Powerware 9315 operation manual Using the Load OFF Pushbutton, To Use the Load OFF Pushbutton

Page 91

Using the LOAD OFF Pushbutton

Load Off is initiated by the covered, red LOAD OFF pushbutton on the Monitor Panel. This pushbutton is protected by

a clear plastic shield to prevent accidental activation. In an emergency, you can press this pushbutton to instantaneously open the input breaker and interrupt UPS output. The UPS is cut off from utility power, and your critical load is de-energized. All power to the critical load is lost. The UPS (including Bypass) remains locked off until you reset the LOAD OFF pushbutton.

WARNING:

All power to the critical load is lost when you press this pushbutton. You should use this feature only in an emergency or when you want to de-energize the critical load.

To restart the UPS after pressing the LOAD OFF pushbutton, follow the procedure “Resetting the UPS System after Load Off” of this chapter before starting the UPS.

NOTE: The Remote Emergency Load Off option functions the same way as the LOAD OFF pushbutton on the Monitor Panel.

To Use the LOAD OFF Pushbutton

1.Raise the clear plastic shield covering the red LOAD OFF pushbutton on the Monitor Panel.

2.Press the LOAD OFF pushbutton.

The breaker and contactors open (you can hear them opening). The CB1 switch trips, and the Load Off PUSH TO RESET pushbutton on the UPS Control Panel pops out. The UPS system shuts down.

Resetting the UPS System after Load Off

CAUTION:

Do not attempt to restart the system after Load Off until the cause of the emergency has been identified and cleared.

The Load Off PUSH TO RESET pushbutton is a small white button on the UPS Control Panel. The PUSH TO RESET pushbutton pops out and the CB1 switch trips when the LOAD OFF pushbutton on the Monitor Panel is activated.

To reset the UPS system:

1.Press the Load Off PUSH TO RESET pushbutton until it clicks in and remains recessed.

2.Move the CB1 switch from the center (tripped) position to OFF. The switch should be difficult to move from the TRIPPED position.

3.The UPS system is now reset. To restart the UPS system, follow the procedure in Chapter 4, “Starting and Stopping the UPS.”

Powerware 9315 (200 kVA ---300 kVA) Operation

83

164201036 Rev. D 041500

 

Image 91
Contents Uninterruptible Power Supply KVA 300 kVA Important Safety Instructions Table of Contents Starting and Stopping the UPS Maintaining the UPS System Responding to System Events List of Figures List of Tables Introduction Using This ManualGetting Help For More InformationGetting Started Typical Powerware 9315 UPS SystemLooking Inside the UPS Battery CabinetMonitor Panel UPS Standard FeaturesInstallation Features Options and AccessoriesOutput Transformer Safety ConsiderationsRisk of Electric Shock Symbols, Controls, and IndicatorsUnderstanding UPS Operation Path of Current Through the UPS in Normal Mode Normal ModePath of Current Through the UPS in Bypass Mode Bypass ModePath of Current Through the UPS in Battery Mode Battery ModeControl Panel Monitor Monitoring and Controlling UPS OperationThis Page Intentionally Left Blank Starting and Stopping the UPS Using the Control PanelTo Place the UPS in Normal Mode To Start the UPS in Bypass Mode To Shut Down the UPS from Normal ModeThis Page Intentionally Left Blank UPS Monitor Panel Using the Monitor PanelAlarm None Using the LCD ScreenAdjusting the Contrast Using the PushbuttonsUsing the Load Off Pushbutton Reading the Status Indicators · Setup Using the Menu OptionsShows the Load Amps Meters screen Shows the Event History Log screen Shows the Active System Events screen Shows the Unit Statistics screen Shows the Mimic screen Time Setup Screen Port Setup Screen Building Alarm Monitoring Using Features and OptionsSummary Alarm Contacts Summary Alarm ContactsRemote Monitor Panel Optional Monitoring AccessoriesSystem Normal External Battery Disconnect Battery CabinetsRelay Interface Module Relay Interface ModuleShutdown Imminent Supervisory Contact ModuleThis Page Intentionally Left Blank Serial Communications Communications Panel Locating the Communications PanelPort 1 DE-9 Connecting Equipment to a Serial PortPort 2 DB-25 Setup Serial Port 1 Screen Configuring the Serial PortsRate ModeSave Default SettingsData/Stop HandshakingPrinting Selected Information Terminal ModeEvent History Log Entire Log Ctrl + PSystem Information Printout Ctrl + a Meters Printout Ctrl + MAPR Battery Test Printout Ctrl + BSystem Configuration Mode Main Menu System ConfigurationProgram Building Alarms Enable/Disable Default Functions Program Unit Name Customize Alarm MessagesChange Password Adjust Output VoltageWK DAY MON Hrmn 4 FRI MAR Battery Test SetupModify Low Battery Time Calibration ModeComputer Mode Remote Monitor ModeThis Page Intentionally Left Blank Remote Notification Remote Notification Features Call Answer Description of OperationCall Out Housekeeping Hardware Requirements Basic Modem Configuration Configuring the ModemConfiguring the Modem to Call a Remote Computer Configuring the Modem to Call a Numeric Pager Configuring the Modem to Answer Incoming Calls Final Modem Configuration Save UPS Setup ConfigurationUser-Selected Events Messages AlarmsRectifier Monitor Maintaining the UPS System Important Safety Instructions164201036 Rev. D Maintenance Training Performing Preventive MaintenanceThis Page Intentionally Left Blank System Input Product SpecificationsNominal +/-- 5% System OutputBattery Specifications Environmental SpecificationsThis Page Intentionally Left Blank System Event Horns Responding to System EventsSystem Event Lights System Event Messages Inverter Messages -- Alarms Inverter Messages -- NoticesInverter Messages Inverter Status Messages Commands Rectifier Status Messages Resetting the UPS System after Load Off Using the Load OFF PushbuttonTo Use the Load OFF Pushbutton This Page Intentionally Left Blank