Select Unit from the Statistics menu to display a listing of statistics about UPS operation.
Figure 14 shows the Unit Statistics screen.
|
| Uninterruptible Power System |
|
| ||||
UPS System Normal |
|
|
| 04 MAY 1997 | 14:23:45 | |||
Alarm: | None |
|
|
|
|
|
|
|
Notice: None |
|
|
|
|
|
|
| |
Battery |
| Start Date: |
| 04 MAY 1997 |
| |||
Percent |
|
|
|
|
|
|
| |
100% | Number of Incidents: Month Total Time On: DAYS HR MN | |||||||
|
| |||||||
|
| On Battery < 1 | Min. | 0 | 0 | UPS | 0035 20 59 | |
|
| On Battery | Min. | 1 | 0 | Bypass | 0000 00 30 | |
|
| On Battery > 4 | Min. | 0 | 0 | Battery | 0000 00 02 | |
|
| Full Batt. Discharge | 0 | 0 | Generator 0000 00 00 | |||
Statistics | Building Alarm | 1 | 2 | 11 | Logic | 0035 21 30 | ||
Building Alarm | 2 | 2 | 9 |
|
|
| ||
|
| Building Alarm | 3 | 3 | 8 |
|
|
|
Unit |
| Building Alarm | 4 | 2 | 5 | Availability |
| |
| Building Alarm | 5 | 3 | 8 | UPS |
| 0.99 | |
|
|
| ||||||
|
| Building Alarm | 6 | 3 | 9 | Bypass |
| 0.81 |
Meters | Events | Statistics Graphics | Setup |
|
|
|
|
|
Figure 14. Unit Statistics Screen
The left column shows the number of UPS incidents for the current month and since the start date shown at the top of the screen. The top right column shows the time that the UPS was on bypass, battery, or generator, and the amount of time the UPS logic has been functioning since the start date. The lower right column shows the percent of availability of the UPS and the bypass source.
Powerware 9315 (200 kVA | 27 |