SECTION 5 / TROUBLE SHOOTING GUIDE

MECHANICAL(FORQUALIFIEDSERVICEPERSONNELONLY)

IMPORTANT NOTICE These instructions are primarily intended for the use of qualified personnel specifically trained and experienced in the installation of this type of heating equipment and related system components. Installation and service personnel may be required by some states to be licensed. Persons not qualified shall not attempt to install this equipment nor attempt repairs according to these instructions.

PROBLEM

CAUSE

 

SOLUTION

 

 

 

 

Harmonics, or whining noise

U.G. inoperative

Check movement by putting in hot water (110°F or hig

 

 

 

 

higher). If no movement, replace.

 

*Debris or restriction in system

Locate the restriction and remove. Flush system

 

 

 

 

and clean.

 

 

*Debris in gas line

Remove debris or blow out gas line.

 

Low

flow

Scale forming in heat exchanger - clean heat

 

 

 

 

exchanger and check pool pH and total alkalinity.

 

 

 

 

 

 

Heater going on and off

Dirty

filter

Backwash filter.

 

continously

Low water level in pool

Raise water level.

 

External bypass setting out of

 

 

 

 

adjustment

Adjust

bypass

 

 

*Pressure switch out of

 

 

 

 

adjustment

Adjust

pressure

switch

 

 

 

Liming or scale forming on

Pool water

Recommended pH should be between 7.4 and 7.8

heat exchanger

 

 

 

Total alkalinity 100-150 PPM maximum.

 

 

 

 

Hardness 150-400 PPM maximum.

Sooting

High

flow

rates

Reduce by adding manual bypass valve. Adjust

 

 

 

 

manual bypass valve until heater outlet water

 

 

 

 

temperature is between 105° and 110°F.

 

U.G. Inoperative

Check movement by putting in hot water (110°F

 

 

 

 

or higher). If no movement, replace.

 

*Air

starvation

Refer to installation instructions.

 

*Improper venting

Follow recommended installation instructions.

 

*Insects or debris clogging

 

 

 

 

burner intake ports

Clean burners.

 

 

 

 

 

 

Pilot outage

Low

gas

pressure

Adjust gas pressure.

 

Restricted

pilot

Clean pilot.

 

 

Weak pilot generator

Replace pilot.

 

 

 

 

 

 

Yellow lazy flame

Low

gas

pressure

Adjust gas pressure.

 

*Insects or debris clogging

 

 

 

 

burner intake ports

Clean burners.

 

 

 

 

 

 

Outer jacket very hot

*Broken refractory caused by

 

 

 

(paint blistered)

shipping damage or improper

 

 

 

 

combustion

Replace refractory panels.

 

Excessive sooting of heat

 

 

 

 

exchanger

Determine cause of sooting & correct.

 

 

 

 

Takes long time to heat

Calculate temperature in °/hr

Heat rise (°/hr.)=

Htr. output_____

pool or spa.

 

 

 

 

 

Pool gallonage x 8.33

 

 

 

 

or refer to heater sizing chart. This does not take into

 

 

 

 

account heat loss due to weather.

 

Filter not running long enough

Reset time clock.

 

 

Dirty

filter

Clean filter.

 

 

Gas line or meter undersized

Refer to installation instructions.

 

 

 

Liming

Bypassing too much water

Inspect bypass for movement, if no movement,

 

 

 

 

replace.

 

 

U.G. not functioning

Replace if no movement when heated.

 

 

 

 

Leaking at well.

Overacid

Replace well and maintain water chemistry properly.

 

 

 

 

Leaking at heat exchanger.

Overacid

Replace heat exchanger and maintain chemistry

 

 

 

 

properly.

 

 

 

 

 

 

Gasket brittle and leaking -

Heater running after pump

 

 

 

(overheated).

shuts off

See pressure switch adjustment.

 

Refractory damage

Replace refractory.

 

Sooted heater

Determine cause of sooting and correct.

 

 

 

 

 

Combustion fan not running

Fan

relay

Replace fan relay

 

Fan

 

Loose connection or failed motor

 

Burned motor

Incorrect wiring,

replace blower

 

 

 

 

 

 

 

(* Indicates symptom usually occurs on initial start-up.)

32

Image 32
Contents Installation Operating Instructions What to do if YOU Smell GASTo Whom IT MAY Concern Contents START-UP Procedures Before START-UPBurners WaterTo Turn OFF GAS to Appliance Millivolt SystemLighting Instructions Operating Instructions Electronic Ignitions SystemsWhat to do if YOU Smell GAS Maintenance and Care Procedures Water Pressure SwitchAfter START-UP Visual InspectionBasic Tips if Heater will not Fire Pool & SPA Water ChemistryAUTOMATICCHLORINATORSANDCHEMICALFEED- ERS ColdweatheroperationGeneral Specifications Receiving EquipmentWinterizing the Pool & SPA Heater Standard Unit Asme UnitInstallation Instructions Heater with Outdoor Stackless TOP Feet horizontallyVent TERMINAL/INDOOR Stack Installation Indoor HeaterSpecifications and Dimensions Combustion AIR Indoor Units OnlyVent Piping GAS Supply ConnectionsGAS Pressure Adjustment Locations GAS Pressure RegulatorPipe Sizing for GAS Connections Plumbing for Water ConnectionsAuxiliary Bypass Valve Adjustment Flow Rates Model Pipe Size MIN.GPM MAX.GPMConnections INLET/OUTLETHEADERPressure Relief Valve Installation Fig. #2004RP2100+ Heat Exchanger Reversal Procedure Jaco Fitting Electricalwiring Millivolt SystemElectronic Intermittent Ignition Device System IID AtmosphericWiring Diagram KEY Wiring Diagram Millivolt Units With Mechanical ThermostatWiring Diagram IID Units atmospheric Wiring Diagram IID Units Low NOx General Location of Controls CONTROLS/ADJUSTMENTS/REPLACEMENTSServicing Instructions Display Status Display FaultsElectronic Controls TWO Wire ONE Function ON/OFF only RP2100 Remote Control InstallationThree Wire TWO Function High Limits Pressure SwitchFlame ROLL-OUT Safety Switch Honeywell Pilot Robertshaw Pilot Tube Cleaning Procedure Desooting ProcedureUnitherm Governor U.G. Replacement Combustion Chamber RemovalSTART-UP Procedures S8610B BurneradjustmentFlame ROLL-OUT Safety Switch OperationAddenda LOW NOX Heaters Trouble Shooting Guide MechanicalforqualifiedservicepersonnelonlyElectrical Standing Pilot Millivolt Raypak Pool or SPA Heater Electrical Check with MV GAS ValveTroubleshooting Honeywell S8600 Electrical Electronic Ignition IIDPage Replacement Parts List RAYPAK,INCPage Pilot Assemblies Honeywell IID Atmospheric unitsPage Page Page Limitedwarranty Raypakresidentialswimmingpoolandspaheaters