York 152, YLCC-h, 122 manual Access to “FACTORY” parameters, Deactivation of the buzzer, Alarm reset

Models: 152 122 YLCC-h YLCC 42/62/82/102/112

1 64
Download 64 pages 50.92 Kb
Page 31
Image 31
Access to “FACTORY” parameters

pre-selected code, which can be changed with the Deactivation of the buzzer and Alarm reset keys. Pressing the PRG key memorizes the new values and exits the procedure. If for over 10 seconds no modification is made, the display begins to flash. If no other key is pressed in 60 seconds, the unit will go back to normal status without changing any parameter.

Access to “FACTORY” parameters

The FACTORY parameters are factory-set. These are pro- tected by a password to avoid access to unauthorized per- sonnel. Pressing the PRG and SEL keys simultaneously for over 5 seconds displays 00 flashing. Enter the password (au- thorized personnel) and press SEL. The first FACTORY pa- rameter is displayed. Pressing the Forces defrost (YLCC-H) and Clearing hour counters keys moves you through all FACTORY parameters available. Pressing SEL once again displays the parameter value of the pre-selected code, which can be changed with the Installation of default parameters and Adjusting display contrast keys. Press- ing the PRG key memorizes the new values and exits the procedure. If for over 10 seconds no modification is made, the display begins to flash. If no other key is pressed in 60 seconds, the unit will go back to normal status without chang- ing any parameter.

Deactivation of the buzzer

To deactivate the alarm buzzer, press the MUTE key. (The buzzer will become operative only is programmed previously.)

Alarm reset

Pressing the Summery of keyboard functions and Manual background keys for over 5 seconds (if using a

remote terminal, press the CLEAR key for over 5 seconds) will cancel present in the memory. The alarm message will also disappear from the display and the alarm relay will be deactivated.

Forces defrost (YLCC-H)

Pressing the SEL and Manual background keys simultaneously for over 5 sec- onds activates the forced defrost cycle of both coils, as long as the temperature of said coils is below the value set for finalizing defrost.

Clearing hour counters

When displaying compressor or heat pump operating hours (parameters c9, cA and cC), the counter can be cleared by pressing the Manual background and Manual background keys simultaneously (if a remote termi- nal is being used, press the CLEAR key).

Installation of default parameters

With the unit turned off, press the PRG key. Holding this key down turns the system on. Once this process is over, the letters dF appear on the display. The default parameters are those included by the controller manufacturer and affect the DIRECT and USER parameters based on the FACTORY val- ues.

Adjusting display contrast

On remote terminals only. Press the key located between MUTE and PRG to access the three contrast levels avail- able.

 

 

Summery of keyboard functions

Key

Unit status

Action

 

 

 

 

Normal operation. Entering water temp. is

DIRECT parameters appear after 5 seconds

 

displayed (probe B1)

SEL

 

 

 

List of parameters

Display of values

 

 

 

 

 

Display of values

Display list of parameters

 

 

 

 

Normal operation

USER parameters appear after 5 seconds

 

 

 

 

List of parameters

Memorizes EEPROM values and then displays probe B1

 

temperature.

PRG

 

 

 

Display of values

Memorizes EEPROM values and then displays probe B1

 

 

temperature.

 

 

 

 

 

 

Buzzer active

Buzzer goes off

 

 

 

 

Normal operation

Activates or deactivates COOL mode after 5 seconds

UP / HEAT

 

 

List of parameters

Display of parameters

 

 

 

 

Display of values

Increases value

 

 

 

 

Normal operation

Activates or deactivates HEAT mode after 5 seconds

DOWN / HEAT

 

 

List of parameters

Display of parameters

 

 

 

 

Display of values

Decreases value

 

 

 

PRG + SEL

Normal operation

FACTORY parameters appear after 5 seconds (password)

 

 

 

SEL + UP

Normal operation

Starts forced defrost after 5 seconds, if allowed by temperature

conditions

 

 

 

 

 

UP + DOWN

Normal operation

Resets alarms after 5 seconds

 

 

Display of hours

Clears counter

 

 

 

 

PRG

In start-up

Installs default parameters and values

 

 

 

PRG + UP

In start-up

Copies key on controller EEPROM

 

 

 

PRG + DOWN

In start-up

Copies EEPROM on the key

 

 

 

31

Page 31
Image 31
York 152, YLCC-h, 122 manual Access to “FACTORY” parameters, Deactivation of the buzzer, Alarm reset, Forces defrost YLCC-H