Accessing Charger Information
Table 9
Interpreting Fault and Warning Indicators
Fault or Warning
Condition
Temp Fan AC Battery Fuse Charger Remote Fault Solution
AC input out of range
fault (<85V or >265 V)
Check AC connections. Change to a more stable AC
power source and check that the voltage and voltage
frequency are within acceptable operating range. See
“Specifications” on page 54.
High Battery Temp fault
(>70°C)
Check the batteries. Do not charge a battery that is
rated other than 12 V nominal for all 12-volt chargers
or 24 V nominal for all 24-volt chargers. Check that
the battery type and temperature settings match the
actual battery and its conditions.
Disconnect or turn off other charging sources such as
an alternator or the charger on a generator with an
electric start.
Allow the battery (or batteries) to cool to normal
operating temperature. See “Specifications” on page
54.