Troubleshooting

Table 3-1

Error Codes for Troubleshooting the PowerHub 1800

 

Error Code

 

Description

 

 

 

 

 

 

 

Displayed

 

of Error

Description of Condition

 

Resolution

 

 

 

 

 

 

E06

 

AC Output

System is still operating but AC load

 

Unit continues to run.

 

 

Overload

applied to the system in inverter mode is

 

If the warning is ignored, the

 

 

Warning

close to shutdown limit.

 

unit will eventually go to the

 

 

 

Alarm will beep once every two seconds

 

E03 fault condition.

 

 

 

 

 

 

 

 

until the warning condition is removed.

 

 

 

 

 

 

 

 

E07

 

System Over

System is still operating but system

 

Unit continues to run.

 

 

Temperature

internal temperature is close to shutdown

 

If the warning is ignored, unit

 

 

Warning

limit.

 

will eventually go to the E04

 

 

 

Alarm will beep once every two seconds

 

fault condition.

 

 

 

 

 

 

 

 

until the warning condition is removed.

 

 

 

 

 

 

 

 

E09

 

Ground Fault

Unit shuts down.

 

Turn the unit off. Check all DC

 

 

Fuse Open

A ground fault has been detection.

 

Input connections (PV, wind

 

 

Warning

 

etc.) and repair any faults or

 

 

 

 

 

 

 

 

 

damage. Replace the ground

 

 

 

 

 

fault fuse (see page 3–10) and

 

 

 

 

 

restart the unit

 

 

 

 

 

 

3–4

975-0288-01-01

Page 40
Image 40
Xantrex Technology PH1800 manual Troubleshooting Error Codes for Troubleshooting the PowerHub