Roberts Gorden POP-ECA/PGP-ECA 015 to 0100 service manual Modulating Operation, High/Low Operation

Page 46

COMBAT® CABINET HEATERS INSTALLATION, COMMISSIONING, OPERATION AND SERVICE MANUAL

SECTION 11: USER INSTRUCTIONS 11.1 User Instructions

The COMBAT® Cabinet heaters are fully automatic and operate from the external controls fitted on site. The only user controls at the heater are the:

Fan Run Button - See Page 40, Figure 20.

Burner lockout reset button - See Page 41, Section 11.2.2.

Limit thermostat reset button - See Page 40, Figure 20.

WARNING

Electrical Shock Hazard

Disconnect electrical power before servicing.

Failure to follow these instructions can result in death or electrical shock.

to low fire. If the temperature rises to the second set point, the burner will turn off. The burner will come on again at either High or Low fire, depending on the thermostat set point.

Set the two stage thermostat to the desired temperature.

Modulating Operation

The on-site control for modulating burners is a temperature controller that provides a varying output signal dependant upon the ambient temperature to the control. The burner firing rate will continuously vary between the maximum and minimum setting. If the temperature rises with the firing rate set to the minimum, the burner will shut down. Set the operating temperature according to the instructions provided with the control.

11.2Common User Controls (all models) 11.2.1 Combination Fan/Limit Thermostat

The Combination Fan/Limit Thermostat is located at the top right side of the heater.

This control ensures the heater does not blow cold air in the normal heating cycle and protects the heat exchanger against overheating.

Figure 20: Fan/Limit Thermostat

11.1.1 Heater Operation

When the heater has been switched on by the remote controls installed on site, the main burner will automatically turn on. The burner control will control the safe ignition of the flame. When the heat exchanger is sufficiently heated, the fan thermostat turns on the main fan(s).

All heaters require a constant gas and electricity supply, which must not be interrupted during the normal operation of this heater.

NOTE: The fan will come on during burner firing for horizontally mounted and high-flow heaters and modulating burners.

Figure 19: Heater Operating Sequence

 

ON

CLOSE

THERMOSTAT

 

DOWN

CALL FOR

 

 

HEAT

ON

 

BURNER

 

 

RUN

ON

 

 

 

 

2-3 MINUTES

RUN ON

FAN

 

 

11.1.2 Heater Operation (high/low or modulating)

The heater will operate as described in Section

11.1.1with these added features:

High/Low Operation

A second limit thermostat or a two-stage thermostat will be installed on site so that as the temperature reaches the first set point, the firing rate will reduce

If the air flow is reduced due to power failure, the limit thermostat will cause the burner to lockout.

Red limit reset button

(Press to reset)

White fan button

Pull out for normal operation.

Press in for constant fan.

The combination fan/limit thermostat is preset during commissioning.

See Page 8, Section 4.4 and Page 34, Figure 13.

NOTE: To reset, the heat exchanger must be cool.

