Aqua Products manual Troubleshooting Honeywell S8600, Electrical Electronic Ignition IID

Page 34

ELECTRICAL (ELECTRONIC IGNITION IID)

WARNING HIGH VOLTAGE

For qualified Technicians ONLY

NOTE: Some heaters may be equipped with an ignition module that shuts off pilot gas if pilot fails to light. To reset, interrupt power to heater.

START

TURN GAS SUPPLY OFF.

TURN THERMOSTAT

(CONTROLLER) TO CALL

FOR HEAT

POWER TO MODULE

(24 V NOMINAL)

YES

Intermittent Pilot System

TROUBLESHOOTING HONEYWELL S8600

NOTE:Before troubleshooting, familiarize yourself with the startup and checkout procedure.

NO

Check line voltage power, low voltage transformer, limit controller, thermostat

(controller) and wiring.

SPARK ACROSS

IGNITER/SENSOR GAP

YES

NO

Pull ignition lead and check spark at module.

Spark Okay?

YES

Check ignition cable, ground wiring, ceramic insulator and gap, and correct.

Check boot of the ignition cable for signs of melting or buckling. Take protective action to shield cable and boot from excessive temperatures.

TURN GAS SUPPLY ON

PILOT BURNER LIGHTS?

YES

SPARK STOPS WHEN

PILOT IS LIT?

YES

MAIN BURNER LIGHTS?

YES

SYSTEM RUNS UNTIL CALL FOR HEAT ENDS?

YES

 

 

• Check that all manual gas valves are open, supply tubing and pressures are good,

NO

 

 

 

 

and pilot burner orifice is not blocked.

 

 

Check electrical connections between module and pilot operator on gas control.

Check for 24 Vac across PV-MV/PV terminals on module. If voltage is okay, replace gas control; if not, replace module.

 

 

 

NOTE:If S8600H goes into lockout, reset system. Lockout is used on L.P.G. models.

 

 

 

 

 

 

 

 

Check continuity of ignition cable and ground wire.

NO

 

 

 

 

 

Clean flame rod.

 

 

 

Check electrical connections between flame rod and module.

 

 

 

Check for cracked ceramic flame rod insulator.

 

 

 

Check that pilot flame covers flame rod and is steady and blue.

 

 

 

Adjust pilot flame.

 

 

 

If problem persists, replace module.

 

 

 

 

 

 

 

 

Check for 24 Vac across MV-MV/PV terminals. If no voltage, replace module.

NO

 

 

Check electrical connections between module and gas control. If okay, replace

 

 

 

 

 

 

gas valve or gas control operator, i.e. pilot gas valve, flow switch etc.

NOTE: IF S8600H goes into lockout, reset system.

NO

• Check continuity of ignition cable and ground wire.

 

NOTE: If ground is poor or erratic, shutdowns may occur occasionally even though operation is normal at the time of checkout.

Check that pilot flame covers flame rod and is steady and blue.

If checks are okay, replace module.

CALL FOR HEAT ENDS

SYSTEM SHUTS OFF?

YES

TROUBLESHOOTING

ENDS

NO

 

Check for proper thermostat (controller) operation.

 

 

 

Remove MV lead at module; if valve closes, recheck temperature controller and

 

 

 

 

 

wiring; if not, replace gas valve.

Repeat procedure until troublefree operation is obtained.

34

Image 34
Contents Installation Operating Instructions What to do if YOU Smell GASTo Whom IT MAY Concern Contents Burners START-UP ProceduresBefore START-UP WaterLighting Instructions Millivolt SystemTo Turn OFF GAS to Appliance What to do if YOU Smell GAS Electronic Ignitions SystemsOperating Instructions After START-UP Maintenance and Care ProceduresWater Pressure Switch Visual InspectionAUTOMATICCHLORINATORSANDCHEMICALFEED- ERS Basic Tips if Heater will not FirePool & SPA Water Chemistry ColdweatheroperationWinterizing the Pool & SPA Heater General SpecificationsReceiving Equipment Standard Unit Asme UnitInstallation Instructions Heater with Outdoor Stackless TOP Feet horizontallyVent TERMINAL/INDOOR Stack Installation Indoor HeaterSpecifications and Dimensions Combustion AIR Indoor Units OnlyVent Piping GAS Supply ConnectionsPipe Sizing for GAS Connections GAS Pressure Adjustment LocationsGAS Pressure Regulator Plumbing for Water ConnectionsConnections Auxiliary Bypass Valve AdjustmentFlow Rates Model Pipe Size MIN.GPM MAX.GPM INLET/OUTLETHEADERPressure Relief Valve Installation Fig. #2004RP2100+ Heat Exchanger Reversal Procedure Jaco Fitting Electronic Intermittent Ignition Device System IID ElectricalwiringMillivolt System AtmosphericWiring Diagram KEY Wiring Diagram Millivolt Units With Mechanical ThermostatWiring Diagram IID Units atmospheric Wiring Diagram IID Units Low NOx Servicing Instructions CONTROLS/ADJUSTMENTS/REPLACEMENTSGeneral Location of Controls Electronic Controls Display FaultsDisplay Status Three Wire TWO Function RP2100 Remote Control InstallationTWO Wire ONE Function ON/OFF only Flame ROLL-OUT Safety Switch Pressure SwitchHigh Limits Honeywell Pilot Robertshaw Pilot Unitherm Governor U.G. Replacement Tube Cleaning ProcedureDesooting Procedure Combustion Chamber RemovalFlame ROLL-OUT Safety Switch START-UP Procedures S8610BBurneradjustment OperationAddenda LOW NOX Heaters Trouble Shooting Guide MechanicalforqualifiedservicepersonnelonlyElectrical Standing Pilot Millivolt Raypak Pool or SPA Heater Electrical Check with MV GAS ValveTroubleshooting Honeywell S8600 Electrical Electronic Ignition IIDPage Replacement Parts List RAYPAK,INCPage Pilot Assemblies Honeywell IID Atmospheric unitsPage Page Page Limitedwarranty Raypakresidentialswimmingpoolandspaheaters