Briggs & Stratton Generator Essential Circuits, Essential Circuit Selection, Device Running Watts

Page 10

Briggs & Stratton Power Products Home Standby Generator

Installation, Start-Up and Owner’s Manual

Essential Circuits

Consult with owner to clearly identify the circuits in building that are "essential".

It is important that you understand which circuits the owner wants to include as "Essential Circuits". Depending on the power consumed by these circuits, most or all of them can be switched to the Home Standby Generator for the duration of normal power interruption.

The wattage reference guide shown in Figure 2 will assist the owner with their decision-making process. It provides the wattage used by many ordinary household devices. Use it as a guide when selecting essential circuits. Review this information with the owner and convey any technical considerations that might affect the cost of installation.

Essential Circuit Selection

When selecting the essential circuits that will be switched to “Standby Power,” it is important that the sum of the combined circuit loads does not exceed the wattage/amperage capacity of the generator.To help you with your selection of essential circuits, please consider the following:

Add up the total wattage of all electrical devices to be connected at one time.This total should NOT be greater than the generator’s wattage capacity.

The rated wattage of lights can be taken from light bulbs.The rated wattage of tools, appliances and motors can usually be found on a data plate or decal affixed to the device.

If the appliance, tool or motor does not give wattage, multiply volts times the ampere rating to determine watts (Volts x Amps = Watts).

Some electric motors (induction types) require about three times more watts of power for starting than for running.This surge lasts for only a few seconds. Be sure you allow for this high starting wattage when selecting electrical devices that will be energized by the Home Standby Generator:

Figure the watts required to start the largest motor.

Add that to the total running watts of all other connected loads.

This Briggs & Stratton Home Standby Generator complies with the following “stationary standby power rating”:

The standby power rating is applicable for supplying power for the duration of normal power interruption. NO sustained overload capability is available for this rating.

Figure 2 — Wattage Reference Guide

 

Device

Running

 

Watts

 

 

 

Air Conditioner (12,000 Btu)*

1700

 

Air Conditioner (24,000 Btu)*

3800

 

Air Conditioner (40,000 Btu)*

6000

 

Battery Charger (20 Amp)

500

 

Circular Saw (6-1/2")

800 to 1000

 

Clothes Dryer (Electric)*

5750

 

Clothes Dryer (Gas)*

700

 

Clothes Washer*

1150

 

Coffee Maker

1750

 

Compressor (1 HP)*

2000

 

Compressor (1/2 HP)*

1400

 

Compressor (3/4 HP)*

1800

 

Curling Iron

700

 

Dehumidifier*

650

 

Electric Blanket

400

 

Electric Range (per element)

1500

 

Electric Skillet

1250

 

Freezer*

700

 

Furnace Fan (3/5 HP)*

875

 

Garage Door Opener*

500 to 750

 

Hair Dryer

1200

 

Hand Drill

250 to 1100

 

Iron

1200

 

Jet Pump*

800

 

Light Bulb

100

 

Microwave Oven

700 to 1000

 

Milk Cooler*

1100

 

Oil Burner on Furnace

300

 

Oil Fired Space Heater (140,000 Btu)

400

 

Oil Fired Space Heater (30,000 Btu)

150

 

Oil Fired Space Heater (85,000 Btu)

225

 

Radio

50 to 200

 

Refrigerator

700

 

Slow Cooker

200

 

Submersible Pump (1 HP)*

2000

 

Submersible Pump (1/2 HP)*

1500

 

Submersible Pump (1-1/2 HP)*

2800

 

Sump Pump*

800 to 1050

 

Table Saw (10")*

1750 to 2000

 

Television

200 to 500

 

