Powerware 9315 operation manual To Place the UPS in Normal Mode

Page 24

The following describes the switches on the Control Panel (see Figure 7):

·The MODE switch is a two-position rotary switch that controls the manual transfer of the UPS to and from Bypass mode. The MODE switch is used to:

---Place the critical load in Bypass mode when the UPS is operating in Normal mode and the bypass source is within acceptable limits. If the transfer does not occur within 2 seconds, an alarm sounds.

---Prevent transfer to Normal mode when the UPS is in Bypass mode.

---Shut down the power processing unit (inverter and rectifier) of the UPS.

·The BATTERY switch is a two-position rotary switch that allows you to manually shunt trip the battery breakers in remote cabinets.

·The circuit breaker (CB1) switch controls the operation of the rectifier and inverter. If CB1 is on (closed), the rectifier turns on when the START switch is activated and the proper voltage is at the input terminals.

·The PUSH TO RESET pushbutton is described in the “Resetting the UPS System after Load Off” section of Chapter 12.

·The START switch activates the power controls on the Control Panel. The START switch is center-biased (the key will rest only in the upright position). Its operation is similar to that of an automobile ignition switch. After setting the operator controls, you turn the START switch to the right momentarily to activate the controls. When you release it, it returns to the upright position.

The following sections describe how to operate these controls to start, stop, or change the operating mode of the UPS.

To Place the UPS in Normal Mode:

1.Close Input Power Feeder breaker

2.Be sure the Load Off PUSH TO RESET pushbutton is pressed in.

3.Turn the BATTERY switch to NORMAL.

4.Turn the MODE switch to NORMAL.

5.Move the CB1 switch to ON.

6.Turn the START switch to the right momentarily.

The rectifier turns on, then the inverter turns on. When the inverter reaches full voltage, it turns on and supplies power to the critical load. It takes less than 1 minute for the UPS to achieve Normal mode.

If a bypass source is available when you turn the START switch on, the critical load is immediately supplied by the bypass source in Bypass mode until the inverter turns on and the UPS transfers to Normal mode. The status indicators on the Monitor Panel indicate when the UPS is in Bypass mode and Normal mode.

7.Close battery breaker(s).

16

Powerware 9315 (200 kVA ---300 kVA) Operation

 

 

164201036 Rev. D 041500

Image 24
Contents Uninterruptible Power Supply KVA 300 kVA Important Safety Instructions Table of Contents Starting and Stopping the UPS Maintaining the UPS System Responding to System Events List of Figures List of Tables Using This Manual IntroductionFor More Information Getting HelpTypical Powerware 9315 UPS System Getting StartedBattery Cabinet Looking Inside the UPSUPS Standard Features Monitor PanelOptions and Accessories Installation FeaturesSafety Considerations Output TransformerSymbols, Controls, and Indicators Risk of Electric ShockUnderstanding UPS Operation Normal Mode Path of Current Through the UPS in Normal ModeBypass Mode Path of Current Through the UPS in Bypass ModeBattery Mode Path of Current Through the UPS in Battery Mode Monitoring and Controlling UPS Operation Control Panel MonitorThis Page Intentionally Left Blank Using the Control Panel Starting and Stopping the UPSTo Place the UPS in Normal Mode To Shut Down the UPS from Normal Mode To Start the UPS in Bypass ModeThis Page Intentionally Left Blank Using the Monitor Panel UPS Monitor PanelUsing the LCD Screen Alarm NoneUsing the Pushbuttons Adjusting the ContrastUsing the Load Off Pushbutton Reading the Status Indicators Using the Menu Options · SetupShows the Load Amps Meters screen Shows the Event History Log screen Shows the Active System Events screen Shows the Unit Statistics screen Shows the Mimic screen Time Setup Screen Port Setup Screen Using Features and Options Building Alarm MonitoringSummary Alarm Contacts Summary Alarm ContactsOptional Monitoring Accessories Remote Monitor PanelSystem Normal Battery Cabinets External Battery DisconnectRelay Interface Module Relay Interface ModuleSupervisory Contact Module Shutdown ImminentThis Page Intentionally Left Blank Serial Communications Locating the Communications Panel Communications PanelConnecting Equipment to a Serial Port Port 1 DE-9Port 2 DB-25 Configuring the Serial Ports Setup Serial Port 1 ScreenMode RateDefault Settings Data/StopHandshaking SaveTerminal Mode Printing Selected InformationEntire Log Ctrl + P Event History LogMeters Printout Ctrl + M System Information Printout Ctrl + aBattery Test Printout Ctrl + B APRSystem Configuration System Configuration Mode Main MenuProgram Building Alarms Enable/Disable Default Functions Customize Alarm Messages Program Unit NameAdjust Output Voltage Change PasswordBattery Test Setup WK DAY MON Hrmn 4 FRI MARCalibration Mode Computer ModeRemote Monitor Mode Modify Low Battery TimeThis Page Intentionally Left Blank Remote Notification Remote Notification Features Description of Operation Call AnswerCall Out Housekeeping Hardware Requirements Configuring the Modem Basic Modem ConfigurationConfiguring the Modem to Call a Remote Computer Configuring the Modem to Call a Numeric Pager Configuring the Modem to Answer Incoming Calls Final Modem Configuration UPS Setup Configuration SaveMessages Alarms User-Selected EventsRectifier Monitor Important Safety Instructions Maintaining the UPS System164201036 Rev. D Performing Preventive Maintenance Maintenance TrainingThis Page Intentionally Left Blank Product Specifications System InputSystem Output Nominal +/-- 5%Environmental Specifications Battery SpecificationsThis Page Intentionally Left Blank Responding to System Events System Event HornsSystem Event Lights Inverter Messages -- Alarms Inverter Messages -- Notices System Event MessagesInverter Messages Inverter Status Messages Commands Rectifier Status Messages Using the Load OFF Pushbutton Resetting the UPS System after Load OffTo Use the Load OFF Pushbutton This Page Intentionally Left Blank