Emerson IS-WEB485ADPT installation manual Install a Liebert IntelliSlot Web/485 Card With Adapter

Page 9

Installation

2.2Install a Liebert IntelliSlot Web/485 Card With Adapter

! WARNING

Risk of electric shock. Can cause equipment damage, injury or death.

Service and maintenance work must be performed only by properly trained and qualified personnel and in accordance with applicable regulations and manufacturers’ specifications.

Opening or removing the covers to any equipment may expose personnel to lethal voltages within the unit even when it is apparently not operating and the input wiring is disconnected from the electrical source.

Check the circuits with a voltmeter before beginning installation.

Follow these steps to install a Liebert IntelliSlot Web/485 Card With Adapter (P/N IS-WEB485ADPT).

Locate the adapter mounting location in your Liebert equipment.

Secure the Liebert IntelliSlot Web/485 Card With Adapter with the supplied screws.

Connect the equipment's communication cable to the TB1 terminal block or P1 on the card (see the user manual for the Liebert power or cooling unit for details).

Connect a Modbus (RS-485) cable to the TB2 terminal block.

Connect an input power supply cable to Pins 1 & 2 on the TB3 terminal block; Pin 1 is at the far left, and Pin 2 is the middle pin.

TB3 (P1: +) (P2: -)

(P3: NC) P1 is on left end of terminal block.

TB2 (P1: +) (P2: -);

P1 is at the right side of the terminal block.

TB1 (P1: +; P2: -); P1 is at the right side of the terminal block.

P1

Network Port for NMS

and Web Access

DB-9 Port

MAC Address

2.2.1Connect the Cable

1.Locate the blue serial configuration cable (null modem) that shipped with the card.

2.Connect the configuration cable to the DB-9 port on the card and to a COM port on your PC.

2.2.2Prepare the Card for Configuration

1.Use terminal emulation software, such as HyperTerminal, to open a direct connection to the card with the settings in Table 3.

2.Press the Enter key for the Main Menu.

3.Select 485 Network Settings to access the communications settings.

4.Select Enabled Application.

5.Select Modbus Server to enable the Modbus application.

Table 3 Communication settings

Baud Rate:

9600

Data Bits:

8

Parity:

None

Stop Bits:

1

Flow Control:

None

6.At the next screen, select Server ID (the default Server ID is 1, but may be any number up to 255).

7.Press Esc to return to the Main Menu.

8.Select IP Network Settings, then Boot/IP Settings and follow the instructions to enter an IP ADDRESS, NETMASK and GATEWAY.

9.Press Esc to return to the Main Menu.

10.Choose Exit and Save to save your changes and reboot the card.

NOTE

When installing the card in a Liebert NX, configure the communication port of NX to 2400 baud. See the NX user manual for details.

5

Image 9
Contents Liebert IntelliSlot Web Cards Page Table of Contents Support Information TablesImportant Safety Instructions Compatibility With Liebert Equipment IntroductionLiebert IntelliSlot card communication protocols Web Support Password ProtectionSnmp Support Liebert Nform SupportInstallation Install a Liebert IntelliSlot Web Card-Non-Adapter VersionPrepare the Card for Configuration Communication settingsSelect Enabled Application Install a Liebert IntelliSlot Web/485 Card With AdapterConfiguration Overview Guide to ConfigurationConfiguration interfaces Guide to configuration detailsConnection settings Open the Terminal Emulation Interface Serial ConnectionName Winsock Open the Terminal Emulation Interface TCP/IP ConnectionTelnet Open the Telnet InterfaceSaving Changes and Reinitializing the Web Card Open the Web InterfaceTerminal Emulation Serial or TCP/IP Connection / Telnet Web InterfaceSystem information identifiers System InformationNetwork Settings menu guide Network SettingsBoot/IP settings range Boot/IP SettingsDomain Name Server settings Domain Name Server DNS SettingsManagement protocol ranges Management ProtocolWeb Interface Snmp Communications Menu Display/Modify CommunitiesSnmp communications menu 10.0.0.7 read public2 Display/Modify Trap CommunitiesSpecify Web Server Settings Web server settingsWeb Server Certificate Path tab View Click on View CertificateAutomatically select Install CertificateInstall Security Certificates Internet Explorer 7 or later Certificate Error View CertificatesContinue to this website Certificate Import Wizard opens. Click Next Configure tab Edit Telnet Telnet ServerTime Sntp Menu Sntp Time Sync Rate Time Server parametersChange Username / Password Factory default passwordsUsername and password guidelines Reset Authentication to Factory Defaults Configure tab Edit Messaging MessagingMessaging menu guide Mail configuration guide Mail ConfigurationConfigure tab Edit SMS ConfigurationSMS configuration guide Customize Messages Terminal Emulation Serial or TCP/IP Connec- tion / TelnetMail and SMS message guidelines Message Consolidation Time Limit Configure tab Edit Customize MessageReset to Factory Defaults Factory SettingsConfigure tab Factory Defaults Reset To Factory Defaults Factory default MAC addresses Liebert DS Local Node Settings for Multiple CardsMonitoring Liebert Equipment Monitor and Control Functions WEB onlyWeb Interface Only Controlling Liebert Equipment Control tab Control Operations Click to view in right panelLiebert GXT2U example Output DS example Setpoints Event Log Controls Event LogLinks Scroll through Event Log tabView Web Card Information Support InformationSupport tab Listing in right panel Summary Support tab Listing in right panel Events or Parameters Events and ParametersEstimated Time to Download the Firmware Upgrade File Appendix a Firmware Updates IntroductionTable A1 Overview of the upgrade process OverviewTable A3 Communication settings Open the Terminal Emulation Interface Serial ConnectionOpen the Terminal Emulation Interface TCP/IP Connection Open the Web Interface Open the Telnet InterfaceDownload the Firmware Upgrade File to the Computer Choose a Method to Install the Firmware Upgrade Install the Firmware UpgradeUpdating the Firmware Http WEB Method Table A4 Firmware update settings Tftp Specify Tftp Server and Upgrade FilenameOpen a Connection to the Card Reconnect to the CardTftp Method Web Interface Begin the Upgrade ProcessTable A5 Firmware update settings Web Updating the Firmware Xmodem Serial Method Connect a Cable to the Serial Ports 115200 bps Call menu Configure buttonOpen a Terminal Emulation Connection Change the Baud Rate toDownload the Second and Third Firmware Update Files Download the First Firmware Update FileCall menu 9600 bps Configure button Complete the Upgrade and Restore Communication RateUpdating the Firmware Xmodem Serial Method A13 Updating the Firmware Xmodem Serial Method A14 Page Iti Ne tTi n That