Error Codes
Error Codes
The following error codes may be displayed on the LED display if the described fault conditions occur.
Table | Error Codes for Troubleshooting the PowerHub 1800 |
| |||
Error Code |
| Description |
|
|
|
|
|
|
| ||
Displayed |
| of Error | Description of Condition |
| Resolution |
|
|
|
|
|
|
E01 |
| DC Input | Unit shuts down. |
| The unit will automatically |
|
| Under Voltage | The input voltage has dropped to below |
| reset once the fault condition is |
|
| Shutdown | the operation voltage limit of 11.0 to |
| removed. |
|
|
|
| If this condition is not corrected | |
|
|
| 10.5 V. |
| |
|
|
|
| and the unit powers down | |
|
|
| An alarm continues to beep once every |
| |
|
|
|
| completely, it will be necessary | |
|
|
| second until input/output voltage drops to |
| to press the ON/OFF Button to |
|
|
| 10.3 V. |
| turn the unit ON again. |
|
|
| The alarm will continue to beep once |
|
|
|
|
| every 30 seconds until battery voltage |
|
|
|
|
| reaches 10.0 V . If the battery reaches |
|
|
|
|
| 10.0 V, the display turns OFF and the unit |
|
|
|
|
| powers down completely. |
|
|
|
|
|
|
|
|
E02 |
| DC Input | Unit shuts down. |
| The unit will automatically |
|
| Over Voltage | An input voltage is greater than 15 V. |
| reset once the fault condition is |
|
| Shutdown |
| removed. | |
|
| The alarm will continue to beep once |
| ||
|
|
|
|
| |
|
|
| every second. |
|
|
|
|
|
|
|
|
E03 |
| AC Output | Unit shuts down. |
| Remove excess AC loads. |
|
| Overload | An AC load applied to the system in |
| Reset of unit is required. |
|
| Shutdown |
| To reset the unit, turn it OFF | |
|
| inverter mode is above operation limit. |
| ||
|
|
|
| and back ON. | |
|
|
|
|
| |
|
|
|
|
|
|
E04 |
| System Over | Unit shuts down. |
| Reduce loads or reduce ambient |
|
| Temperature | System internal temperature is above |
| temperature around the |
|
| Shutdown |
| PowerHub. | |
|
| operation limit. |
| ||
|
|
|
| The unit will automatically | |
|
|
| The alarm will continue to beep once |
| |
|
|
|
| reset once the unit cools down | |
|
|
| every second. |
| and reaches a safe operating |
|
|
|
|
| temperature. |
|
|
|
|
|
|
E05 |
| DC Input | System is still operating but input voltage |
| Unit continues to run. |
|
| Under Voltage | has dropped too close to the shutdown |
| If the warning is ignored, the |
|
| Alarm | limit (11.0 to 10.5 Vdc). |
| unit will eventually goes to the |
|
|
| Alarm will beep once every two seconds |
| E01 fault condition. |
|
|
|
|
| |
|
|
| until the warning condition is removed. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|