York 122, 152 Controls, Accessories, Centrifugal fans, Hydro kit GH, DI buffer tanks, Operation

Models: 152 122 YLCC-h YLCC 42/62/82/102/112

1 64
Download 64 pages 50.92 Kb
Page 6
Image 6
Centrifugal fans

connected and tested.The electric box has a door with a block- ing mechanism and contains the compressor and fan contac- tors, fuses and electrical protection. Also has IP44 protec- tion.

Centrifugal fans

Transmission is by belts and removable core pulleys. The motors are mounted on tensing bases fastened directly to the fan casing.

Two versions are available: with horizontal or vertical air dis- charge

Compatible with the following units:

GH200

for size 42

GH260

for sizes 62 and 82

GH600S

for sizes 102 and 122

GH600P

for size 152

Controls

So as to achieve maximum energy savings, perfect opera- tion of the equipment and prolong the useful life of same, the YLCC water chillers or heat pump units are equipped with the following controls:

- Electronic thermostat that controls cold water return tem- perature.

-Electronic antifreeze thermostat.

-High pressure switch, 31 bar.

-Low pressure switch, 2 bar.

-Stage rotation (included in the thermostat).

-Remote terminal unit (optional).

-Timed start.

-Remote control.

comp

PRG

 

 

mute

 

 

 

clear

 

SEL

chillerµ

 

 

x 100

 

 

Accessories

Hydro kit GH

Includes: Buffer tank, automatic air purger, pressure gauge, automatic 1.5 bar filling valve, expansion vessel, pump, flow switch, drain valve, safety valve and electronic board for in- terconnection. Available in 200, 260 and 600 litre capacities. There are two versions of GH600: GH600S and GH600P.

DI buffer tanks

Cylindrical shape and in vertical position. Available in 200, 260 and 600 litre capacities.

Low ambient kit (factory-mounted, optional)

This accessory allows operation of the unit when the con- densing outdoor air temperature is below 10° C.

General information

This accessory controls condensing pressure in the winter cycle by varying air flow through the outdoor coils. This flow variation keeps condensing pressure constant when outdoor temperatures are low.

Operation

By means of the pressure detected through the analogical pressure switches installed in the cooling circuit, and carry- ing out the appropriate calculations as programmed, this con- trol generates an analogical signal that opens the dampers to maintain the condensing pressure previously programmed as the set point.

6

Page 6
Image 6