Identification of system intakes and outlets

Terminals

Description

 

 

B1-GND

Water temp. probe at evaporating unit intake

 

 

B2-GND

Water temp. probe at evaporating unit outlet (Circuit 1)

 

 

B3-GND

Fan speed and circuit defrost control probe (Circuit 1)

 

 

B4-GND

Evaporating unit water discharge temp. (Circuit 2)

 

 

B5-GND

Fan speed and circuit defrost control probe (Circuit 2)

 

 

ID1-IDCOM

High pressure switch (Circuit 1)

 

 

ID2-IDCOM

Low pressure switch (Circuit 2)

 

 

ID3-IDCOM

Compressor thermal protector (Circuit 1) (YLCC and YLCC-H - 82 and 102 only) (or fan on YLCC)

 

 

ID4-IDCOM

Fan thermal protector (Circuit 1) (YLCC-H only)

 

 

ID5-IDCOM

Water flow switch and auxiliary contact of pump contactor

 

 

ID6-IDCOM

Remote ON/OFF

 

 

ID7-IDCOM

Remote cool/heat

 

 

ID8-IDCOM

High pressure switch (Circuit 2)

 

 

ID9-IDCOM

Low pressure switch (Circuit 2)

 

 

ID10-IDCOM

Compressor thermal protector (Circuit 2) (YLCC and YLCC-H - 82 and 102 only) (or fan on YLCC)

 

 

ID11-IDCOM

Fan thermal protector (Circuit 2) (YLCC-H only)

 

 

Y1-GND

PWM analogical outlet for fan control (Circuit 1)

 

 

Y2-GND

PWM analogical outlet for fan control (Circuit 2)

 

 

RES. 1

Antifreeze or backup heater (Circuit 1)

 

 

COMP. 1

Compressor (Circuit 1)

 

 

VALVE 1

4-way valve (Circuit 1)

 

 

PUMP

Water pump

 

 

ALARM

General alarm remote signal

 

 

RES. 2

Antifreeze or backup heater (Circuit 2)

 

 

COMP. 2

Compressor (Circuit 2)

 

 

VALVE 2

4-way valve (Circuit 2)

 

 

Accessories

Remote control unit

For access and control by means of the buttons and LEDs available.

Allows selecting the cool, heat and OFF functions, and the

red LED indicates any failure.

Can be installed at a maximum distance of 50 m.The remote terminal should be connected to the unit with a 7 x 0,35 mm2 cable.

1

 

 

 

2

 

 

3

 

 

 

4

 

 

5

 

 

 

6

 

 

1- Voltage indicator LED. When the LED is on, the machine is powered.

2- General alarm LED. When this LED is on, the unit has a failure.

3- On/Off push button.

4- On/Off LED. When on, the unit is in operation.

5- Cool/heat pushbutton.

6- Cool/heat LED. When LED is off, cool mode. When the LED is on, heat mode.

28

Page 28
Image 28