Roberts Gorden POP-ECA/PGP-ECA 015 to 0100 Start Gas Valves, Rate of Opening, Main Gas Valves

Page 43

SECTION 10: COMMISSIONING

Figure 17: Dungs Gas Valve

10.4 Gas Valves

Dungs Combination Gas Valve

All model 015 - 030 gas-fired burners operate as direct main flame ignition and have no separate start gas train. All other models operate with a first stage start gas flame supplied from a start gas train containing a start gas pressure regulator and two safety shut-off valves, for all gas types.

The main gas is released at the second stage, and the combination main gas valve block contains a main burner pressure regulator and two safety shut- off valves, for all gas types. See Page 37, Figure 17. For high/low or modulating burners, the Dungs gas valve has extra features because it is an air/gas ratio control valve. Please refer to the manufacturer’s instructions for setting the controls.

10.4.1 Start Gas Valves

appliances and need no further adjustment. When replacing a gas valve, ensure that this device is set in the fully open position by releasing the locking screw and turning the "V MAX" fully counter- clockwise towards the "+" and then retightening the locking screw.

10.4.4 Rate of Opening

The slow opening adjustment can be seen on Page 37, Figure 17. This device is a hydraulic damper which slows down the rate of opening of the second main gas valve to give a smooth main gas ignition. This is preset at the factory at the slowest setting and will need no further adjustment. If a new valve is fitted, then remove the plastic screw on top and with a small screwdriver turn the "V Start" screw fully clockwise towards the "-" and refit the plastic cover.

Where fitted, the start gas valve train is fitted with a pressure regulator and two start gas safety shut off valves. The start gas regulator is used to adjust the burner firing rate during the start gas phase of these models.

10.4.2 Main Gas Valves

See Page 37, Figure 17 for the position of the burner pressure regulator. This must be used to set the burner pressure indicated in the data tables in Section 4.

For high/low or modulating burners, the Dungs gas valve has extra features because it is an air/gas ratio control valve. Please refer to the manufacturer’s instructions for setting the controls.

10.4.3 Throughput Adjuster

These valves have a throughput adjuster fitted to the second main gas valve. See Page 37, Figure 17. This will be factory set at fully open on new

10.5 Combustion Testing (all models)

Combustion quality must be tested to prove correct heater operation. Incorrect results will indicate faults with the installation or appliance.

Combustion testing must be carried out with all covers in place. The flue gas is sampled in the flue, within 1 meter of the heater. The values of CO2 should be between 9.5% and 10.0% for natural gas and 11% for LPG, depending upon the model.

The CO will be up to 80 ppm (0.008%) dry, air free, depending upon the model. Temperature rise of the flue gases above ambient should be approximately 160°C to 180°C. Seal the test hole in the flue after testing.

To alter combustion performance, open/close the combustion air damper to reduce or increase these values. Once adjusted to the optimum combustion setting, lock the air damper into position. Repeat the steps in Section 10.2.6.

37

Image 43
Contents Immediately call your local gas Follow the gas supplier’s Improper installation, adjustment, alteration, serviceManual thoroughly before installing or servicing Supplier after leaving the buildingPage Roberts-Gordon LLC Page Table of Figures Page Product Approval Corrosive Chemicals Clearances to CombustiblesNational Standards and Applicable Codes Ventilation Minimum Required Installation ClearancesCritical Considerations 3.1 Basic Information Location and Suspension All modelsInstallation Clearances and Clearances to Combustibles Front View all models Side View Models 015 Dimension Data PGP & POP Internal HeatersAll models Model 015/020/030 040 050 060/070/080 0100 Dimension Data PGP & POP External HeatersPGP & POP External Heaters Front View Side View Rear ViewVertical and Horizontal Heaters Air Outlet Spigots top view Outlet Spigot DimensionsMax 25 mbar 10 in WG Model 015 020 030 040 050 060 070 080 0100Max 45 mbar 18 in WG Maximum Gross Heat Input Min 17 mbar 6.8 in WG Max 25 mbar 10 in WGLight Fuel Oil Gas Oil Data Technical Data Ecoflam Oil-Fired Burners burner reference GKerosene Data Handling Heater Installation 5.1 GeneralTypical Installation of a Oil-Fired Cabinet Heater Flue Termination Flue Installation 6.1 Flue InstallationJoint with high Rain CollarSilicon Sealer Distribution Ducting AIR Supply 7.1 Air SupplyIsolated Equipment Rooms Building VentilationFuel Piping 4 B. M. Oil Lifter Fuel Oil Supply 8.2.1 Fuel Storage TankFuel Pipes Gravity Feed SystemsPressurised System Installation Duplex System Remote Frost Thermostat Remote ControlsBurner Controls Thermostat Positioning Room Thermostats or Roberts-Gordon ControlCCH Wiring Diagram Gas Models 15-30 floor standing CCH Wiring Diagram Oil Models 15-30 floor standing GAS Burner 7-WAY Plug CCH Wiring Diagram Gas Models 15-30 horizontal mountingOIL Burner 6-WAY Plug CCH Wiring Diagram Oil Models 15-30 horizontal mountingCCH Wiring Diagram Gas Models 40-50 floor standing CCH Wiring Diagram Oil Models 40-50 floor standing Outputs Lockout Reset Signal From Burner RUN Signal CCH Wiring Diagram Oil Models 40-50 horizontal mounting CCH Wiring Diagram Gas Models 60-100 floor standing CCH Wiring Diagram Oil Models 60-100 floor standing CCH Wiring Diagram Gas Models 60-100 horizontal mounting CCH Wiring Diagram Oil Models 60-100 horizontal mounting Page Polarity Test 3 Ø Polarity Test 1 ØLouvers Electrical Checks Before Operating the Heater Initial Setting Commissioning the Burner gas heaters Gas SupplyMotor Starter and Thermal Overload Control Gas-Fired HeatersDescription of Gas-Fired Heater Control Sequence of OperationGas Train Circuit for Dungs Gas Valves all models Rate of Opening Throughput AdjusterCombustion Testing all models Start Gas ValvesCommissioning the Burner Oil Heaters Pressure SwitchComplete the Commissioning High/Low and Modulating BurnersFault Conditions Fault Display MessagesFault Display Error DiagnosisPull out for normal operation Press in for constant fan Modulating OperationHeater Operation high/low or modulating High/Low OperationSimple Fault Finding oil fired heaters Burner Lockout Reset ButtonSimple Fault Finding all models Simple Fault Finding burner faultsIf you smell gas Servicing 12.1 Servicing Instructions Burner Maintenance12.3 Fan/Motor Assembly Maintenance all models Heat Exchanger MaintenanceBurner Conversion Conversion Between Fuels 13.1 GeneralConduct Commissioning procedure as shown on Page 33, Section Conduct Commissioning procedure as shown on Page 33, Section Troubleshoot Ends Oil-Fired Gas-Fired Troubleshooting for Flame Supervision SystemTroubleshooting for Main Fan Circuit 1 Ø Troubleshooting for Solenoid Valves CircuitConduct Commissioning procedure as on Page 33, Section Troubleshooting for Main Fan 3 ØControl Circuit Fuse 10 or 5 A, 1-1/4 long sand filled Burner ComponentsContactor Overloads models 060 toRoberts Gordon Description 015 020 030 040 050 060 070 080 0100 Spare Parts ListPage Page Some objects can catch fire or explode when placed