Emerson IS-WEB485ADPT Open the Terminal Emulation Interface TCP/IP Connection, Winsock

Page 12

Configuration Overview

3.3 Open the Terminal Emulation Interface - TCP/IP Connection

To access configuration using terminal emulation software with an Ethernet connection to the Web card:

1.Open a terminal emulation application, such as HyperTerminal.

To do this:

Click the Start button, then Programs, Accessories, Communications and finally HyperTerminal.

2.In the Connection Description window, enter a name for the connection—for example, GXT2U—then click OK.

3.In the Connect To window:

Choose TCP/IP (Winsock) from the Connect Using drop-down list.

Enter the IP address or hostname of the Web card—for example, 192.168.0.125—in the Host Address box, then click OK.

Name

TCP/IP

(Winsock)

4.When the message at right appears in the HyperTerminal window, press the Enter key.

5.Enter the Administrator username and password (both are case- sensitive):

a.Login (username—default is Liebert)

b.Password (default is Liebert)

NOTE

RTCS v2.96.00 Telnet server

Service Port Manager Active <Esc> Ends Session

Login: Liebert

Password: ********

For security, change the default username and password (see 5.7 - Change Username / Password).

6.In the Main Menu, enter the number that corresponds to your choice. Refer to 3.1 - Guide to Configuration for details on each function.

7.After making changes, return to the Main Menu and choose Exit and Save to reboot the Web card and put your changes into effect (see 3.6 - Saving Changes and Reinitializing the Web Card).

Main Menu

----------

1:System Information

2:IP Network Settings

3:Messaging

4:Factory Settings

5:Firmware Updates

q:Quit and abort changes

x:Exit and save

Please select a key ?>

8

Image 12
Contents Liebert IntelliSlot Web Cards Page Table of Contents Tables Support InformationImportant Safety Instructions Compatibility With Liebert Equipment IntroductionLiebert IntelliSlot card communication protocols Password Protection Web SupportSnmp Support Liebert Nform SupportInstall a Liebert IntelliSlot Web Card-Non-Adapter Version InstallationPrepare the Card for Configuration Communication settingsInstall a Liebert IntelliSlot Web/485 Card With Adapter Select Enabled ApplicationGuide to Configuration Configuration OverviewConfiguration interfaces Guide to configuration detailsConnection settings Open the Terminal Emulation Interface Serial ConnectionName Open the Terminal Emulation Interface TCP/IP Connection WinsockOpen the Telnet Interface TelnetOpen the Web Interface Saving Changes and Reinitializing the Web CardTerminal Emulation Serial or TCP/IP Connection / Telnet Web InterfaceSystem Information System information identifiersNetwork Settings Network Settings menu guideBoot/IP Settings Boot/IP settings rangeDomain Name Server DNS Settings Domain Name Server settingsManagement Protocol Management protocol rangesWeb Interface Snmp Communications Menu Display/Modify CommunitiesSnmp communications menu Display/Modify Trap Communities 10.0.0.7 read public2Specify Web Server Settings Web server settingsWeb Server Click on View Certificate Certificate Path tab ViewInstall Certificate Automatically selectInstall Security Certificates Internet Explorer 7 or later Certificate Error View CertificatesContinue to this website Certificate Import Wizard opens. Click Next Configure tab Edit Telnet Telnet ServerTime Sntp Menu Time Server parameters Sntp Time Sync RateChange Username / Password Factory default passwordsUsername and password guidelines Reset Authentication to Factory Defaults Configure tab Edit Messaging MessagingMessaging menu guide Mail Configuration Mail configuration guideSMS Configuration Configure tab EditSMS configuration guide Customize Messages Terminal Emulation Serial or TCP/IP Connec- tion / TelnetMail and SMS message guidelines Configure tab Edit Customize Message Message Consolidation Time LimitReset to Factory Defaults Factory SettingsConfigure tab Factory Defaults Reset To Factory Defaults Liebert DS Local Node Settings for Multiple Cards Factory default MAC addressesMonitoring Liebert Equipment Monitor and Control Functions WEB onlyWeb Interface Only Controlling Liebert Equipment Control tab Control Operations Click to view in right panelLiebert GXT2U example Output DS example Setpoints Event Log Event Log ControlsLinks Scroll through Event Log tabView Web Card Information Support InformationSupport tab Listing in right panel Summary Events and Parameters Support tab Listing in right panel Events or ParametersAppendix a Firmware Updates Introduction Estimated Time to Download the Firmware Upgrade FileTable A1 Overview of the upgrade process OverviewTable A3 Communication settings Open the Terminal Emulation Interface Serial ConnectionOpen the Terminal Emulation Interface TCP/IP Connection Open the Telnet Interface Open the Web InterfaceDownload the Firmware Upgrade File to the Computer Choose a Method to Install the Firmware Upgrade Install the Firmware UpgradeUpdating the Firmware Http WEB Method Specify Tftp Server and Upgrade Filename Table A4 Firmware update settings TftpOpen a Connection to the Card Reconnect to the CardBegin the Upgrade Process Tftp Method Web InterfaceTable A5 Firmware update settings Web Updating the Firmware Xmodem Serial Method 115200 bps Call menu Configure button Connect a Cable to the Serial PortsOpen a Terminal Emulation Connection Change the Baud Rate toDownload the First Firmware Update File Download the Second and Third Firmware Update FilesComplete the Upgrade and Restore Communication Rate Call menu 9600 bps Configure buttonUpdating the Firmware Xmodem Serial Method A13 Updating the Firmware Xmodem Serial Method A14 Page Ne t ItiTi n That