Yellow and green LEDs on base plate

Yellow and green LEDs on base plate

The yellow LED indicates unit operation. Under normal condi- tions, it flashes once per second. In the case of an alarm, it flashes twice per second.When it goes off, no voltage is reach- ing the base plate.

The green LED indicates communication with the remote ter- minal. In the case of a communication failure, this LED re- mains off (failures are normally due to bad contact between the telephone connector and one of the female bases on the main board or the terminal.

Probe calibration

If necessary, the probes can be calibrated by using the fol- lowing parameters.

Parameter

Description

 

 

Unit

 

 

 

/6

Calibration probe B1 (entering water

0.1°C/F

temperature)

 

 

 

 

 

 

/7

Calibration probe B2 (discharge water

0.1°C/F

temperature exchanger 1)

 

 

 

 

/8

Calibration probe

B3

(refrigerant

0.1°C/F

temperature circuit 1)

 

 

 

 

 

 

/9

Calibration probe B4 (discharge water

0.1°C/F

temperature exchanger 2)

 

 

 

 

/A

Calibration probe

B5

(refrigerant

0.1°C/F

temperature circuit 2)

 

 

 

 

 

 

Remote ON/OFF

A remote ON/OFF digital intake can be connected between terminals ID6-IDCOM of the base plate. To activate this in- take, give value 1 to parameter H7 (H7 = 1). Said digital in- take has priority over the one originating at the keyboard. When this digital intake is open, the unit remains in the OFF mode.

Remote COOL/HEAT

A remote COOL/HEAT digital intake can be connected be- tween terminals ID7-IDCOM of the base plate. To activate

this intake, give value 1 to parameter H6 (H6 = 1). When this function is activated, the COOL/HEAT digital signal overrides the one originating at the keyboard and the unit remains in the COOL mode.

Protection of “DIRECT” parameters

Parameter H9 allows deactivating access to the DIRECT and USER parameters from the local and remote terminals. In any case, parameter values can be displayed but not changed. The following functions will also be deactivated: cool/heat selection, forced defrost and clearing of hour counters. To select the coo, heat, off and on functions, the remote digital cool/heat and remote on/off intakes must be used.

Parameter H9

Remote terminal

Local terminal

 

 

 

0

Activated

Deactivated

 

 

 

1

Activated

Activated

 

 

 

2

Deactivated

Deactivated

 

 

 

3

Deactivated

Activated

 

 

 

Buzzer configuration

Parameter P4 allows selecting three buzzer operating modes.

Parameter P4 Buzzer function

0Always disconnected

Between 1 & 14 Disconnects once this value in minutes is over

15Operating until the cause of the alarm disappears

Operation

Cooling cycle YLCC

The heat exchanger for water acts as an evaporator unit, while the finned coil acts as a condenser unit. The summer cycle diagram indicates the circuit followed by the refrigerant.

Cooling cycle diagram forYLCC

EVAPORATOR

CONDENSER

CENTRIFUGAL

 

FAN

SCROLL

COMPRESSOR

EXPANSION

VALVE

FILTER-DRYER

SIGHT GLASS

The units are made up of two circuits, with common water connections.