Aqua Products manual RP2100 Remote Control Installation, Three Wire TWO Function

Page 26

RP2100 REMOTE CONTROL INSTALLATION

CAUTION: Before installing remote controls to the RP2100 Digital Heater, read the following:

The Raypak RP 2100 Digital Heater is remote ready in most cases. The digital liquid crystal (LCD) display shows the actual pool temperature, operating status, and service codes (See examples below). The touch pad on the control panel allows you to select the desired pool or spa temperature. It also indicates when a remote system is controlling the heater by displaying REM in the display. When connecting the RP2100 Digital to a remote system, identify whether it is a two or three wire remote system. Select the appropriate instruction listed below to properly install the remote to the heater.

OFF Mode

Heating in the

Heating in the Remote Mode

 

POOL Mode

SPA Mode

Remote Wiring Instructions 1.Turn off power to the heater. 2.Turn off gas to the heater.

3.Remove the four screws on the side of the heater holding the control panel (see figure # 9375)

Fig # 9375

4.Lay control panel forward towards you. This will provide access to the back of the temperature control board.

5.Install the remote wire harness on the P7 terminal (see figure # 9373).

Important Installation Notes for

Remote or external wiring configuration

Remote wiring must be run in separate conduit.

Remote wiring must not be run parallel to High Voltage lines.

For runs of under 30 feet, remote wiring should have stranded conductors with a minimum of 22 AWG, 600V, cable twisting 1.5 to 2.5 and jacketed.

For runs over 30 feet, the conductors should be a minimum of 20 AWG, 600V, cable twisting 1.5 to 2.5 inch lay that is shielded and jacketed.

Maximum cable length of 200 feet.

For both Two and Three wire remote systems, the provided P-7 wiring connector must be utilized. Please refer to the wiring instructions.

Two-Wire Remote Systems:

To remotely select either pool or spa operation (3-wire/2- function) requires 3 wires to be connected to the heater. A switch mechanism that will provide contact closure between HIGH/SPA or LOW/POOL and common, needs to be supplied. This mechanism can be a 3-way switch or any other remote control system that provides dry contact closure for either setting. See remote wiring instructions on this page.

Two or Three-Wire Remote Operation:

To remotely select a single operating ON/OFF mode (2 wire/single function) requires two wires to be connected to the heater. This requires a switching mechanism that can be a 2-way switch or a remote control system with a single dry contact closure. See remote wiring instruc- tions on this page.

NOTE: Do Not connect wiring to fireman switch location.

Fig # 9373

THREE WIRE TWO FUNCTION

6.For a 3-wire/2 function configuration, connect the HIGH/SPA wire to the orange wire with the black stripe; the LOW/POOL wire to the black wire with the orange stripe; and the common wire to the yellow wire with the black stripe (see figure # 9373).

7.For the 2-wire/1 function configuration, connect the orange/black and black/orange wires to one contact and the yellow/black wire to the other contact (see figure # 9374).

8.Verify the mode button is in the "OFF" position.

Fig # 9374

TWO WIRE ONE FUNCTION ON/OFF ONLY

26

Image 26
Contents Installation Operating Instructions What to do if YOU Smell GASTo Whom IT MAY Concern Contents Burners START-UP ProceduresBefore START-UP WaterTo Turn OFF GAS to Appliance Millivolt SystemLighting Instructions Operating Instructions Electronic Ignitions SystemsWhat to do if YOU Smell GAS After START-UP Maintenance and Care ProceduresWater Pressure Switch Visual InspectionAUTOMATICCHLORINATORSANDCHEMICALFEED- ERS Basic Tips if Heater will not FirePool & SPA Water Chemistry ColdweatheroperationWinterizing the Pool & SPA Heater General SpecificationsReceiving Equipment Standard Unit Asme UnitInstallation Instructions Heater with Outdoor Stackless TOP Feet horizontallyVent TERMINAL/INDOOR Stack Installation Indoor HeaterSpecifications and Dimensions Combustion AIR Indoor Units OnlyVent Piping GAS Supply ConnectionsPipe Sizing for GAS Connections GAS Pressure Adjustment LocationsGAS Pressure Regulator Plumbing for Water ConnectionsConnections Auxiliary Bypass Valve AdjustmentFlow Rates Model Pipe Size MIN.GPM MAX.GPM INLET/OUTLETHEADERPressure Relief Valve Installation Fig. #2004RP2100+ Heat Exchanger Reversal Procedure Jaco Fitting Electronic Intermittent Ignition Device System IID ElectricalwiringMillivolt System AtmosphericWiring Diagram KEY Wiring Diagram Millivolt Units With Mechanical ThermostatWiring Diagram IID Units atmospheric Wiring Diagram IID Units Low NOx General Location of Controls CONTROLS/ADJUSTMENTS/REPLACEMENTSServicing Instructions Display Status Display FaultsElectronic Controls TWO Wire ONE Function ON/OFF only RP2100 Remote Control InstallationThree Wire TWO Function High Limits Pressure SwitchFlame ROLL-OUT Safety Switch Honeywell Pilot Robertshaw Pilot Unitherm Governor U.G. Replacement Tube Cleaning ProcedureDesooting Procedure Combustion Chamber RemovalFlame ROLL-OUT Safety Switch START-UP Procedures S8610BBurneradjustment OperationAddenda LOW NOX Heaters Trouble Shooting Guide MechanicalforqualifiedservicepersonnelonlyElectrical Standing Pilot Millivolt Raypak Pool or SPA Heater Electrical Check with MV GAS ValveTroubleshooting Honeywell S8600 Electrical Electronic Ignition IIDPage Replacement Parts List RAYPAK,INCPage Pilot Assemblies Honeywell IID Atmospheric unitsPage Page Page Limitedwarranty Raypakresidentialswimmingpoolandspaheaters