Bryant ASPAS1BBL025 owner manual Troubleshooting Points, Problem Cause Correction

Page 26

Section 5 — Troubleshooting

Bryant Liquid-cooled 25 kW Generator

TROUBLESHOOTING POINTS

PROBLEM

CAUSE

CORRECTION

Engine won’t crank.

1.

15 amp fuse blown.

1.

Replace fuse.

 

2.

Loose or corroded or defective

2.

Tighten, clean or replace

 

 

battery cables.

 

battery cables as necessary.

 

3.

Defective starter contactor.

3.

Replace contactor.

 

4.

Defective starter motor.

4.

Replace starter motor.

 

5.

Dead or Defective Battery.

5.

Remove, change or replace battery.

 

6.

5 amp fuse blown.

6.

Replace fuse.

 

 

 

 

 

Engine cranks but won't start

1.

Out of fuel.

1.

Replenish fuel.

 

2.

Fuel solenoid (FS) is defective

2.

Replace solenoid.

 

3.

Open Wire #14A from Engine Control

3.

Reconnect wire.

 

 

circuit board.

 

 

 

4.

Spark plugs defective.

4.

Clean, regap or replace plugs.

 

 

 

 

 

Engine starts hard, runs rough.

1.

Flame arrestor (air cleaner) plugged or

1.

Clean or replace as needed.

 

 

damaged.

 

 

 

2.

Plugged fuel line.

2.

Unclog fuel line.

 

3.

Defective spark plugs.

3.

Clean, regap or replace plugs.

 

 

 

 

 

Engine starts then shuts down.

1.

Engine oil level is low.

1.

Check oil and add oil as needed.

 

2.

Engine is overheated.

2.

Check cooling system for leaks.

 

3.

Defective Low Oil Pressure Switch

3.

Replace switch.

 

4.

Defective Coolant Temperature Switch

4.

Replace switch.

 

5.

Defective Control Module circuit board.

5.

Replace board.

 

6.

Coolant Level is Low.

6.

Repair leak - Add coolant.

 

7.

Defective Low Coolant Level Switch

7.

Replace Switch.

 

 

 

 

AUTO/OFF/MANUAL Switch at OFF,

1. Defective AUTO/OFF/MANUAL switch

1.

Replace switch.

engine continues to run

2. Open/disconnected wire #15A between

2.

Reconnect/close wire.

 

 

AUTO/OFF/MANUAL switch and Control

 

 

 

 

Module circuit board.

 

 

 

3.

Defective Control Module circuit board

3.

Replace board.

 

 

 

 

No AC output from generator.

1. Check main line circuit breaker.

1.

Reset to ON or CLOSED.

 

2.

Check circuit breaker & fuses.

2.

Reset and replace, if necessary.

 

3.

Transfer switch set to NORMAL position

3.

Set to GENERATOR position.

 

4.

Generator internal failure.

4.

Contact a dealer.

 

5.

Thermal circuit breaker open.

5.

Auto-reset - Wait 5 min. and

 

 

 

 

attempt restart.

NOTE:

Under normal operating conditions, if repair of generator set or replacement of any parts is necessary dur- ing the warranty period, you must contact a dealer. Failure to have the repair or replacement performed by a Bryant dealer will result in non-coverage of warranty repair cost.

24 Bryant

Image 26
Contents Page Introduction ‹ Operation and Maintenance‹ HOW to Obtain Service Your Bryant Dealer isTable of Contents General Hazards Fire Hazards ‹ Standards IndexAutomatic System Operation Transfer SwitchGenerator Generator AC Connection Systems‹ 1.7.3 LOW Coolant Level Switch ‹ 1.7.1 LOW OIL Pressure Switch‹ 1.7.2 High Coolant Temperature Switch Generator Fuel SystemSpecifications UnpackingFuel Consumption Engine OIL Recommendations‹ 2.1.1 Nfpa Standards Before InstallationCoolant Recommendations ‹ 2.1.2 Other Published StandardsGenerator Mounting Support Generator LocationBasic Standby Electric System Emergency Circuit Isolation MethodTotal Circuit Isolation Method Transfer Switch Signal ConnectionsBattery Installation Grounding the Generator‹ 2.11.1 Prior to Initial START-UP Preparation Before START-UP‹ 2.10.1 Vented Batteries Control Console Components ‹ 3.1.6 System Ready LED ‹ 3.1.5 SET Exercise Time Switch‹ 3.1.3 15 AMP Fuse ‹ 3.1.4 5 AMP FuseAutomatic Operation Manual Transfer START-UP Engine Governor AdjustmentsRetransfer and Shutdown Weekly Exercise CycleControl Board DIP Switch Settings OFF SET Exercise Time To SET Exerciser TimeExhaust Manifold Procedure Intake Manifold ProcedureCylinder Head Procedure Checking Fluid Levels Cooling SystemOverload Protection for Engine DC Electrical System ‹ 4.8.6 Perform Visual Inspection ‹ 4.8.11 Changing the Engine AIR Cleaner‹ 4.8.5 Check Engine Coolant Level ‹ 4.8.7 Inspect Exhaust System‹ 4.9.1 Cleaning the Generator Miscellaneous Maintenance‹ 4.8.13 Coolant Change ‹ 4.9.3 Battery Maintenance ‹ 4.9.2 Battery‹ 4.9.4 Battery Replacement Periodic Replacement PartsScheduled Maintenance Service Maintenance Interval InformationLevel Maintenance Level Troubleshooting Points Problem Cause CorrectionBryant Liquid-cooled 25 kW Generator Bryant Liquid-cooled 25 kW Generator Bryant Liquid-cooled 25 kW Generator Electrical Data Electrical Data Electrical Data Electrical Data Electrical Data Electrical Data Electrical Data Electrical Data Anelp Ttbo MO Battery Post Cover RED Hold Down Battery 2.5L FordBattery Post Cover Black Boot Battery CablePanel for Access Assembly Cover Access Assembly BASE-DOOR Ground WireGRD Wire Assy 99HSB Roof ACO & STD Encl 2.5LBryant Assy Wire Fuse Holder Assy 2A 12V UL BatterySwitch ROC Dpst 125V SPD Screw Hhtt M5-0.8 X 12 BP19 20 STARTER, 12 Volt Tank Coolant RecoveryEngine 2.5L Ford Spring BushingARBC0 Retu E1028A RO19I/N SSA .Y GASKET, AIR Cleaner Adapter Body Carburetor AssemblyCover AIR Cleaner Bracket Fuel RegulatorSead L Rotor 390 25KW 1P Direct HSB 2.5L Ford Rotor 390 15KW 1P Direct HSB 2.5L FordRotor 390 20KW 1P Direct HSB 2.5L Ford Rotor 39030AD1 HSB TecumMuffler 2.5L Ford Pipe Muffler OUTPipe Exhaust 2.5L Ford Saddle 2 InchASM Motor Stepper Housing Governor ConnectorCover Connector Housing Harn GOV 2.5L FordHOSE, 2.5L Ford Lower Support Radiator 2.5L AL TALRADIATOR, 2.5L Ford VENTURI, 16 FAN 2.5L Ford RadiatorInstallation Diagram PURCHASER’S/OWNER’S Warranty Responsibilities Your Warranty Rights and ObligationsMANUFACTURER’S Emission Control System Warranty Coverage Emission Control System Warranty Emission Related Parts Include the FollowingWarranty Schedule