit will transition to the Float charge. This stage will not exceed 4 hours |
| maximum. |