Powerware 9315 operation manual Configuring the Modem to Call a Remote Computer

Page 71

Configuring the Modem to Call a Remote Computer

To configure the modem to call a remote computer, perform the following procedure:

NOTE: Perform this procedure only after completing “Basic Modem Configuration” section of this chapter.

The brackets ([ ]) in the following steps indicate characters that require keying in prior to pressing [ENTER].

1.Connect the modem to the PC through the serial port as described in the modem manufacturer’s manual .

2.Key in [A], [T], then press [ENTER].

3.Confirm that the modem responds with “OK” or “0” (zero).

NOTE: In steps 4 and 5, the “xxxxxxx” is the phone number of a remote computer. The phone number should include all local line and long distance access numbers needed to dial out. This number is limited to 32 characters.

Placing a “T” at the beginning of the number informs the modem to use tone dialing. For example, use “9” if needed for an outside line, “1” for long distance + (Area Code) + Number or whatever access codes are needed to dial the call directly. Add a “,” in the number anywhere that a delay is needed. This will cause a one-second delay. More than one delay may be added to the number; for example, enter “AT&Z0=T,9,,1 (Area Code) (Phone Number)”.

4.To program a group one number, key in [A], [T], [&], [Z], [0] (zero), [=], [T], [,], [xxxxxxx], then press [ENTER].

5.To program a group two number, key in [A], [T], [&], [Z], [1], [=], [T], [,], [xxxxxxx], then press [ENTER].

6.Confirm that the modem responds with “OK” or “0” (zero).

7.Key in [A], [T], [&], [W], [0] (zero), then press [ENTER].

8.Confirm that the modem responds with “OK” or “0” (zero).

9.Connect a telephone line to the modem and test the modem by keying in [A], [T], [D], [S], [0] (zero), then pressing [ENTER].

10.The modem dials the telephone number stored in step 4 or 5. (The number is displayed on the terminal screen as it is dialed.) Repeat steps 4 (or 5) through 9 as necessary to modify the telephone number.

11.Confirm that the modem responds with “1” (one) when the connection is made.

NOTE: To set up a group one or group two pager number, refer to “Configuring the Modem to Call a Numeric Pager” section of this chapter.

Powerware 9315 (200 kVA ---300 kVA) Operation

63

164201036 Rev. D 041500

 

Image 71
Contents Uninterruptible Power Supply KVA 300 kVA Important Safety Instructions Table of Contents Starting and Stopping the UPS Maintaining the UPS System Responding to System Events List of Figures List of Tables Introduction Using This ManualGetting Help For More InformationGetting Started Typical Powerware 9315 UPS SystemLooking Inside the UPS Battery CabinetMonitor Panel UPS Standard FeaturesInstallation Features Options and AccessoriesOutput Transformer Safety ConsiderationsRisk of Electric Shock Symbols, Controls, and IndicatorsUnderstanding UPS Operation Path of Current Through the UPS in Normal Mode Normal ModePath of Current Through the UPS in Bypass Mode Bypass ModePath of Current Through the UPS in Battery Mode Battery ModeControl Panel Monitor Monitoring and Controlling UPS OperationThis Page Intentionally Left Blank Starting and Stopping the UPS Using the Control PanelTo Place the UPS in Normal Mode To Start the UPS in Bypass Mode To Shut Down the UPS from Normal ModeThis Page Intentionally Left Blank UPS Monitor Panel Using the Monitor PanelAlarm None Using the LCD ScreenUsing the Load Off Pushbutton Using the PushbuttonsAdjusting the Contrast Reading the Status Indicators · Setup Using the Menu OptionsShows the Load Amps Meters screen Shows the Event History Log screen Shows the Active System Events screen Shows the Unit Statistics screen Shows the Mimic screen Time Setup Screen Port Setup Screen Building Alarm Monitoring Using Features and OptionsSummary Alarm Contacts Summary Alarm ContactsRemote Monitor Panel Optional Monitoring AccessoriesSystem Normal External Battery Disconnect Battery CabinetsRelay Interface Module Relay Interface ModuleShutdown Imminent Supervisory Contact ModuleThis Page Intentionally Left Blank Serial Communications Communications Panel Locating the Communications PanelPort 1 DE-9 Connecting Equipment to a Serial PortPort 2 DB-25 Setup Serial Port 1 Screen Configuring the Serial PortsRate ModeSave Default SettingsData/Stop HandshakingPrinting Selected Information Terminal ModeEvent History Log Entire Log Ctrl + PSystem Information Printout Ctrl + a Meters Printout Ctrl + MAPR Battery Test Printout Ctrl + BProgram Building Alarms System ConfigurationSystem Configuration Mode Main Menu Enable/Disable Default Functions Program Unit Name Customize Alarm MessagesChange Password Adjust Output VoltageWK DAY MON Hrmn 4 FRI MAR Battery Test SetupModify Low Battery Time Calibration ModeComputer Mode Remote Monitor ModeThis Page Intentionally Left Blank Remote Notification Remote Notification Features Call Out Description of OperationCall Answer Housekeeping Hardware Requirements Basic Modem Configuration Configuring the ModemConfiguring the Modem to Call a Remote Computer Configuring the Modem to Call a Numeric Pager Configuring the Modem to Answer Incoming Calls Final Modem Configuration Save UPS Setup ConfigurationUser-Selected Events Messages AlarmsRectifier Monitor Maintaining the UPS System Important Safety Instructions164201036 Rev. D Maintenance Training Performing Preventive MaintenanceThis Page Intentionally Left Blank System Input Product SpecificationsNominal +/-- 5% System OutputBattery Specifications Environmental SpecificationsThis Page Intentionally Left Blank System Event Lights Responding to System EventsSystem Event Horns System Event Messages Inverter Messages -- Alarms Inverter Messages -- NoticesInverter Messages Inverter Status Messages Commands Rectifier Status Messages To Use the Load OFF Pushbutton Using the Load OFF PushbuttonResetting the UPS System after Load Off This Page Intentionally Left Blank