Powerware 9315 operation manual Configuring the Modem, Basic Modem Configuration

Page 70

Configuring the Modem

The modem must be configured by the user before connecting to the UPS. In addition, the modem must be programmed with the Call Out telephone numbers in order to operate the Remote Notification option.

To configure the modem, connect the serial port of a standard PC computer to the modem through the serial cable. Run a terminal emulation program on the computer. Test the connection to the modem by typing [A], [T] and [ENTER].

The modem should respond with either “OK” or “0” (zero). If the modem does not respond, consult the modem manufacturer’s manual to confirm your setup. If the modem still does not respond, then seek technical assistance from your modem manufacturer.

After connection, perform “Basic Modem Configuration” and the remaining sections of this chapter.

Basic Modem Configuration

The basic modem configuration consists of establishing the default operating parameters for the modem and saving them to the modem memory. This procedure sets up the modem for all operations. The configuration procedure is as follows:

1.Connect the modem to the PC through the serial port as described in the modem manufacturer’s manual.

NOTE: The brackets ([ ]) in the following steps indicate characters that require keying in prior to pressing [ENTER].

2.Key in [A], [T], then press [ENTER].

3.Confirm that the modem responds with “OK” or “0” (zero).

4.Key in [A], [T], [&], [F], then press [ENTER].

5.Confirm that the modem responds with “OK” or “0” (zero).

6.Key in [A], [T], [Q], [0] (zero), [V], [0] (zero), [M], [0] (zero), [N], [0] (zero), [X],

[0](zero), [&], [A], [0] (zero), [&], [D], [0] (zero), [&], [K], [0] (zero), [&], [Q], [5]. Verify that the display reads “ATQ0V0M0N0X0&A0&D0&K0&Q5”, then press [ENTER].

7.Confirm that the modem responds with “OK” or “0” (zero).

8.Key in [A], [T], [&], [W], [0] (zero), then press [ENTER].

9.Confirm that the modem responds with “OK” or “0” (zero).

10.Key in [A], [T], [&], [Y], [0] (zero), then press [ENTER].

11.Confirm that the modem responds with “OK” or “0” (zero).

62

Powerware 9315 (200 kVA ---300 kVA) Operation

 

164201036 Rev. D 041500

Image 70
Contents Uninterruptible Power Supply KVA 300 kVA Important Safety Instructions Table of Contents Starting and Stopping the UPS Maintaining the UPS System Responding to System Events List of Figures List of Tables Using This Manual IntroductionFor More Information Getting HelpTypical Powerware 9315 UPS System Getting StartedBattery Cabinet Looking Inside the UPSUPS Standard Features Monitor PanelOptions and Accessories Installation FeaturesSafety Considerations Output TransformerSymbols, Controls, and Indicators Risk of Electric ShockUnderstanding UPS Operation Normal Mode Path of Current Through the UPS in Normal ModeBypass Mode Path of Current Through the UPS in Bypass ModeBattery Mode Path of Current Through the UPS in Battery ModeMonitoring and Controlling UPS Operation Control Panel MonitorThis Page Intentionally Left Blank Using the Control Panel Starting and Stopping the UPSTo Place the UPS in Normal Mode To Shut Down the UPS from Normal Mode To Start the UPS in Bypass ModeThis Page Intentionally Left Blank Using the Monitor Panel UPS Monitor PanelUsing the LCD Screen Alarm NoneAdjusting the Contrast Using the PushbuttonsUsing the Load Off Pushbutton Reading the Status Indicators Using the Menu Options · SetupShows the Load Amps Meters screen Shows the Event History Log screen Shows the Active System Events screen Shows the Unit Statistics screen Shows the Mimic screen Time Setup Screen Port Setup Screen Using Features and Options Building Alarm MonitoringSummary Alarm Contacts Summary Alarm ContactsOptional Monitoring Accessories Remote Monitor PanelSystem Normal Battery Cabinets External Battery DisconnectRelay Interface Module Relay Interface ModuleSupervisory Contact Module Shutdown ImminentThis Page Intentionally Left Blank Serial Communications Locating the Communications Panel Communications PanelConnecting Equipment to a Serial Port Port 1 DE-9Port 2 DB-25 Configuring the Serial Ports Setup Serial Port 1 ScreenMode RateHandshaking Default SettingsData/Stop SaveTerminal Mode Printing Selected InformationEntire Log Ctrl + P Event History LogMeters Printout Ctrl + M System Information Printout Ctrl + aBattery Test Printout Ctrl + B APRSystem Configuration Mode Main Menu System ConfigurationProgram Building Alarms Enable/Disable Default Functions Customize Alarm Messages Program Unit NameAdjust Output Voltage Change PasswordBattery Test Setup WK DAY MON Hrmn 4 FRI MARRemote Monitor Mode Calibration ModeComputer Mode Modify Low Battery TimeThis Page Intentionally Left Blank Remote Notification Remote Notification Features Call Answer Description of OperationCall Out Housekeeping Hardware Requirements Configuring the Modem Basic Modem ConfigurationConfiguring the Modem to Call a Remote Computer Configuring the Modem to Call a Numeric Pager Configuring the Modem to Answer Incoming Calls Final Modem Configuration UPS Setup Configuration SaveMessages Alarms User-Selected EventsRectifier Monitor Important Safety Instructions Maintaining the UPS System164201036 Rev. D Performing Preventive Maintenance Maintenance TrainingThis Page Intentionally Left Blank Product Specifications System InputSystem Output Nominal +/-- 5%Environmental Specifications Battery SpecificationsThis Page Intentionally Left Blank System Event Horns Responding to System EventsSystem Event Lights Inverter Messages -- Alarms Inverter Messages -- Notices System Event MessagesInverter Messages Inverter Status Messages Commands Rectifier Status Messages Resetting the UPS System after Load Off Using the Load OFF PushbuttonTo Use the Load OFF Pushbutton This Page Intentionally Left Blank