Briggs & Stratton Generator owner manual Fuel System Selection, Automatic Operation Sequence

Page 18

Briggs & Stratton Power Products Home Standby Generator

Installation, Start-Up and Owner’s Manual

FUEL SYSTEM SELECTION

The engine of your Home Standby Generator is factory calibrated to run on natural gas (NG). It may also be operated on liquid propane (LP).

To configure the fuel system for LP use:

1.LP fuel inlet pressure must be between 11 and 14 inches water column.

2.Set AUTO/OFF/MANUAL switch to OFF.

3.Pull service disconnect from disconnect box.

4.Remove 15 Amp fuse.

5.Change main jet in fuel mixer following instruction sheet provided in LP conversion kit.

6.Reinstall 15 Amp fuse.

9.Connect an RMS AC voltmeter and a frequency meter to check generator output at load side of circuit breaker.Voltage should be 230-240 Volts, frequency should be 62.0 - 62.5 Hz.

10.Check generator output between one generator connection lug and neutral lug, then between other generator connection lug and neutral lug. In both cases, voltage reading should be between 115-120 Volts.

11.Set AUTO/OFF/MANUAL switch to OFF. Engine will shut down.

AUTOMATIC OPERATION SEQUENCE

7.Reinstall service disconnect in disconnect box.

8.Set AUTO/OFF/MANUAL switch to AUTO.

9.Reset exercise timer following instructions “Setting Exercise Timer” on page 19.

The generator is now ready to operate automatically using LP fuel.With a fixed main jet for LP gas, there is no need to perform any engine adjustments for LP operation.

INITIAL START-UP (NO LOAD)

Begin testing the generator without any electrical loads connected, as follows:

1.Set AUTO/OFF/MANUAL switch to OFF.

2.Set generator’s main circuit breaker to OFF (open) position.

3.Install 15 Amp fuse in control panel.

4.Set AUTO/OFF/MANUAL switch to MANUAL.

NOTE: When the Home Standby Generator is started for the very first time, it will require that air in the gaseous fuel lines be purged.This may take a few minutes.

5.DO NOT crank engine for more than 15 seconds, then pause for 15 seconds to reduce heat in starter.

6.Repeat process until engine starts.

7.Listen for unusual noises, vibration or other indications of abnormal operation. Check for oil leaks while the engine runs.

8.Let engine warm up for about five minutes to allow internal temperatures to stabilize.Then, set generators main circuit breaker to ON (or closed) position.

The generator’s control panel houses a logic control circuit board.This control board constantly monitors utility power source voltage. Should that voltage drop below a preset level, control board action will signal the engine to crank and start.

When utility source voltage is restored above a preset voltage level, the engine is signaled to shut down.

The actual system operation is not adjustable and is sequenced by sensors and timers on the control board, as follows:

Utility Voltage Dropout Sensor

This sensor monitors utility source voltage.

If utility source voltage drops below 70 percent of the nominal supply voltage, the sensor energizes a six second timer.

Once the timer has expired, the generator will start.

Utility Voltage Pickup Sensor

This sensor monitors utility power supply voltage.When that voltage is restored above 70 percent of the nominal source voltage, a time delay starts timing and the generator will go to engine cool-down.

Engine Cool-down Timer

When the load is transferred back to the utility power source, the engine cool-down timer starts timing.

The timer will run for about one minute, then the generator will stop.

Minimum generator run time is five minutes.