Description

Part Number

Combination Fan/Limit Thermostat

K017A

40

Image 46
Contents Supplier after leaving the building Improper installation, adjustment, alteration, serviceManual thoroughly before installing or servicing Immediately call your local gas Follow the gas supplier’sPage Roberts-Gordon LLC Page Table of Figures Page Product Approval Corrosive Chemicals Clearances to CombustiblesNational Standards and Applicable Codes Location and Suspension All models Minimum Required Installation ClearancesCritical Considerations 3.1 Basic Information VentilationInstallation Clearances and Clearances to Combustibles Front View all models Side View Models 015 Dimension Data PGP & POP Internal HeatersAll models Rear View Dimension Data PGP & POP External HeatersPGP & POP External Heaters Front View Side View Model 015/020/030 040 050 060/070/080 0100Outlet Spigot Dimensions Vertical and Horizontal Heaters Air Outlet Spigots top viewMax 25 mbar 10 in WG Model 015 020 030 040 050 060 070 080 0100Max 45 mbar 18 in WG Min 17 mbar 6.8 in WG Max 25 mbar 10 in WG Maximum Gross Heat InputLight Fuel Oil Gas Oil Data Technical Data Ecoflam Oil-Fired Burners burner reference GKerosene Data Heater Installation 5.1 General HandlingTypical Installation of a Oil-Fired Cabinet Heater Flue Installation 6.1 Flue Installation Flue TerminationJoint with high Rain CollarSilicon Sealer Building Ventilation AIR Supply 7.1 Air SupplyIsolated Equipment Rooms Distribution DuctingFuel Piping Gravity Feed Systems Fuel Oil Supply 8.2.1 Fuel Storage TankFuel Pipes 4 B. M. Oil LifterPressurised System Installation Duplex System Positioning Room Thermostats or Roberts-Gordon Control Remote ControlsBurner Controls Thermostat Remote Frost ThermostatCCH Wiring Diagram Gas Models 15-30 floor standing CCH Wiring Diagram Oil Models 15-30 floor standing CCH Wiring Diagram Gas Models 15-30 horizontal mounting GAS Burner 7-WAY PlugCCH Wiring Diagram Oil Models 15-30 horizontal mounting OIL Burner 6-WAY PlugCCH Wiring Diagram Gas Models 40-50 floor standing CCH Wiring Diagram Oil Models 40-50 floor standing Outputs Lockout Reset Signal From Burner RUN Signal CCH Wiring Diagram Oil Models 40-50 horizontal mounting CCH Wiring Diagram Gas Models 60-100 floor standing CCH Wiring Diagram Oil Models 60-100 floor standing CCH Wiring Diagram Gas Models 60-100 horizontal mounting CCH Wiring Diagram Oil Models 60-100 horizontal mounting Page Electrical Checks Polarity Test 1 ØLouvers Polarity Test 3 ØGas Supply Initial SettingCommissioning the Burner gas heaters Before Operating the HeaterSequence of Operation Control Gas-Fired HeatersDescription of Gas-Fired Heater Control Motor Starter and Thermal OverloadGas Train Circuit for Dungs Gas Valves all models Start Gas Valves Throughput AdjusterCombustion Testing all models Rate of OpeningHigh/Low and Modulating Burners Pressure SwitchComplete the Commissioning Commissioning the Burner Oil HeatersError Diagnosis Fault Display MessagesFault Display Fault ConditionsHigh/Low Operation Modulating OperationHeater Operation high/low or modulating Pull out for normal operation Press in for constant fanSimple Fault Finding burner faults Burner Lockout Reset ButtonSimple Fault Finding all models Simple Fault Finding oil fired heatersIf you smell gas Heat Exchanger Maintenance Burner Maintenance12.3 Fan/Motor Assembly Maintenance all models Servicing 12.1 Servicing InstructionsConversion Between Fuels 13.1 General Burner ConversionConduct Commissioning procedure as shown on Page 33, Section Conduct Commissioning procedure as shown on Page 33, Section Troubleshoot Ends Troubleshooting for Flame Supervision System Oil-Fired Gas-FiredTroubleshooting for Solenoid Valves Circuit Troubleshooting for Main Fan Circuit 1 ØTroubleshooting for Main Fan 3 Ø Conduct Commissioning procedure as on Page 33, SectionOverloads models 060 to Burner ComponentsContactor Control Circuit Fuse 10 or 5 A, 1-1/4 long sand filledRoberts Gordon Spare Parts List Description 015 020 030 040 050 060 070 080 0100Page Page Some objects can catch fire or explode when placed

POP-ECA/PGP-ECA 015 to 0100 specifications

The Roberts Gordon POP-ECA/PGP-ECA 015 to 0100 series represents a significant advancement in the realm of heating technologies, particularly in industrial and commercial applications. These innovative units are designed to provide efficient, reliable heating solutions tailored to meet the diverse needs of various environments.

Main features of the POP-ECA/PGP-ECA series include their high-performance heating capabilities, which allow for rapid temperature rise and consistent heating throughout a space. This efficiency is critical for industries that require precise temperature control for their processes. The units are engineered to emit heat evenly, reducing hot spots and ensuring that the entire area is warmed effectively.

One of the standout technologies incorporated into these heaters is their advanced combustion system. This system optimizes fuel usage, enhancing energy efficiency while minimizing emissions. This aspect is particularly vital in today’s environmentally conscious world, where businesses seek to reduce their carbon footprint. The designs are compliant with current environmental regulations, making them suitable for use in various operational settings.

The POP-ECA/PGP-ECA series also boasts a variety of innovative features aimed at user convenience. Integrated control systems allow for easy adjustments and monitoring, enabling operators to maintain ideal temperature settings with minimal effort. Additionally, many units in the series offer flexible mounting options, allowing for vertical or horizontal installation to suit different space constraints and layout requirements.

Characteristics of the POP-ECA/PGP-ECA series also include robust construction, ensuring durability and longevity even in the most demanding environments. The materials used are resistant to corrosion and wear, providing a reliable heating solution that requires minimal maintenance over time. Moreover, the compact design of the units means that they can be installed in tight spaces without sacrificing performance.

Overall, the Roberts Gordon POP-ECA/PGP-ECA 015 to 0100 series stands as a testament to cutting-edge engineering in heating technology. With their combination of efficiency, environmentally conscious design, and user-friendly features, these units are an excellent choice for a wide range of industrial and commercial heating applications. They exemplify the future of heating solutions, prioritizing performance while remaining mindful of energy consumption and environmental impact.