Factory Settings
7.2Liebert DS - Local Node Settings for Multiple Cards
If you use two cards of the same type with the Liebert DS, you will need to change the local node set- ting of one card. These steps apply only when both cards are the same type, either:
•Two Liebert IntelliSlot Web cards (P/N
•Two Liebert IntelliSlot 485 cards (P/N
Terminal Emulation (Serial or TCP/IP Connection) / Telnet
To access local node settings:
1.Choose Factory Settings from the Main Menu.
2.Choose Advanced Communication Settings from the Factory Settings Menu.
3.Choose Local Node Settings from the Advanced Communication Settings Menu.
4.Choose Node 1 from the Local Node Settings Menu, then use the following guide to make changes.
If there are two Liebert IntelliSlot Web cards or two Liebert IntelliSlot 485 cards, you must change the address of one card (see Table 22):
•For the Liebert IntelliSlot Web card, the default address is 1. For two Web cards, set the address of the second card to 2.
•For the Liebert IntelliSlot 485 card, the default address is 2. For two 485 cards, set the address of the second card to 1.
Table 22 Factory default MAC addresses
Liebert DS
Factory Settings Menu
1:Advanced Communication Settings
2:Reset to Factory Defaults
<ESC>: Cancel menu level Please select a key ?>
Liebert DS
Advanced Communication Settings Menu
1:Local Node Settings
2:Managed Device Settings
2:Reset to Default
<ESC>: Cancel menu level Please select a key ?>
Liebert DS
Local Node Settings Menu
1:Node ID: 1
2:Communication Rate: 38400
3:Maximum Master Address: 3
4:Maximum Retry Count: 5
5:Retry Interval(sec): 5
<ESC>: Cancel menu level Please select a key ?>
|
| Factory Default | Set Node 1 Address |
Liebert IntelliSlot Card | Part Number | MAC Address | of Second Card to: |
|
|
|
|
Liebert IntelliSlot Web | 0x01 | 2 | |
|
|
|
|
Liebert IntelliSlot 485 | 0x02 | 1 | |
|
|
|
|
35