York 122, YLCC-h, 152 Clearances, Drainage, Locating and securing the unit, Location dimensions

Models: 152 122 YLCC-h YLCC 42/62/82/102/112

1 64
Download 64 pages 50.92 Kb
Page 22
Image 22
Clearances

Clearances

When installing each unit, clearances should be left for:

1- Air intake and discharge.

2- Water, drain and power supply connections

3- Maintenance servicing.

Note: See minimum clearances indicated on the general di- mensions diagrams.

Drainage

The unit has two connections for draining condensed water accumulated in the coil during operation in the winter cycle, or for fully emptying the unit. The outer diameter of these connections is 28 mm. At outdoor temperatures below 0° C, condensed water can freeze and obstruct the drain. It is ad- visable to take this into account and, when considered nec- essary, install a flexible electric heater. This heater can be connected by means of an ambient thermostat set to 3° C, for example. This thermostat activates the heater when the

temperature is below the set point.

Locating and securing the unit

These units are designed to be placed on the floor indoors. With air discharge and return ducts, if necessary. Before open- ing the packing, make sure you have received the appropri- ate product by checking the specifications described on the outside of same.

The unit should be placed on a perfectly horizontal plane, making sure the base can support the weight of the unit.

If vibration-free operation is required, the unit can be placed on a cork or similar anti-vibratory base, or fastened to the base with anti-vibratory plates or supports (optional acces- sory).

If the unit is to be placed on the floor, a concrete base should be prepared so as to distribute weight evenly.

The following illustration shows the spaces and fastening points that correspond to the location of each model.

Location dimensions

 

 

 

 

A

 

 

 

 

 

 

C

 

D

 

C

 

 

 

E

 

 

 

 

 

 

 

B

F

 

 

 

 

 

 

 

 

E

 

 

 

 

 

 

 

 

 

 

 

 

 

ANCHORING

 

 

 

 

 

 

 

 

HOLES Ø G

 

 

Model

A

B

C

D

E

F

Ø G

42

2 240

774

200

1 840

55

664

16.5

(4)

62

2 240

929

200

1 840

55

819

16.5

(4)

82

2 891

1 000

200

1 245.5 (x 2)

55

890

16.5

(6)

102

2 891

1 000

200

1 245.5 (x 2)

55

890

16.5

(6)

122

3 200

1 300

200

1 400 (x2)

55

1 190

16.5

(6)

152

3 200

1 300

200

1 400 (x2)

55

1 190

16.5

(6)

22

 

 

 

 

 

 

 

 

Page 22
Image 22
York 122, YLCC 42/62/82/102/112, YLCC-h, 152 manual Clearances, Drainage, Locating and securing the unit, Location dimensions