Emerson IS-WEB485ADPT Install a Liebert IntelliSlot Web Card-Non-Adapter Version, Installation

Page 8

Installation

2.0 INSTALLATION

! WARNING

Only a qualified service professional should install these products. Liebert recommends having a Liebert Services representative perform the installation in large UPSs. Contact Liebert Services at 1-800-LIEBERT (1-800-543-2378).

2.1Install a Liebert IntelliSlot Web Card—Non-Adapter Version

Follow these steps to install a Liebert IntelliSlot Web card (non-adapter version—P/N IS-WEBCARD, IS-WEBLB and IS-WEBLBDS).

1.Locate the Liebert IntelliSlot option bay on your Liebert equipment—You might need to remove a plastic cover.

2.Insert the Liebert IntelliSlot Web Card into the Liebert IntelliSlot bay.

3.Secure the card with the supplied screws.

4.Connect an Ethernet cable.

DHCP: The card ships with DHCP service enabled. The MAC address is on a sticker on the top of the card.

OR

Static IP: To assign a static IP address or hostname, use terminal emulation software to configure the card, as described in Sections 2.1.1 and 2.1.2.

2.1.1Connect the Cable

1.Locate the blue serial configuration cable (null modem) that shipped with the card.

2.Connect the configuration cable to the DB-9 port on the card and to a COM port on your PC.

2.1.2Prepare the Card for Configuration

Use terminal emulation software, such as Microsoft® HyperTerminal, to open a connection to the card with the settings in Table 2.

Table 2 Communication settings

Baud Rate:

9600

 

 

Data Bits:

8

 

 

Parity:

None

 

 

Stop Bits:

1

 

 

Flow Control:

None

 

 

Press the Enter key for the Main Menu, above right.

Select IP Network Settings, then Boot/IP Settings and follow the instructions to enter an IP ADDRESS, NETMASK and GATEWAY.

Press Esc to return to the Main Menu.

Choose Exit and Save to save your changes and reboot the card.

NOTE

When installing the card in a Liebert NX, configure the communication port of NX to 2400 baud. See the NX user manual for details.

4

Image 8
Contents Liebert IntelliSlot Web Cards Page Table of Contents Tables Support InformationImportant Safety Instructions Liebert IntelliSlot card communication protocols Compatibility With Liebert EquipmentIntroduction Password Protection Web SupportSnmp Support Liebert Nform SupportInstall a Liebert IntelliSlot Web Card-Non-Adapter Version InstallationPrepare the Card for Configuration Communication settingsInstall a Liebert IntelliSlot Web/485 Card With Adapter Select Enabled ApplicationGuide to Configuration Configuration OverviewConfiguration interfaces Guide to configuration detailsName Connection settingsOpen the Terminal Emulation Interface Serial Connection Open the Terminal Emulation Interface TCP/IP Connection WinsockOpen the Telnet Interface TelnetOpen the Web Interface Saving Changes and Reinitializing the Web CardTerminal Emulation Serial or TCP/IP Connection / Telnet Web InterfaceSystem Information System information identifiersNetwork Settings Network Settings menu guideBoot/IP Settings Boot/IP settings rangeDomain Name Server DNS Settings Domain Name Server settingsManagement Protocol Management protocol rangesWeb Interface Snmp communications menu Snmp Communications MenuDisplay/Modify Communities Display/Modify Trap Communities 10.0.0.7 read public2Web Server Specify Web Server SettingsWeb server settings Click on View Certificate Certificate Path tab ViewInstall Certificate Automatically selectContinue to this website Install Security Certificates Internet Explorer 7 or laterCertificate Error View Certificates Certificate Import Wizard opens. Click Next Time Sntp Menu Configure tab Edit TelnetTelnet Server Time Server parameters Sntp Time Sync RateUsername and password guidelines Change Username / PasswordFactory default passwords Reset Authentication to Factory Defaults Messaging menu guide Configure tab Edit MessagingMessaging Mail Configuration Mail configuration guideSMS Configuration Configure tab EditSMS configuration guide Mail and SMS message guidelines Customize MessagesTerminal Emulation Serial or TCP/IP Connec- tion / Telnet Configure tab Edit Customize Message Message Consolidation Time LimitConfigure tab Factory Defaults Reset To Factory Defaults Reset to Factory DefaultsFactory Settings Liebert DS Local Node Settings for Multiple Cards Factory default MAC addressesWeb Interface Only Monitoring Liebert EquipmentMonitor and Control Functions WEB only Liebert GXT2U example Output DS example Setpoints Controlling Liebert EquipmentControl tab Control Operations Click to view in right panel Event Log Event Log ControlsLinks Scroll through Event Log tabSupport tab Listing in right panel Summary View Web Card InformationSupport Information Events and Parameters Support tab Listing in right panel Events or ParametersAppendix a Firmware Updates Introduction Estimated Time to Download the Firmware Upgrade FileTable A1 Overview of the upgrade process OverviewOpen the Terminal Emulation Interface TCP/IP Connection Table A3 Communication settingsOpen the Terminal Emulation Interface Serial Connection Open the Telnet Interface Open the Web InterfaceDownload the Firmware Upgrade File to the Computer Updating the Firmware Http WEB Method Choose a Method to Install the Firmware UpgradeInstall the Firmware Upgrade Specify Tftp Server and Upgrade Filename Table A4 Firmware update settings TftpOpen a Connection to the Card Reconnect to the CardBegin the Upgrade Process Tftp Method Web InterfaceTable A5 Firmware update settings Web Updating the Firmware Xmodem Serial Method 115200 bps Call menu Configure button Connect a Cable to the Serial PortsOpen a Terminal Emulation Connection Change the Baud Rate toDownload the First Firmware Update File Download the Second and Third Firmware Update FilesComplete the Upgrade and Restore Communication Rate Call menu 9600 bps Configure buttonUpdating the Firmware Xmodem Serial Method A13 Updating the Firmware Xmodem Serial Method A14 Page Ne t ItiTi n That