Powerware 9315 operation manual Battery Test Printout Ctrl + B, Apr

Page 57

Battery Test Printout (Ctrl + B)

This key sequence prints the Battery Test Log. The log consists of a history of the last 30 battery tests that were run and the results of those tests. The most recent test will appear at the bottom of the log. Figure 29 shows a sample of the Battery Test Log.

 

 

 

Uninterruptible Power System

 

 

 

 

 

 

 

 

 

UPS # 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UPS System Normal

 

 

 

 

 

 

 

12 APR 97 15:39:31

 

 

 

 

Alarm:

None

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Notice:

None

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Battery Test Log

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Date/Time

 

 

 

Volts

Health

Data

 

 

 

 

AUG

14

23:45

498.0

1.00

 

0000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SEP

11

23:45

498.0

1.00

 

0000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OCT

9

23:45

498.0

1.00

 

0000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOV

13

23:45

498.0

0.99

 

0000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DEC

11

23:45

498.0

0.99

 

0000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

JAN

8

23:45

498.0

0.98

 

0000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FEB

12

23:45

498.0

0.98

 

0000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MAR

12

23:41

000.0

0.00

 

0003

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

APR

9

23:45

496.2

0.98

 

0000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 29. Battery Test Log

The Date/Time field is the date and time of the battery test.

The Volts field is a measured value of the battery voltage during the test. This field will display 000.0 if the test did not run to completion.

The Health field is a relative measurement of your batteries condition. This number can be used to chart the condition of your batteries. If a sudden change of this number occurs relative to the previous test results, it is an indication that your batteries may need attention. This display is 0.00 if the test does not run to completion.

The Data field is a value to be used by your field service engineer to gain more information about the battery tests.

If the battery test does not complete, the Volts and Health field will read zero and the UPS Event History Log will report either Battery Test Failed, Battery Test Aborted (Load), or Battery Test Aborted (Utility). If the test ran to completion, Battery Passed Test will appear in the UPS Event History Log.

Powerware 9315 (200 kVA ---300 kVA) Operation

49

164201036 Rev. D 041500

 

Image 57
Contents Uninterruptible Power Supply KVA 300 kVA Important Safety Instructions Table of Contents Starting and Stopping the UPS Maintaining the UPS System Responding to System Events List of Figures List of Tables Introduction Using This ManualGetting Help For More InformationGetting Started Typical Powerware 9315 UPS SystemLooking Inside the UPS Battery CabinetMonitor Panel UPS Standard FeaturesInstallation Features Options and AccessoriesOutput Transformer Safety ConsiderationsRisk of Electric Shock Symbols, Controls, and IndicatorsUnderstanding UPS Operation Path of Current Through the UPS in Normal Mode Normal ModePath of Current Through the UPS in Bypass Mode Bypass ModePath of Current Through the UPS in Battery Mode Battery ModeControl Panel Monitor Monitoring and Controlling UPS OperationThis Page Intentionally Left Blank Starting and Stopping the UPS Using the Control PanelTo Place the UPS in Normal Mode To Start the UPS in Bypass Mode To Shut Down the UPS from Normal ModeThis Page Intentionally Left Blank UPS Monitor Panel Using the Monitor PanelAlarm None Using the LCD ScreenUsing the Pushbuttons Adjusting the ContrastUsing the Load Off Pushbutton Reading the Status Indicators · Setup Using the Menu OptionsShows the Load Amps Meters screen Shows the Event History Log screen Shows the Active System Events screen Shows the Unit Statistics screen Shows the Mimic screen Time Setup Screen Port Setup Screen Building Alarm Monitoring Using Features and OptionsSummary Alarm Contacts Summary Alarm ContactsRemote Monitor Panel Optional Monitoring AccessoriesSystem Normal External Battery Disconnect Battery CabinetsRelay Interface Module Relay Interface ModuleShutdown Imminent Supervisory Contact ModuleThis Page Intentionally Left Blank Serial Communications Communications Panel Locating the Communications PanelPort 1 DE-9 Connecting Equipment to a Serial PortPort 2 DB-25 Setup Serial Port 1 Screen Configuring the Serial PortsRate ModeData/Stop Default SettingsHandshaking SavePrinting Selected Information Terminal ModeEvent History Log Entire Log Ctrl + PSystem Information Printout Ctrl + a Meters Printout Ctrl + MAPR Battery Test Printout Ctrl + BSystem Configuration System Configuration Mode Main MenuProgram Building Alarms Enable/Disable Default Functions Program Unit Name Customize Alarm MessagesChange Password Adjust Output VoltageWK DAY MON Hrmn 4 FRI MAR Battery Test SetupComputer Mode Calibration ModeRemote Monitor Mode Modify Low Battery TimeThis Page Intentionally Left Blank Remote Notification Remote Notification Features Description of Operation Call AnswerCall Out Housekeeping Hardware Requirements Basic Modem Configuration Configuring the ModemConfiguring the Modem to Call a Remote Computer Configuring the Modem to Call a Numeric Pager Configuring the Modem to Answer Incoming Calls Final Modem Configuration Save UPS Setup ConfigurationUser-Selected Events Messages AlarmsRectifier Monitor Maintaining the UPS System Important Safety Instructions164201036 Rev. D Maintenance Training Performing Preventive MaintenanceThis Page Intentionally Left Blank System Input Product SpecificationsNominal +/-- 5% System OutputBattery Specifications Environmental SpecificationsThis Page Intentionally Left Blank Responding to System Events System Event HornsSystem Event Lights System Event Messages Inverter Messages -- Alarms Inverter Messages -- NoticesInverter Messages Inverter Status Messages Commands Rectifier Status Messages Using the Load OFF Pushbutton Resetting the UPS System after Load OffTo Use the Load OFF Pushbutton This Page Intentionally Left Blank