Introduction

Standby Mode

In the Standby Mode, the Charger is OFF but monitors the battery

 

voltage. If battery voltage drops below 12.5 Vdc, the unit will start a new

 

Bulk stage.

 

Bulk

Absorption

 

Standby

 

Stage

Stage

Float Stage

(Stop Mode)

 

 

 

 

If the voltage drops to 12.5 Vdc

 

 

 

 

while in Standby, the Charger

 

 

14.2 Vdc

 

will start a new Bulk Stage.

 

 

 

 

Voltage 12.5 Vdc

 

13.7 Vdc

12.5 Vdc

 

 

 

 

 

 

40 A or

 

 

 

Current

10 A

 

 

 

 

Maximum

 

 

 

 

Charge

 

4 A

 

 

Amps

 

 

 

Setting

 

 

 

 

Time

4 hours

8 hours

 

 

 

 

 

 

(Maximum)

 

 

40 A or

Current

10 A

Maximum

Charge

Amps

Setting

Time

If the current rises to 6A

during the Float period, the Charger will start the whole cycle back at the Bulk Stage.

4 A

6 A

 

4 hours

8 hours

(Maximum)

Figure 1-3Three-Stage Charging Process

The PowerHub 1800 will reset to the default setting of 40 A whenever one of the following occurs.

1.The unit is turned OFF by the ON/OFF Button.

2.All DC input sources (solar panels or wind generators) are removed and utility AC is not available.

1–6

975-0288-01-01

Page 24
Image 24
Xantrex Technology PH1800 manual Voltage 12.5 Vdc