Bryant ASPAS1BBL025 Generator Location, Basic Standby Electric System, Generator Mounting Support

Page 11

Section 2 — Installation

Bryant Liquid-cooled 25 kW Generator

AGRICULTURAL WIRING HANDBOOK, obtainable from the Food and Energy Council, 909 University Avenue, Columbia, MO, 65201.

ASAE EP-364.2, INSTALLATION AND MAINTE-

NANCE OF FARM STANDBY ELECTRIC POWER, available from the American Society of Agricultural Engineers, 2950 Niles Road, St. Joseph, MI 49085.

A52.1, AMERICAN NATIONAL STANDARD FOR CHIMNEYS, FIREPLACES AND VENTING SYS- TEMS, available from the American National Standard Institute, 1430 Broadway, New York, N.Y. 10018.

2.2GENERATOR LOCATION

Install the generator set, in its protective enclosure outdoors, where adequate cooling and ventilating air always is available. Consider these factors:

2.4BASIC STANDBY ELECTRIC

SYSTEM

Figure 2.1 shows a schematic diagram of a basic standby electric system. Both the UTILITY power supply and the STANDBY GENERATOR output are connected to an approved transfer switch. The trans- fer switch is required by electrical code and serves the following functions:

Permits the LOAD circuits to be connected to only one power supply at a time.

Prevents electrical backfeed between the generator and the UTILITY power circuits.

Notice that both the STANDBY and the UTILITY power supplies to the transfer switch are protected against overload by a main line circuit breaker.

Install the unit where air inlet and outlet openings will not become obstructed by leaves, grass, snow, etc. If prevailing winds will cause blowing or drift- ing, consider using a windbreak to protect the unit.

Install the generator on high ground where water levels will not rise and endanger it.

Allow sufficient room on all sides of the generator for maintenance and servicing. Five feet allowance of space is recommended on all sides. Local codes may supercede this recommendation.

Where strong prevailing winds blow from one direction, face the generator air inlet openings into the prevailing winds.

Install the generator as close as possible to the transfer switch. This reduces the length of wiring and conduit.

Install the generator as close as possible to the fuel supply, to reduce the length of piping. HOWEVER, REMEMBER THAT LAWS OR CODES MAY REG- ULATE THE DISTANCE.

2.3GENERATOR MOUNTING AND

SUPPORT

Retain the generator compartment to a concrete slab with 1/4-inch masonry type anchor bolts. Be sure the bolts are long enough to retain the compartment. The slab should be at least six inches thick and should extend beyond the enclosure to a distance of at least three inches on all sides.

Figure 2.1 – Basic Standby Electric System

NOTE:

Bryant recommends the use of a Bryant transfer switch in conjunction with this generator.

2.5EMERGENCY CIRCUIT ISOLATION

METHOD

This prevents overloading the generator by keeping electrical loads below the wattage/amperage capacity of the generator. If the generator is powering only crit- ical loads, within the wattage/amperage capacity, dur- ing utility power outages, consider using the emer- gency circuit isolation method.

Critical electrical loads are grouped together and wired into a separate “Emergency Distribution Panel.” Load circuits powered by that panel are with- in the wattage/amperage capacity of the generator set. The transfer switch must meet the following require- ments:

It must have an ampere rating equal to the total amperage rating of the emergency distribution panel circuit.

It must be installed between the building’s main distribution panel and the emergency distribution panel.

Bryant 9

Image 11
Contents Page Your Bryant Dealer is ‹ Operation and Maintenance‹ HOW to Obtain Service IntroductionTable of Contents General Hazards ‹ Standards Index Fire HazardsGenerator AC Connection Systems Transfer SwitchGenerator Automatic System OperationGenerator Fuel System ‹ 1.7.1 LOW OIL Pressure Switch‹ 1.7.2 High Coolant Temperature Switch ‹ 1.7.3 LOW Coolant Level SwitchUnpacking SpecificationsEngine OIL Recommendations Fuel Consumption‹ 2.1.2 Other Published Standards Before InstallationCoolant Recommendations ‹ 2.1.1 Nfpa StandardsEmergency Circuit Isolation Method Generator LocationBasic Standby Electric System Generator Mounting SupportGrounding the Generator Transfer Switch Signal ConnectionsBattery Installation Total Circuit Isolation Method‹ 2.11.1 Prior to Initial START-UP Preparation Before START-UP‹ 2.10.1 Vented Batteries Control Console Components ‹ 3.1.4 5 AMP Fuse ‹ 3.1.5 SET Exercise Time Switch‹ 3.1.3 15 AMP Fuse ‹ 3.1.6 System Ready LEDWeekly Exercise Cycle Manual Transfer START-UP Engine Governor AdjustmentsRetransfer and Shutdown Automatic OperationOFF SET Exercise Time To SET Exerciser Time Control Board DIP Switch SettingsExhaust Manifold Procedure Intake Manifold ProcedureCylinder Head Procedure Checking Fluid Levels Cooling SystemOverload Protection for Engine DC Electrical System ‹ 4.8.7 Inspect Exhaust System ‹ 4.8.11 Changing the Engine AIR Cleaner‹ 4.8.5 Check Engine Coolant Level ‹ 4.8.6 Perform Visual Inspection‹ 4.9.2 Battery Miscellaneous Maintenance‹ 4.8.13 Coolant Change ‹ 4.9.3 Battery Maintenance ‹ 4.9.1 Cleaning the GeneratorPeriodic Replacement Parts ‹ 4.9.4 Battery ReplacementService Maintenance Interval Information Scheduled MaintenanceLevel Maintenance Level Problem Cause Correction Troubleshooting PointsBryant Liquid-cooled 25 kW Generator Bryant Liquid-cooled 25 kW Generator Bryant Liquid-cooled 25 kW Generator Electrical Data Electrical Data Electrical Data Electrical Data Electrical Data Electrical Data Electrical Data Electrical Data Anelp Ttbo MO Boot Battery Cable Hold Down Battery 2.5L FordBattery Post Cover Black Battery Post Cover REDPanel for Access Roof ACO & STD Encl 2.5L Assembly BASE-DOOR Ground WireGRD Wire Assy 99HSB Assembly Cover AccessBryant Screw Hhtt M5-0.8 X 12 BP Assy 2A 12V UL BatterySwitch ROC Dpst 125V SPD Assy Wire Fuse Holder19 20 Spring Bushing Tank Coolant RecoveryEngine 2.5L Ford STARTER, 12 VoltARBC0 Retu E1028A RO19I/N SSA .Y Bracket Fuel Regulator Body Carburetor AssemblyCover AIR Cleaner GASKET, AIR Cleaner AdapterSead L Rotor 39030AD1 HSB Tecum Rotor 390 15KW 1P Direct HSB 2.5L FordRotor 390 20KW 1P Direct HSB 2.5L Ford Rotor 390 25KW 1P Direct HSB 2.5L FordSaddle 2 Inch Pipe Muffler OUTPipe Exhaust 2.5L Ford Muffler 2.5L FordHarn GOV 2.5L Ford Housing Governor ConnectorCover Connector Housing ASM Motor StepperVENTURI, 16 FAN 2.5L Ford Radiator Support Radiator 2.5L AL TALRADIATOR, 2.5L Ford HOSE, 2.5L Ford LowerInstallation Diagram PURCHASER’S/OWNER’S Warranty Responsibilities Your Warranty Rights and ObligationsMANUFACTURER’S Emission Control System Warranty Coverage Emission Related Parts Include the Following Emission Control System WarrantyWarranty Schedule