Powerware 9315 operation manual Environmental Specifications, Battery Specifications

Page 85

Environmental Specifications

Operating Temperature

0 to 40˚C without derating. However, operating

 

at or near 40˚C will adversely affect battery life

 

(refer to your battery specifications for more

 

information). The recommended operating

 

temperature is 25˚C.

 

 

Operating Altitude

Maximum 1500m (5000 ft) at 40_C without

 

derating

 

 

Storage Temperature

---20 to +70˚C (prolonged storage above 40˚C

 

will cause rapid battery self-discharge)

 

 

Relative Humidity (operating and

95% maximum noncondensing

storage)

 

 

 

Acoustical Noise

65 dBA at a 1m distance

 

 

EMI Supression

Meets FCC Regulation 47, Part 15, Subpart J, for

 

class A devices

 

 

Electrostatic Discharge (ESD)

Meets IEC 801---2 specifications. Withstands up

Immunity

to 25 kV without damage and with no disturbance

 

or adverse effect to the critical load.

 

 

System Efficiency at Full Unity

400V, 600V Models:

Power Factor Load and Nominal

91%

Input Voltage

480V Models:

Note: The 208/600 systems use an

92%

input isolation transformer

option that reduces system

.

efficiency.

 

 

 

Battery Specifications

These specifications are for batteries supplied by the UPS manufacturer in line-up-and-match cabinets:

Battery Type

Sealed, maintenance-free, high rate discharge, lead-acid

 

cells

 

 

Nominal Battery String

480 VDC (240 cells) for PowerwarePlus 225, 300

Voltage

420 VDC (210 cells) for PowerwarePlus 200, 250

Float Charging

2.25 VDC per cell

 

(540 VDC based on 240 cells)

 

(470 VDC based on 210 cells)

 

 

Equalizing Charge

2.40 VDC per cell, set to 2.25 VDC at factory

 

 

Battery Charge Current

Limited to 25% of full, regardless of actual load on inverter

Limit

 

 

 

Powerware 9315 (200 kVA ---300 kVA) Operation

77

164201036 Rev. D 041500

 

Image 85
Contents Uninterruptible Power Supply KVA 300 kVA Important Safety Instructions Table of Contents Starting and Stopping the UPS Maintaining the UPS System Responding to System Events List of Figures List of Tables Introduction Using This ManualGetting Help For More InformationGetting Started Typical Powerware 9315 UPS SystemLooking Inside the UPS Battery CabinetMonitor Panel UPS Standard FeaturesInstallation Features Options and AccessoriesOutput Transformer Safety ConsiderationsRisk of Electric Shock Symbols, Controls, and IndicatorsUnderstanding UPS Operation Path of Current Through the UPS in Normal Mode Normal ModePath of Current Through the UPS in Bypass Mode Bypass ModePath of Current Through the UPS in Battery Mode Battery ModeControl Panel Monitor Monitoring and Controlling UPS OperationThis Page Intentionally Left Blank Starting and Stopping the UPS Using the Control PanelTo Place the UPS in Normal Mode To Start the UPS in Bypass Mode To Shut Down the UPS from Normal ModeThis Page Intentionally Left Blank UPS Monitor Panel Using the Monitor PanelAlarm None Using the LCD ScreenAdjusting the Contrast Using the PushbuttonsUsing the Load Off Pushbutton Reading the Status Indicators · Setup Using the Menu OptionsShows the Load Amps Meters screen Shows the Event History Log screen Shows the Active System Events screen Shows the Unit Statistics screen Shows the Mimic screen Time Setup Screen Port Setup Screen Building Alarm Monitoring Using Features and OptionsSummary Alarm Contacts Summary Alarm ContactsRemote Monitor Panel Optional Monitoring AccessoriesSystem Normal External Battery Disconnect Battery CabinetsRelay Interface Module Relay Interface ModuleShutdown Imminent Supervisory Contact ModuleThis Page Intentionally Left Blank Serial Communications Communications Panel Locating the Communications PanelPort 1 DE-9 Connecting Equipment to a Serial PortPort 2 DB-25 Setup Serial Port 1 Screen Configuring the Serial PortsRate ModeData/Stop Default SettingsHandshaking SavePrinting Selected Information Terminal ModeEvent History Log Entire Log Ctrl + PSystem Information Printout Ctrl + a Meters Printout Ctrl + MAPR Battery Test Printout Ctrl + BSystem Configuration Mode Main Menu System ConfigurationProgram Building Alarms Enable/Disable Default Functions Program Unit Name Customize Alarm MessagesChange Password Adjust Output VoltageWK DAY MON Hrmn 4 FRI MAR Battery Test SetupComputer Mode Calibration ModeRemote Monitor Mode Modify Low Battery TimeThis Page Intentionally Left Blank Remote Notification Remote Notification Features Call Answer Description of OperationCall Out Housekeeping Hardware Requirements Basic Modem Configuration Configuring the ModemConfiguring the Modem to Call a Remote Computer Configuring the Modem to Call a Numeric Pager Configuring the Modem to Answer Incoming Calls Final Modem Configuration Save UPS Setup ConfigurationUser-Selected Events Messages AlarmsRectifier Monitor Maintaining the UPS System Important Safety Instructions164201036 Rev. D Maintenance Training Performing Preventive MaintenanceThis Page Intentionally Left Blank System Input Product SpecificationsNominal +/-- 5% System OutputBattery Specifications Environmental SpecificationsThis Page Intentionally Left Blank System Event Horns Responding to System EventsSystem Event Lights System Event Messages Inverter Messages -- Alarms Inverter Messages -- NoticesInverter Messages Inverter Status Messages Commands Rectifier Status Messages Resetting the UPS System after Load Off Using the Load OFF PushbuttonTo Use the Load OFF Pushbutton This Page Intentionally Left Blank