18

Image 18
Contents Installation Start-Up Table of Contents Important Safety Instructions Do not dispose of battery in a fireOperate generator only outdoors Amp fuse Before working on the equipment Save These Customer Instructions Responsibilities Installer ResponsibilitiesInstallation Assistance IntroductionBattery Know Your Home Standby GeneratorOil Fill Know Your Control Panel AUTO/OFF/MANUALInstallation Procedures Owner OrientationShipment Contents Lifting the GeneratorHome Standby Generator Location Essential Circuits Essential Circuit SelectionDevice Running Watts Fuel Inlet Dimensions Removable Roof and Access DoorDisconnect Box Mounting Guidelines Gaseous Fuel System To Home Standby Fuel ConsumptionFrom Fuel LoadFuel Pipe Sizing 10ft 15ft 20ft 30ft 40ft 50ft 60ft 70ft 80ft 90ft 100ftFuel Comparison Chart Physical Properties Propane Natural GasWithdrawal Rate 32F 20F 10F 30F 40F Wire Connections Before Initial START-UPServicing the Battery Battery ConnectionCharging the Battery Fuel Supply SystemFuel System Selection Automatic Operation SequenceInitial START-UP no Load Setting Exercise Timer Installation InspectionTo perform the Set Exercise procedure Automatic Operation SpecificationsFault Detection System Servicing the SystemNo LED Discharged Battery Number of LED Flashes Fault DescriptionReset Fault Detection System Engine Fail To StartChanging Oil Generator MaintenanceChanging Engine Oil and Filter Changing Oil FilterTo Clean the Generator When Calling the FactoryStorage Troubleshooting Problem Cause CorrectionBriggs & Stratton Power Products Home Standby Generator Schematic Wiring Diagram Exploded View Main Unit Description Parts List Main UnitOptional Accessories Not Illustrated Items Not IllustratedExploded View Enclosure Parts List Enclosure Exploded View Control Panel Parts List Control Panel ADAPTER, Mounting,Alternator Exploded View and Parts List AlternatorHARNESS,Wire DC Charge SCREW, M5 .8 x 10 TaptiteConsumer Use Years Years or YearTabla DE Contenido Manual de Instalación,Arranque y PropietarioSensor de Excitación de Tensión de la Compañía Advertencia PeligroPrecaución Los generadores producen un voltaje muy poderosoResponsabilidades DEL Cliente Conserve Estas InstruccionesIntroducción Responsabilidades DEL InstaladorDe Nivel de Aceite Conozca SU Generador DE ReservaEtiqueta del Motor Tapón de Llenado y Varilla Tapón de Llenado y Varilla de Nivel de Aceite PermiteDisyuntor Interruptor Conozca EL Panel DE ControlFusible de Fusible de 15 Amperios Protege los circuitos de control deOrientación Para EL Propietario Procedimientos DE InstalaciónContenido de la Caja Elevación del GeneradorUbicación del Generador de Reserva Circuitos Fundamentales Selección de los Circuitos FundamentalesDispositivo Vatiaje de Dimensiones de la Entrada de Combustible Directrices de Montaje del Cuadro de DesconexiónTecho y Puerta de Acceso Desmontables Sistema DE Combustible Gaseoso Advertencia El generador de reserva viene preparado de fábrica paraConsumo de Combustible Gas Natural Vapor de PLDimensiones de la Cañería de Combustible Gas Natural peso específico =Propano Líquido PL peso específico = Cuadro de Comparación de Combustibles Propiedades físicas Propano Gas naturalTasa de consumo 32F 20F 10F 30F 40F Conexiones DE Cables Antes DEL Arranque InicialCargar la Batería Conexión de la BateríaSistema de Suministro de Combustible Servicio la BateríaSelección DEL Sistema DE Combustible Arranque Inicial SIN CargaSecuencia DE Operación Automática Ajuste DEL Temporizador DE Ejercicio Inspección Posterior a LA InstalaciónTemporizador de enfriamiento del motor Sistema DE Detección DE EspecificacionesOperación Automática FallasNo se Enciende el LED Batería Descargada Cantidad de Destellos del LED Descripción de la FallaRestablecimiento del Sistema de Detección de Fallas Baja Presión de AceiteCambio del Filtro de Aceite Mantenimiento DEL GeneradorCambio del Aceite del Motor y del Filtro Cambio del AceiteAlmacenamiento Para Limpiar el GeneradorSi Llama a la Fábrica Reparacion DE Averias Garantía Limitada Fonctionnement Automatique Manuel dInstallation, Démarrage et UtilisateurTable DES Matières Entretien DE LA GénératriceAvertissement NE touchez PAS les fils dénudés ou les boîtiers Conservez CES Instructions Responsabilités DE LinstallateurAide À Linstallation IntroductionFAMILIARISEZ-VOUS Avec Votre Génératrice D’ÉTAT D’ATTENTE Filtre à Air Et Jauge dHuile Filtre à lHuileFAMILIARISEZ-VOUS Avec LE Tableau DE Commande 15 AmpèresDisjoncteur Interrupteur Procédures Dinstallation Conseils AU PropriétaireContenu de la Boîte Emplacement du Génératrice d’état d’AttenteDirectives Générales Concernant lEmplacement Soulèvement de la GénératriceCircuits Essentiels Sélection des Circuits EssentielsAppareil Watts Dimensions de lOrifice dAdmission du Combustible Directives dAssemblage du Boîtier de DébranchementToit Amovible et Porte dAccès LE Système DE Combustible Gazeux Avertissement Le génératrice d’état d’attente a été réglé en usine pourConsommation de Combustible Gas Naturel Vapeur PLGrosseur du Tuyau de Combustible Gaz Naturel densité = 0,65Gaz de Pétrole Liquéfié GPL densité = 1,50 Charte de Comparaison des Combustibles Propriétés physiques Propane Gaz naturelRaccords DE Fils Avant LE Démarrage InitialRechargez la Batterie Branchement de la BatterieSystème dAlimentation en Combustible Entretien de la BatterieDémarrage Initial Sans Capteur de Prise en Charge de la Tension de ServiceSélection DU Système DE Combustible Séquence DE Fonctionnement AutomatiqueRéglage DE LA Minuterie DU Cycle Dexercice Vérification InstallationWarranty Registration Box Milwaukee,Wisconsin Minuterie de Refroidissement du MoteurSystème DE Détection DES Pannes CaractéristiquesFonctionnement Automatique Entretien du SystèmeAucun DEL Batterie déchargée Clignotements Du VoyantRéarmement du Système de Détection des Pannes Faible Pression dHuileChangement du filtre à huile Entretien DU GénérateurChangement dHuile à Moteur et de Filtre Vidange de lHuileRemisage Pour Nettoyer le GénérateurCommunications avec le Fabricant Dépannage Remarques Garantie Limitée