Bryant ASPAS1BBL025 Miscellaneous Maintenance, ‹ 4.9.1 Cleaning the Generator, ‹ 4.9.2 Battery

Page 21

Section 4 — Maintenance

Bryant Liquid-cooled 25 kW Generator

‹ 4.8.13 COOLANT CHANGE

 

‹ 4.9.3 BATTERY MAINTENANCE

Every year, have a Bryant dealer drain, flush and refill the cooling system. See “Specifications” for cool- ing system recommendations.

4.9MISCELLANEOUS MAINTENANCE

‹4.9.1 CLEANING THE GENERATOR

Keep the generator as clean and as dry as possible. Dirt and moisture that accumulates on internal gen- erator windings have an adverse effect on insulation resistance.

Periodically clean generator exterior surfaces. A soft brush may be used to loosen caked on dirt. Use a vacuum system or dry, low pressure air to remove any accumulations of dirt. The generator is housed inside an all-weather enclosure, clean the enclosure with a soft, damp cloth or sponge and water.

Once each year have the generator cleaned and inspected by a dealer. That dealer will use dry, low pressure air to clean internal windings. Parts inside the control console should be cleaned and inspected at this time as well.

Finally, have the insulation resistance of stator and rotor windings checked. If insulation resistances are excessively low, the generator may require drying.

‹4.9.2 BATTERY

All lead-acid storage batteries discharge when not in use. Refer to specific instructions and warnings that accompany the battery. If such information is not available, observe the following precautions when handling a battery:

DO NOT use jumper cables and a booster battery to crank or start the generator engine.

DO NOT recharge a weak battery while it is installed in the generator. Remove battery from generator and recharge in a well-ventilated area, away from fuel vapors, sparks, heat or flames.

Battery electrolyte fluid is an extremely caustic sulfuric solution that can cause severe burns. DO NOT permit fluid to contact eyes, skin, clothing, painted surfaces, wiring insulation, etc. If any bat- tery fluid is spilled, flush the affected area with clear water immediately.

Always wear safety glasses, rubber apron and gloves when handling a battery.

Batteries give off explosive hydrogen gas while charging. The gas can form an explosive mixture around the battery for several hours after charging. Any spark, heat or flames can ignite the gas and cause an explosion which can shatter the battery, causing blindness or other serious injury.

The battery should be inspected per Section 4.7, Scheduled Maintenance. The following procedure should be followed for inspection:

1.Inspect the battery posts and cables for tightness and corrosion. Tighten and clean as necessary.

2.Check the battery fluid level of unsealed batteries and, if necessary, fill with DISTILLED WATER ONLY. DO NOT USE TAP WATER IN BATTERIES.

3.Have the state of charge and condition checked. This should be done with an automotive-type bat- tery hydrometer.

DANGER

Storage batteries give off explosive hydrogen gas. This gas can form an explosive mixture around the battery for several hours after charging. The slightest spark can ignite the gas and cause an explosion. Such an explosion can shatter the battery and cause blindness or other injury. Any area that houses a storage battery must be properly ventilated. Do not allow smoking, open flame, sparks or any spark producing tools or equipment near the battery.

Battery electrolyte fluid is an extremely corro- ! sive sulfuric acid solution that can cause severe

burns. Do not permit fluid to contact eyes, skin, clothing, painted surfaces, etc. Wear protective goggles, protective clothing and gloves when handling a battery. If fluid is spilled, flush the affected area immediately with clear water.

Do not use any jumper cables or booster bat- ! tery to crank and start the generator engine. If

the battery has completely discharged, remove it from the generator for recharging.

Be sure the AUTO/OFF/MANUAL switch is set to ! the OFF position, before connecting the battery cables. If the switch is set to AUTO or MANUAL,

the generator can crank and start as soon as the battery cables are connected.

Be sure the utility power supply is turned off, or sparking may occur at the battery posts as the cables are attached and cause an explosion.

