Specifications
Float Stage | In the Float stage, the constant voltage mode limited to 13.7 Vdc. An 8- |
| hour timer is started at this point. |
| If, during the |
| back to the Bulk Stage and starts over. |
| If the unit stays at 4A or less for the 8 hour timer, it will transition to |
| Standby Mode. |
Standby Mode | In the Standby Mode, the Charger is OFF but monitors the battery |
| voltage. If battery voltage drops below 12.5 Vdc, the unit will start a new |
| Bulk stage. |
| Bulk | Absorption |
| Standby |
| Stage | Stage | Float Stage | (Stop Mode) |
|
|
|
| If the voltage drops to 12.5 Vdc |
|
|
|
| while in Standby, the Charger |
|
| 14.2 Vdc |
| will start a new Bulk Stage. |
|
|
|
| |
Voltage 12.5 Vdc |
| 13.7 Vdc | 12.5 Vdc | |
|
| |||
|
|
| ||
| 40 A or |
|
|
|
Current | 10 A |
|
|
|
| Maximum |
|
|
|
| Charge |
| 4 A |
|
| Amps |
|
| |
| Setting |
|
|
|
| Time | 4 hours | 8 hours |
|
|
|
| ||
|
| (Maximum) |
|
|
40 A or
Current
10 A
Maximum
Charge
Amps
Setting
Time
If the current rises to 6A
during the Float period, the Charger will start the whole cycle back at the Bulk Stage.
4 A | 6 A |
| |
4 hours | 8 hours |
(Maximum)