Xantrex Technology ENET-XFR3 manual Chapter

Page 62

Operation

Table 3-7Command Reference

 

 

Command

Description

IMAX <current>

S ts an upper soft limit on the supply’s programmed output current. If the soft limit

 

is

xceeded, or if the soft limit value is lower than the present output current

 

setting, the supply will ignore the command, turn on the ERR LED, and set the

 

ERR b in the bit registers.

 

Range: 0 to model maximum output current (IMAX)

 

Initial value: model IMAX

IMAX?

Asks for he supply’s soft current limit setting.

 

R

ponse: IMAX <current>

IOUT?

M asures the supply’s actual current output using the built-in current readback

 

circuitry.

 

R

ponse: IOUT <current>

 

 

IRDAT

Calculates a d records the slope and offset for readback voltage using IRLO and

<Ilo>,<Ihi>

IRHI data. Set CMODE ON before using this command. See also the calibration

 

procedures in Chapter 4.

 

<Ilo> and <Ihi> are in <current> format.

 

 

IRHI

The power supply outputs a current value to an external device connected as part of

 

the cal bration procedure and records a current readback value internally. These

 

values are at the high end of the programmed current range. Refer to the output

 

value as IRHI and record it to use as input with the IRDAT command. Set

 

CMODE ON before using this command. See also the calibration procedures in

 

Chapter 4.

 

 

IRLO

The power supply outputs a current value to an external device connected as part of

 

the calibration procedure and records a current readback value internally. These

 

values are at the low end of the programmed current range. Refer to the output

 

value as IRLO and record it to use as input with the IRDAT command. Set

 

CMODE ON before using this command. See also the calibration procedures in

 

Chapter 4.

 

 

ISET <current>

Sets the power supply’s output current in amps (default) or in milliamps. This

 

programmed current is the actual output in CC mode or the current limit in CV

 

mode.

 

Range: 0 to model maximum output current (IMAX)

 

Initial value: 0 amps

 

 

ISET?

Asks for the supply’s present output current setting. Does not apply to current

 

settings which are being held. See HOLD command.

 

Response: ISET <current>

 

 

 

3–12

TM-XR9B-01XN

Image 62
Contents Operating Manual Page XFR 1.2kW and 2.8kW Ethernet/RS-232 Interface Option Date and Revision Audience PurposeScope Organization Conventions Used Related InformationPage Important Safety Instructions Viii Contents Operation Calibration SpecificationsAdvanced Ethernet Administration Xii Figures Xiv Tables Xvi Features DescriptionFeatures and Functions Interface FeaturesReadback Functions Ethernet FeaturesProgrammable Functions Page Configuration IntroductionFor RS-232 Initial Inspection ERR Front PanelSRQ FLT1Item Ethernet/RS-232 Interface PCB 2Ethernet/RS-232 Interface Jumper Selections XoffProcedure for 1.2kW XFR Changing Internal JumpersProcedure for 2.8kW XFR 1Step#DescriptionActionModeConfigure for Ethernet Basic Setup Procedure EthernetBasic Setup Procedure RS-232 1StepConfiguring for Ethernet or RS-232 EthernetEthernet Communications Ethernet ConnectionLocating the Power Supply on Your Network Configuring Ethernet Bridge Installing and Using RealPort1 BackgroundRS-232Communications RS-232 Connection6Jumper J2 Settings for Baud Rate Baud Rate SelectionFlow Control Selection 7Jumper J2 Flow Control SectionRemote/Local Mode Startup Remote/Local OperationRemote Mode Operation Local Mode Operation Remote Enable REN CommandXON/XOFF Power Supply SettingsLocal Lockout LLO Command RTS/CTSAdditional User Options and Settings OVP SelectionHigh LOW OFF TTL Shutdown PolarityLowon User Signals User Lines ConnectorUser Lines Signal Connector Circuit Block Diagram User Lines Cable Connection 7User Lines Cable with Ferrite BlockOperation Manual Conventions Command SyntaxRS-232Operation Command Format and Parameters FormatFlo ting Point Number floa Order Command StringsCommand Terminators Iset 2.0A VsetCommand Summary DLY? AUXB?CMODE? ERR?IHI FAULT?Idata ILOCmode 1/ON Command ReferenceAUXA? Description AlsoRemote/Local Operation on Chapter Mask None = Unmask ALL ALL, None Command Voltage settings which are being held. See Hold command Accumulated Status, Status, and Fault Registers ASTS?ACF PONREM OPFError0 #ErrorNo ErrorsIdentificationExplanation Error CodesTroubleshooting Diagnostic LEDsEthernet Mode Troubleshooting Tips 10 Ethernet Mode TipsPossibleCauses RS-232Mode Troubleshooting Tips RS-232and/or Ethernet Mode Troubleshooting TipsPage Calibration Calibration Voltage Program Calibration Procedure Voltage Mode CalibrationVoltage Calibration Setup Voltage Readback Calibration Procedure Current Program Calibration Procedure Current Mode CalibrationCurrent Calibration Setup Current Readback Calibration Procedure Over Voltage Protection OVP Calibration Page Specifications 40-30 OVP600-2 40-70 600-4 Page Administration Changing the Root Password Introduction Resetting the Configuration to DefaultsResetting the Configuration from a Browser Viewing Network Statistics Copying the Configuration to and from a ServerViewing Port Statistics and Settings DIA Interpreting LED InformationNET Page Warranty and Product Information WarrantyDisclaimer ProductReturn Material Authorization Policy ExclusionsInformation About Your System Return ProcedureOut of Warranty Service Page Xantrex Technology Inc