Bryant 19

Image 21
Contents Page ‹ HOW to Obtain Service ‹ Operation and MaintenanceIntroduction Your Bryant Dealer isTable of Contents General Hazards ‹ Standards Index Fire HazardsGenerator Transfer SwitchAutomatic System Operation Generator AC Connection Systems‹ 1.7.2 High Coolant Temperature Switch ‹ 1.7.1 LOW OIL Pressure Switch‹ 1.7.3 LOW Coolant Level Switch Generator Fuel SystemUnpacking SpecificationsEngine OIL Recommendations Fuel ConsumptionCoolant Recommendations Before Installation‹ 2.1.1 Nfpa Standards ‹ 2.1.2 Other Published StandardsBasic Standby Electric System Generator LocationGenerator Mounting Support Emergency Circuit Isolation MethodBattery Installation Transfer Switch Signal ConnectionsTotal Circuit Isolation Method Grounding the GeneratorPreparation Before START-UP ‹ 2.10.1 Vented Batteries‹ 2.11.1 Prior to Initial START-UP Control Console Components ‹ 3.1.3 15 AMP Fuse ‹ 3.1.5 SET Exercise Time Switch‹ 3.1.6 System Ready LED ‹ 3.1.4 5 AMP FuseRetransfer and Shutdown Manual Transfer START-UP Engine Governor AdjustmentsAutomatic Operation Weekly Exercise CycleOFF SET Exercise Time To SET Exerciser Time Control Board DIP Switch Settings Intake Manifold Procedure Cylinder Head Procedure Exhaust Manifold Procedure Cooling System Overload Protection for Engine DC Electrical SystemChecking Fluid Levels ‹ 4.8.5 Check Engine Coolant Level ‹ 4.8.11 Changing the Engine AIR Cleaner‹ 4.8.6 Perform Visual Inspection ‹ 4.8.7 Inspect Exhaust System‹ 4.8.13 Coolant Change ‹ 4.9.3 Battery Maintenance Miscellaneous Maintenance‹ 4.9.1 Cleaning the Generator ‹ 4.9.2 BatteryPeriodic Replacement Parts ‹ 4.9.4 Battery ReplacementService Maintenance Interval Information Scheduled MaintenanceLevel Maintenance Level Problem Cause Correction Troubleshooting PointsBryant Liquid-cooled 25 kW Generator Bryant Liquid-cooled 25 kW Generator Bryant Liquid-cooled 25 kW Generator Electrical Data Electrical Data Electrical Data Electrical Data Electrical Data Electrical Data Electrical Data Electrical Data Anelp Ttbo MO Battery Post Cover Black Hold Down Battery 2.5L FordBattery Post Cover RED Boot Battery CablePanel for Access GRD Wire Assy 99HSB Assembly BASE-DOOR Ground WireAssembly Cover Access Roof ACO & STD Encl 2.5LBryant Switch ROC Dpst 125V SPD Assy 2A 12V UL BatteryAssy Wire Fuse Holder Screw Hhtt M5-0.8 X 12 BP19 20 Engine 2.5L Ford Tank Coolant RecoverySTARTER, 12 Volt Spring BushingARBC0 Retu E1028A RO19I/N SSA .Y Cover AIR Cleaner Body Carburetor AssemblyGASKET, AIR Cleaner Adapter Bracket Fuel RegulatorSead L Rotor 390 20KW 1P Direct HSB 2.5L Ford Rotor 390 15KW 1P Direct HSB 2.5L FordRotor 390 25KW 1P Direct HSB 2.5L Ford Rotor 39030AD1 HSB TecumPipe Exhaust 2.5L Ford Pipe Muffler OUTMuffler 2.5L Ford Saddle 2 InchCover Connector Housing Housing Governor ConnectorASM Motor Stepper Harn GOV 2.5L FordRADIATOR, 2.5L Ford Support Radiator 2.5L AL TALHOSE, 2.5L Ford Lower VENTURI, 16 FAN 2.5L Ford RadiatorInstallation Diagram Your Warranty Rights and Obligations MANUFACTURER’S Emission Control System Warranty CoveragePURCHASER’S/OWNER’S Warranty Responsibilities Emission Related Parts Include the Following Emission Control System WarrantyWarranty Schedule