York 122, YLCC 42/62/82/102/112, YLCC-h Cooling cycle compressor on, Heating cycle compressor on

Models: 152 122 YLCC-h YLCC 42/62/82/102/112

1 64
Download 64 pages 50.92 Kb
Page 34
Image 34
Cooling cycle (compressor on)
Single-phase axial or centrifugal fans operation with speed control
Speed selection is carried out in both the cooling as well as the heating cycles.

- In “pump absent” mode, the flow switch alarm is deacti- - To see pump operating hours, see DIRECT cC parameter. vated.

- The water pump will start 20 seconds before compressor (c7) starts.

- When the compressor turns off, the pump will continue op- erating for 20 minutes more (c8).

Cooling cycle (compressor on)

Maximum speed

Minimum speed

Fan off

 

 

Condensing temperature

Cooling cycle cut-off

Cooling cycle minimum

Cooling cycle maximum

(F9)

speed temperature (F5)

speed temperature (F6)

Heating cycle (compressor on)

Maximum speed

Minimum speed

Fan off

 

 

Evaporating

 

 

temperature

Heating cycle maximum

Heating cycle minimum

Heating cycle cut-off

speed temperature (F8)

speed temperature (F7)

(FA)

Parameter

Description

Unit

Factory value

 

 

YLCC-H

YLCC

 

 

 

 

 

 

 

 

 

F1 (FACTORY)

Fan presence (0 = no, 1 = yes)

 

1

0

 

 

 

 

 

F2 (USER)

Operating mode. (0 = always ON; 1 = parallel with

 

 

 

 

 

comp.; 2 = parallel with comp. Reg. ON/OFF; 3 = parallel

 

1

1

 

 

with comp. Speed control).

 

 

 

 

 

 

 

 

 

 

 

 

F3

(FACTORY)

Minimum voltage threshold at triac (a)

steps

0

0

 

 

 

 

 

 

F4

(FACTORY)

Maximum voltage threshold at triac (b)

steps

166

166

 

 

 

 

 

F5 (USER)

Cooling cycle minimum speed temp.

°C

35

35

 

 

 

 

 

F6 (USER)

Cooling cycle minimum speed temp.

°C

45

45

 

 

 

 

 

F7 (USER)

Heating cycle minimum speed temp.

°C

35

35

 

 

 

 

 

F8 (USER)

Heating cycle maximum speed temp.

°C

30

30

 

 

 

 

 

F9 (USER)

Cooling cycle fan off temperature

°C

20

20

 

 

 

 

 

FA (USER)

Heating cycle fan off temperature

°C

40

40

 

 

 

 

 

Fb (USER)

Fan start time

4 secs.

0

0

34

Page 34
Image 34
York 122, YLCC 42/62/82/102/112, YLCC-h, 152 manual Cooling cycle compressor on, Heating cycle compressor on