Unit addressing

Unit addressing within the network can be selected by means of the value given to parameter HA and the dip-switch sys- tem configuration included in serial board RS485. Effective addressing is obtained by adding the offset value taken from the following table to HA.

For example, if the HA value is 12 and dip-switch 1 is set to ON, the address obtained will be 12 + 128 = 140.

OFFSET

DIP 1

DIP 2

DIP 3

DIP 4

 

 

 

 

 

0

off

off

off

off

 

 

 

 

 

16

off

off

off

ON

 

 

 

 

 

32

off

off

ON

off

 

 

 

 

 

48

off

off

ON

ON

 

 

 

 

 

64

off

ON

off

off

 

 

 

 

 

80

off

ON

off

ON

 

 

 

 

 

96

off

ON

ON

off

 

 

 

 

 

112

off

ON

ON

ON

 

 

 

 

 

128

ON

off

off

off

 

 

 

 

 

144

ON

off

off

off

 

 

 

 

 

160

ON

off

ON

off

 

 

 

 

 

Unit control

comp

PRG

 

 

mute

chillerµ

 

 

 

 

clear

 

SEL

 

x 100

 

 

Display

The display always shows, by default, the return water tem- perature detected by probe B1. This comprises three figures with automatic viewing of a decimal point between -19.9 and +19.9° C. Beyond this range, the displayed value will always comprise two figures. E.g. 21° C. Nevertheless, the regulator in the internal program always operates based on tenths of a degree.

Unit status

Unit status information is indicated by 5 LEDs located on the terminal display, and 2 LEDs (yellow and green) on the base plate.

Led

Flashing

On

 

 

 

Comp. (left)

Comp. 1 in demand (Temp.)

Comp. 1 activated

 

 

 

Comp. (right)

Comp. 2 in demand (Temp.)

Comp. 2 activated

 

 

 

Cool

 

Operating in COOL

 

 

 

Heat

 

Operating in HEAT

 

 

 

x 100

 

Value x 100

 

 

 

Keyboard

The terminal keyboard is comprised of four keys: PRG/mute, SEL,/HEAT and /COOL. These keys allow selecting unit

operating mode, monitor its status and set operating param- eters. There are more keys available on the remote terminal version for working ease. Key functions and their variants, when pressed two at a time, are detailed below.

Activation/deactivation of “COOL” function

The COOL function can be activated and deactivated by pressing the COOL key for over 5 seconds. It is impossible to go directly from the HEAT to the COOL mode without previ- ously deactivating the HEAT function.

Activation/deactivation of “HEAT” function

The HEAT function can be activated and deactivated by press- ing the HEAT key for over 5 seconds. It is impossible to go directly from the COOL to the HEAT mode without previously deactivating the COOL function.

Access to “DIRECT” parameters

The DIRECT parameters are accessible to the user and are related to set points and their differentials, to entering and discharge water temperature of the exchanger, to the refrig- erant temperature in the coil and to the compressor and pump operating hours counters. Pressing the SEL key for over 5 seconds displays the code of the first parameter, which is the cool cycle set point. Pressing the and keys moves you through all DIRECT codes available. Pressing SEL once again displays the parameter value of the pre-selected code, which can be changed with the and keys. Pressing the PRG key memorizes the new values and exits the procedure. If for over 10 seconds no modification is made, the display begins to flash. If no other key is pressed in 60 seconds, the unit will go back to normal status without changing any parameter.

"DIRECT"

Description

Factory value

parameter

 

 

 

r1

COOL set point

12°C

 

 

 

r2

COOL cycle differential

3°K

 

 

 

r3

HEAT set point

40°K

 

 

 

r4

HEAT cycle differential

3°K

 

 

 

r6

Water discharge temp. exchanger 1

Readout °C

 

 

 

r7

Water discharge temp. exchanger 2

Readout °C

 

 

 

r8

Refrigerant temp. coil 1

Readout °C

 

 

 

r9

Refrigerant temp. coil 2

Readout °C

 

 

 

c9

Operating hours compressor 1

Readout hours x 100

 

 

 

cA

Operating hours compressor 2

Readout hours x 100

 

 

 

cC

Operating hours water pump

Readout hours x 100

 

 

 

Access to “USER” parameters

The USER parameters are those used by the unit to operate accordingly. These are protected by a password to avoid ac- cess to unauthorized personnel. Pressing the PRG key for over 5 seconds displays 00 flashing. Enter the password (au- thorized personnel) and press SEL. Pressing the and keys moves you through all USER parameters available. Pressing SEL once again displays the parameter value of the

30

Page 30
Image 30
York 122, YLCC-h Unit addressing, Unit control, Display, Unit status, Keyboard, Activation/deactivation of Cool function