NOTE: Do not use teflon tape on gas line pipe thread. A flexible sealant is recommended.

A minimum of 7" W.C. and a maximum of 14" W.C. upstream pressure under load, and no load conditions must be provided for natural gas or a minimum of 12" W.C. and a maximum of 14" for propane gas.

GAS PRESSURE REGULATOR

The gas pressure regulator is preset at 4" W. C. for natural gas, and 11" W. C. for propane gas. The pressure at the gas valve, taken with a manometer, should be about 3.7" W. C. natural gas (3.9" W.C. for Low NOx) and 10.5" W. C. propane gas. If an adjustment is needed, remove

seal and turn adjustment screw clockwise

to

increase pressure or counter-clockwise

to

decrease pressure.

 

ELECTRONIC IGNITION GAS VALVES-CONTINUED

Fig # 9328

Fig # 9329

 

Gas

 

Pressure

 

Adjustment

Robertshaw 7200

Robertshaw 7000 BDER

Model 185

Model 265-335

Gas

Fig # 9327Pressure

Adjustment

Robertshaw 7000 DERHC

Model 405

PIPE SIZING FOR GAS CONNECTIONS

Fig. # 8149Fig. # 9365

ATMOSHPERIC

LOW NOx

GAS PRESSURE ADJUSTMENT LOCATIONS

MILLIVOLT GAS VALVES

Gas

Pressure

Adjustment

Fig # 9263

Robertshaw 7000

Models 185 thru 405

ELECTRONIC IGNITION GAS VALVES

Gas

Pressure

Adjustment

Honeywell VR8304

 

Models 185 thru 405

Fig # 9264

 

Low NOx units are not available in propane.

PLUMBING FOR WATER CONNECTIONS

LOCATION

The RP 2100 heater requires water flow and positive pressure to fire and operate properly. It must therefore be installed downstream of the discharge side of the filter pump. A typical installation is plumbed as follows:

1.The inlet side of the filter is plumbed directly to the discharge side of the filter pump;

2.The outlet side of the filter is then plumbed to the inlet of the heater; and

3.The outlet of the heater is plumbed to the return line to the pool or spa. The pump, filter and heater are thus plumbed in series.

15

Image 15
Contents What to do if YOU Smell GAS Installation Operating InstructionsTo Whom IT MAY Concern Contents Water START-UP ProceduresBefore START-UP BurnersMillivolt System Lighting InstructionsTo Turn OFF GAS to Appliance Electronic Ignitions Systems What to do if YOU Smell GASOperating Instructions Visual Inspection Maintenance and Care ProceduresWater Pressure Switch After START-UPColdweatheroperation Basic Tips if Heater will not FirePool & SPA Water Chemistry AUTOMATICCHLORINATORSANDCHEMICALFEED- ERSStandard Unit Asme Unit General SpecificationsReceiving Equipment Winterizing the Pool & SPA HeaterInstallation Instructions Feet horizontally Heater with Outdoor Stackless TOPIndoor Heater Vent TERMINAL/INDOOR Stack InstallationCombustion AIR Indoor Units Only Specifications and DimensionsGAS Supply Connections Vent PipingPlumbing for Water Connections GAS Pressure Adjustment LocationsGAS Pressure Regulator Pipe Sizing for GAS ConnectionsINLET/OUTLETHEADER Auxiliary Bypass Valve AdjustmentFlow Rates Model Pipe Size MIN.GPM MAX.GPM ConnectionsFig. #2004 Pressure Relief Valve InstallationRP2100+ Heat Exchanger Reversal Procedure Jaco Fitting Atmospheric ElectricalwiringMillivolt System Electronic Intermittent Ignition Device System IIDWiring Diagram Millivolt Units With Mechanical Thermostat Wiring Diagram KEYWiring Diagram IID Units atmospheric Wiring Diagram IID Units Low NOx CONTROLS/ADJUSTMENTS/REPLACEMENTS Servicing InstructionsGeneral Location of Controls Display Faults Electronic ControlsDisplay Status RP2100 Remote Control Installation Three Wire TWO FunctionTWO Wire ONE Function ON/OFF only Pressure Switch Flame ROLL-OUT Safety SwitchHigh Limits Honeywell Pilot Robertshaw Pilot Combustion Chamber Removal Tube Cleaning ProcedureDesooting Procedure Unitherm Governor U.G. ReplacementOperation START-UP Procedures S8610BBurneradjustment Flame ROLL-OUT Safety SwitchAddenda LOW NOX Heaters Mechanicalforqualifiedservicepersonnelonly Trouble Shooting GuideRaypak Pool or SPA Heater Electrical Check with MV GAS Valve Electrical Standing Pilot MillivoltElectrical Electronic Ignition IID Troubleshooting Honeywell S8600Page RAYPAK,INC Replacement Parts ListPage Honeywell IID Atmospheric units Pilot AssembliesPage Page Page Limitedwarranty Raypakresidentialswimmingpoolandspaheaters