Powerware 9315 operation manual Housekeeping

Page 68

·The UPS logs a successful notify to the event log when the remote computer or modem answers and leaves an event message with the following format.

nnn<space>mmm<LF><CR> where:

nnn

= The telephone number of the UPS (20 characters maximum)

<space>

= ASCII space character (0x20)

mmm

= Event message for notice or alarm (40 characters maximum)

<LF>

=

ASCII line feed character (0x0A)

<CR>

=

ASCII carriage return character (0x0D)

If calling a pager service and the service answers, the UPS delays momentarily and then dials the pager number. Refer to the “Configuring the Modem to Call a Numeric Pager” section of this chapter for more information on configuring a modem to dial a pager.

NOTE: Because the pager service is not a modem, the UPS does not know if its message got through; therefore, the UPS continues to call the pager service for a programmed number of times or until a call-in reset is performed.

An unsuccessful notify event is logged into the UPS event log for each attempted call out.

If the phone number that the UPS is calling does not answer, the UPS delays for a time period (programmable from 1 to 60 minutes) and then reattempts the call. If answered, the UPS ceases further attempts to call. Each call group can be programmed for a separate number of attempts to call and delay between calls. Each unsuccessful attempt to call causes an unsuccessful notify event to be logged into the UPS event log.

If both call groups are active, the UPS alternates between calling the groups. The Call Out process can be terminated at any time by calling into the UPS and sending the reset command (press and hold [CTRL] and press [R]) or by turning the key switch on the front of the UPS.

Housekeeping

When the modem is idle, the UPS “pings” (tests for connection) the modem by sending an “AT” to the modem at five-minute intervals. If the modem does not respond correctly, by sending either “OK” or “0” to the UPS, the UPS attempts to re-initialize the modem. After a successful re-initialization, the UPS returns to the Housekeeping function. If the re-initialization is unsuccessful, two more attempts to re-initialize the modem are made before the UPS disables all Call Out attempts. Re-initialization is then attempted every ten minutes or until the communications mode is changed by the UPS front panel controls (or the modem re-initializes). For each unsuccessful attempt, the UPS logs a modem failure event into the event log. When the modem link is confirmed, the UPS communications resume normal operation and Call Out is enabled.

60

Powerware 9315 (200 kVA ---300 kVA) Operation

 

164201036 Rev. D 041500

Image 68
Contents Uninterruptible Power Supply KVA 300 kVA Important Safety Instructions Table of Contents Starting and Stopping the UPS Maintaining the UPS System Responding to System Events List of Figures List of Tables Using This Manual IntroductionFor More Information Getting HelpTypical Powerware 9315 UPS System Getting StartedBattery Cabinet Looking Inside the UPSUPS Standard Features Monitor PanelOptions and Accessories Installation FeaturesSafety Considerations Output TransformerSymbols, Controls, and Indicators Risk of Electric ShockUnderstanding UPS Operation Normal Mode Path of Current Through the UPS in Normal ModeBypass Mode Path of Current Through the UPS in Bypass ModeBattery Mode Path of Current Through the UPS in Battery ModeMonitoring and Controlling UPS Operation Control Panel MonitorThis Page Intentionally Left Blank Using the Control Panel Starting and Stopping the UPSTo Place the UPS in Normal Mode To Shut Down the UPS from Normal Mode To Start the UPS in Bypass ModeThis Page Intentionally Left Blank Using the Monitor Panel UPS Monitor PanelUsing the LCD Screen Alarm NoneUsing the Load Off Pushbutton Using the PushbuttonsAdjusting the Contrast Reading the Status Indicators Using the Menu Options · SetupShows the Load Amps Meters screen Shows the Event History Log screen Shows the Active System Events screen Shows the Unit Statistics screen Shows the Mimic screen Time Setup Screen Port Setup Screen Using Features and Options Building Alarm MonitoringSummary Alarm Contacts Summary Alarm ContactsOptional Monitoring Accessories Remote Monitor PanelSystem Normal Battery Cabinets External Battery DisconnectRelay Interface Module Relay Interface ModuleSupervisory Contact Module Shutdown ImminentThis Page Intentionally Left Blank Serial Communications Locating the Communications Panel Communications PanelConnecting Equipment to a Serial Port Port 1 DE-9Port 2 DB-25 Configuring the Serial Ports Setup Serial Port 1 ScreenMode RateDefault Settings Data/StopHandshaking SaveTerminal Mode Printing Selected InformationEntire Log Ctrl + P Event History LogMeters Printout Ctrl + M System Information Printout Ctrl + aBattery Test Printout Ctrl + B APRProgram Building Alarms System ConfigurationSystem Configuration Mode Main Menu Enable/Disable Default Functions Customize Alarm Messages Program Unit NameAdjust Output Voltage Change PasswordBattery Test Setup WK DAY MON Hrmn 4 FRI MARCalibration Mode Computer ModeRemote Monitor Mode Modify Low Battery TimeThis Page Intentionally Left Blank Remote Notification Remote Notification Features Call Out Description of OperationCall Answer Housekeeping Hardware Requirements Configuring the Modem Basic Modem ConfigurationConfiguring the Modem to Call a Remote Computer Configuring the Modem to Call a Numeric Pager Configuring the Modem to Answer Incoming Calls Final Modem Configuration UPS Setup Configuration SaveMessages Alarms User-Selected EventsRectifier Monitor Important Safety Instructions Maintaining the UPS System164201036 Rev. D Performing Preventive Maintenance Maintenance TrainingThis Page Intentionally Left Blank Product Specifications System InputSystem Output Nominal +/-- 5%Environmental Specifications Battery SpecificationsThis Page Intentionally Left Blank System Event Lights Responding to System EventsSystem Event Horns Inverter Messages -- Alarms Inverter Messages -- Notices System Event MessagesInverter Messages Inverter Status Messages Commands Rectifier Status Messages To Use the Load OFF Pushbutton Using the Load OFF PushbuttonResetting the UPS System after Load Off This Page Intentionally Left Blank