York YLCC 42/62/82/102/112, 122 Operation of set points, Compressors, Operation of cooling cycle

Models: 152 122 YLCC-h YLCC 42/62/82/102/112

1 64
Download 64 pages 50.92 Kb
Page 32
Image 32
Operation of set points

Operation of set points

Operation of cooling cycle

Differential/2

(r2/2)

Second compressor

First compressor

COOL set point (r1)

COOL set point (r1)+Differential (r2)

Operation of heating cycle

Differential/2

(r4/2)

Second compressor

 

First compressor

COOL set point (r1)

COOL set point (r3)+Differential (r4)

Parameter

Description

Unit

Factory value

 

 

YLCC-H

YLCC

 

 

 

 

 

 

 

 

 

 

r1

(DIRECT)

COOL set point

°C

12

12

 

 

 

 

 

 

r2

(DIRECT)

COOL cycle differential

°K

3

3

 

 

 

 

 

 

r3

(DIRECT)

HEAT set point

°C

40

40

 

 

 

 

 

 

r4

(DIRECT)

HEAT cycle differential

°K

3

3

 

 

 

 

 

rA (USER)

Minimum COOL set point

°C

8

8

 

 

 

 

 

rb (USER)

Maximum COOL set point

°C

30

30

 

 

 

 

 

rC (USER)

Minimum HEAT set point

°C

15

15

 

 

 

 

 

rd (USER)

Maximum HEAT set point

°C

50

50

 

 

 

 

 

/d (USER)

Degrees C or F (0 = °C; 1 = °F)

 

0

0

 

 

 

 

 

 

Compressors

Parameter

Description

Unit

Factory value

 

 

YLCC-H

YLCC

 

 

 

 

 

 

 

 

c1 (USER)

Minimum run time

sec.

5

5

 

 

 

 

 

c2 (USER)

Minimum off time

10 secs.

1

1

 

 

 

 

 

c3 (USER)

Time between two starts of the same compressor

10 secs.

36

36

 

 

 

 

 

c4 (USER)

Time between two starts of the two compressors

sec.

10

10

 

 

 

 

 

c5 (USER)

Time between off of the two compressors

sec.

3

3

 

 

 

 

 

c6 (USER)

Start timing

sec.

10

10

 

 

 

 

 

c7 (USER)

Compressor start delay regarding the pump

sec.

20

20

 

 

 

 

 

c8 (USER)

Pump delay regarding the compressor

min.

20

20

 

 

 

 

 

c9 (DIRECT)

Compressor 1 operating hours counter

hours

 

 

 

 

 

 

 

cA (DIRECT)

Compressor 2 operating hours counter

hours

 

 

 

 

 

 

 

cb (USER)

Operating hours for maintenance alarm

hours

 

 

 

 

 

 

 

cC (DIRECT)

Pump operating hours counter

hours

 

 

 

 

 

 

 

r5 (FACTORY)

Compressor rotation (0 = yes; 1 = 0)

 

0

0

 

 

 

 

 

32

Page 32
Image 32
York YLCC 42/62/82/102/112 Operation of set points, Compressors, Operation of cooling cycle, Operation of heating cycle