Chapter 3: Installing the Switch and Modules

Installing and Replacing AT-PWR06 Power Supply Module

Installing Power Supply Module

The AT-PWR06 power supply module may be installed in one of the two power supply slots - PSU1 and PSU2. See Figure 1 on page 19 for the location of these slots.

The AT-DC2552XS L2 Data Center Switch can operate under full load with one power supply module installed. However, if you want power supply redundancy, a second power supply may be installed.

There is no functional difference between the two available power supply slots. Operation of the AT-DC2552XS is the same when installed in either slot. If you want to use only one power supply, Allied Telesis recommends that you install it in the PSU1 slot.

The following procedures are included in this section:

“Installing Power Supply Module” on page 48

“Replacing Power Supply Module” on page 50

“Installing Power Supply Blank Cover” on page 51

Install the AT-PWR06 power supply module by performing the following procedure:

1.Identify the power supply slot where you are installing the AT-PWR06 power supply module.

2.Loosen the captive screw on the blank cover panel of the power supply slot blank cover and remove the cover. See Figure 18.

Figure 18. Loosen Power Supply Captive Screws

3. Store the blank cover in a safe place for future use.

48

Image 48
Contents Installation Guide Page Electrical Safety and Emissions Standards TickTranslated Safety Statements Contents Page Figures Figures Tables Tables Preface Document Conventions Contacting Allied Telesis Preface Overview ChapterAT-DC2552XS Features FunctionsInstallation Options Optional QSFP+ Transceivers  AT-QSFPSR 40GBASE-SR4 MPOLED LED FANAT-DC2552XS Rear Panel Stack Installation Guide for AT-2552XS L2 Data Center Switch Cable Type 10Mbps 100Mbps 1000Mbps LEDs LEDQSFP+ LEDs QSFP+ LED is described in Table Power FaultLink ACT LED LinkFAN1 FAN2AC OK Console Port AT-PWR06 Power Supply Module Stack Installation Guide for AT-2552XS L2 Data Center Switch AT-FAN06 Fan Module Beginning the Installation Installation Overview Step ProcedureReviewing Safety Precautions Beginning the Installation Stack Installation Guide for AT-2552XS L2 Data Center Switch Beginning the Installation Planning the Installation Unpacking the Switch AT-DC2552XS SwitchAT-PWR06 Power Supply AT-FAN06 Fan Module Installing the Switch and Modules Installing the Switch on a Desktop Installing the Switch in an Equipment Rack Possible Bracket LocationsInstalling the Switch and Modules Mounting the Switch in an Equipment Rack Installing and Replacing AT-PWR06 Power Supply Module Installing Power Supply ModuleInsert AT-PWR06 Module Into Chassis Replacing Power Supply Module Tighten AT-PWR06 Captive ScrewsInstalling Power Supply Blank Cover Installing and Replacing AT-FAN06 Fan Module Installing Fan ModuleStack Installation Guide for AT-2552XS L2 Data Center Switch Replacing Fan Module Installing the SFP+ and QSFP+ Transceivers and Cables Installing SFP+ Transceivers and Cables 10GBASE-SRAT-SP10SR 10GBASE-LRInstalling SFP+ Transceiver Removing SFP+ Dust Cover Installing a SFP+ Direct Attach Cables Installing the SFP+ and QSFP+ Transceivers and Cables Installing QSFP+ Transceivers and Cables 40GBASE-SR4AT-QSFPSR Installing the SFP+ and QSFP+ Transceivers and Cables QSFP+ Mthtp Installing the SFP+ and QSFP+ Transceivers and Cables Powering the Switch Powering On the Switch Stack Installation Guide for AT-2552XS L2 Data Center Switch Turn Off the switch Managing the Switch Connecting the Console Port Local ManagementStack Installation Guide for AT-2552XS L2 Data Center Switch NET Mgmt Cable Installation Remote Network ManagementStack Installation Guide for AT-2552XS L2 Data Center Switch Managing the Switch Troubleshooting Troubleshooting Stack Installation Guide for AT-2552XS L2 Data Center Switch Troubleshooting Technical Specifications Physical SpecificationsEnvironmental Specifications Appendix aPower Specifications CertificationsQuality and Reliability MtbfRJ-45 Twisted Pair Port Pinouts TX+ RX+Pinout Pair Stack Installation Guide for AT-2552XS L2 Data Center Switch Appendix a Technical Specifications