Toaster

1000 to 1650

*Allow three (3) times listed watts for starting device

10

Image 10
Contents Installation Start-Up Table of Contents Do not dispose of battery in a fire Important Safety InstructionsOperate generator only outdoors Amp fuse Before working on the equipment Save These Customer Instructions Responsibilities Installer ResponsibilitiesInstallation Assistance IntroductionKnow Your Home Standby Generator BatteryOil Fill Know Your Control Panel AUTO/OFF/MANUALInstallation Procedures Owner OrientationLifting the Generator Shipment ContentsHome Standby Generator Location Essential Circuit Selection Essential CircuitsDevice Running Watts Removable Roof and Access Door Fuel Inlet DimensionsDisconnect Box Mounting Guidelines Gaseous Fuel System To Home Standby Fuel ConsumptionFrom Fuel LoadFuel Pipe Sizing 10ft 15ft 20ft 30ft 40ft 50ft 60ft 70ft 80ft 90ft 100ftPhysical Properties Propane Natural Gas Fuel Comparison ChartWithdrawal Rate 32F 20F 10F 30F 40F Wire Connections Before Initial START-UPServicing the Battery Battery ConnectionCharging the Battery Fuel Supply SystemAutomatic Operation Sequence Fuel System SelectionInitial START-UP no Load Installation Inspection Setting Exercise TimerTo perform the Set Exercise procedure Automatic Operation SpecificationsFault Detection System Servicing the SystemNo LED Discharged Battery Number of LED Flashes Fault DescriptionReset Fault Detection System Engine Fail To StartChanging Oil Generator MaintenanceChanging Engine Oil and Filter Changing Oil FilterWhen Calling the Factory To Clean the GeneratorStorage Troubleshooting Problem Cause CorrectionBriggs & Stratton Power Products Home Standby Generator Schematic Wiring Diagram Exploded View Main Unit Description Parts List Main UnitOptional Accessories Not Illustrated Items Not IllustratedExploded View Enclosure Parts List Enclosure Exploded View Control Panel Parts List Control Panel ADAPTER, Mounting,Alternator Exploded View and Parts List AlternatorHARNESS,Wire DC Charge SCREW, M5 .8 x 10 TaptiteConsumer Use Years Years or YearManual de Instalación,Arranque y Propietario Tabla DE ContenidoSensor de Excitación de Tensión de la Compañía Advertencia PeligroPrecaución Los generadores producen un voltaje muy poderosoResponsabilidades DEL Cliente Conserve Estas InstruccionesIntroducción Responsabilidades DEL InstaladorDe Nivel de Aceite Conozca SU Generador DE ReservaEtiqueta del Motor Tapón de Llenado y Varilla Tapón de Llenado y Varilla de Nivel de Aceite PermiteDisyuntor Interruptor Conozca EL Panel DE ControlFusible de Fusible de 15 Amperios Protege los circuitos de control deOrientación Para EL Propietario Procedimientos DE InstalaciónElevación del Generador Contenido de la CajaUbicación del Generador de Reserva Selección de los Circuitos Fundamentales Circuitos FundamentalesDispositivo Vatiaje de Directrices de Montaje del Cuadro de Desconexión Dimensiones de la Entrada de CombustibleTecho y Puerta de Acceso Desmontables Sistema DE Combustible Gaseoso Advertencia El generador de reserva viene preparado de fábrica paraConsumo de Combustible Gas Natural Vapor de PLGas Natural peso específico = Dimensiones de la Cañería de CombustiblePropano Líquido PL peso específico = Propiedades físicas Propano Gas natural Cuadro de Comparación de CombustiblesTasa de consumo 32F 20F 10F 30F 40F Conexiones DE Cables Antes DEL Arranque InicialCargar la Batería Conexión de la BateríaSistema de Suministro de Combustible Servicio la BateríaArranque Inicial SIN Carga Selección DEL Sistema DE CombustibleSecuencia DE Operación Automática Inspección Posterior a LA Instalación Ajuste DEL Temporizador DE EjercicioTemporizador de enfriamiento del motor Sistema DE Detección DE EspecificacionesOperación Automática FallasNo se Enciende el LED Batería Descargada Cantidad de Destellos del LED Descripción de la FallaRestablecimiento del Sistema de Detección de Fallas Baja Presión de AceiteCambio del Filtro de Aceite Mantenimiento DEL GeneradorCambio del Aceite del Motor y del Filtro Cambio del AceitePara Limpiar el Generador AlmacenamientoSi Llama a la Fábrica Reparacion DE Averias Garantía Limitada Fonctionnement Automatique Manuel dInstallation, Démarrage et UtilisateurTable DES Matières Entretien DE LA GénératriceAvertissement NE touchez PAS les fils dénudés ou les boîtiers Conservez CES Instructions Responsabilités DE LinstallateurAide À Linstallation IntroductionFAMILIARISEZ-VOUS Avec Votre Génératrice D’ÉTAT D’ATTENTE Filtre à Air Et Jauge dHuile Filtre à lHuile15 Ampères FAMILIARISEZ-VOUS Avec LE Tableau DE CommandeDisjoncteur Interrupteur Procédures Dinstallation Conseils AU PropriétaireContenu de la Boîte Emplacement du Génératrice d’état d’AttenteDirectives Générales Concernant lEmplacement Soulèvement de la GénératriceSélection des Circuits Essentiels Circuits EssentielsAppareil Watts Directives dAssemblage du Boîtier de Débranchement Dimensions de lOrifice dAdmission du CombustibleToit Amovible et Porte dAccès LE Système DE Combustible Gazeux Avertissement Le génératrice d’état d’attente a été réglé en usine pourConsommation de Combustible Gas Naturel Vapeur PLGaz Naturel densité = 0,65 Grosseur du Tuyau de CombustibleGaz de Pétrole Liquéfié GPL densité = 1,50 Charte de Comparaison des Combustibles Propriétés physiques Propane Gaz naturelRaccords DE Fils Avant LE Démarrage InitialRechargez la Batterie Branchement de la BatterieSystème dAlimentation en Combustible Entretien de la BatterieDémarrage Initial Sans Capteur de Prise en Charge de la Tension de ServiceSélection DU Système DE Combustible Séquence DE Fonctionnement AutomatiqueRéglage DE LA Minuterie DU Cycle Dexercice Vérification InstallationWarranty Registration Box Milwaukee,Wisconsin Minuterie de Refroidissement du MoteurSystème DE Détection DES Pannes CaractéristiquesFonctionnement Automatique Entretien du SystèmeAucun DEL Batterie déchargée Clignotements Du VoyantRéarmement du Système de Détection des Pannes Faible Pression dHuileChangement du filtre à huile Entretien DU GénérateurChangement dHuile à Moteur et de Filtre Vidange de lHuilePour Nettoyer le Générateur RemisageCommunications avec le Fabricant Dépannage Remarques Garantie Limitée