Powerware 9315 operation manual System Normal

Page 42

The RMP contains a local horn and the following backlit status indicators:

SYSTEM NORMAL

The UPS is energized (either with utility power or battery backup) and is supplying conditioned power to the critical load.

NO REDUNDANCY

This indicator applies only to parallel systems when one cabinet is not functioning. This feature is not available on this system.

ON GENERATOR

This alarm means that the UPS input and bypass are being supplied by the power from the generator, instead of from the utility power.

ON BYPASS

The bypass source is supplying the critical load. Usually this means that the UPS is not energized. The load is not protected in Bypass mode, and a horn sounds after 30 seconds.

UPS ALARM

The UPS system is issuing an alarm. Conditions that affect the current UPS mode are indicated by the alarm lamps and horn on the UPS.

ON BATTERY

The UPS battery backup is supplying the critical load. The utility power is either interrupted or out of specification. The SYSTEM NORMAL indicator is also lit.

BYPASS UNAVAILABLE

The UPS system is in Normal mode, but

a bypass source is not within specification. A horn sounds after 30 seconds.

SHUTDOWN IMMINENT

The UPS is preparing to shut down because the UPS is in Battery mode and the DC voltage is approaching its low limit.

This light is accompanied by an audible alarm horn.

34

Powerware 9315 (200 kVA ---300 kVA) Operation

 

164201036 Rev. D 041500

Image 42
Contents Uninterruptible Power Supply KVA 300 kVA Important Safety Instructions Table of Contents Starting and Stopping the UPS Maintaining the UPS System Responding to System Events List of Figures List of Tables Using This Manual IntroductionFor More Information Getting HelpTypical Powerware 9315 UPS System Getting StartedBattery Cabinet Looking Inside the UPSUPS Standard Features Monitor PanelOptions and Accessories Installation FeaturesSafety Considerations Output TransformerSymbols, Controls, and Indicators Risk of Electric ShockUnderstanding UPS Operation Normal Mode Path of Current Through the UPS in Normal ModeBypass Mode Path of Current Through the UPS in Bypass ModeBattery Mode Path of Current Through the UPS in Battery ModeMonitoring and Controlling UPS Operation Control Panel MonitorThis Page Intentionally Left Blank Using the Control Panel Starting and Stopping the UPSTo Place the UPS in Normal Mode To Shut Down the UPS from Normal Mode To Start the UPS in Bypass ModeThis Page Intentionally Left Blank Using the Monitor Panel UPS Monitor PanelUsing the LCD Screen Alarm NoneUsing the Pushbuttons Adjusting the ContrastUsing the Load Off Pushbutton Reading the Status Indicators Using the Menu Options · SetupShows the Load Amps Meters screen Shows the Event History Log screen Shows the Active System Events screen Shows the Unit Statistics screen Shows the Mimic screen Time Setup Screen Port Setup Screen Using Features and Options Building Alarm MonitoringSummary Alarm Contacts Summary Alarm ContactsOptional Monitoring Accessories Remote Monitor PanelSystem Normal Battery Cabinets External Battery DisconnectRelay Interface Module Relay Interface ModuleSupervisory Contact Module Shutdown ImminentThis Page Intentionally Left Blank Serial Communications Locating the Communications Panel Communications PanelConnecting Equipment to a Serial Port Port 1 DE-9Port 2 DB-25 Configuring the Serial Ports Setup Serial Port 1 ScreenMode RateHandshaking Default SettingsData/Stop SaveTerminal Mode Printing Selected InformationEntire Log Ctrl + P Event History LogMeters Printout Ctrl + M System Information Printout Ctrl + aBattery Test Printout Ctrl + B APRSystem Configuration System Configuration Mode Main MenuProgram Building Alarms Enable/Disable Default Functions Customize Alarm Messages Program Unit NameAdjust Output Voltage Change PasswordBattery Test Setup WK DAY MON Hrmn 4 FRI MARRemote Monitor Mode Calibration ModeComputer Mode Modify Low Battery TimeThis Page Intentionally Left Blank Remote Notification Remote Notification Features Description of Operation Call AnswerCall Out Housekeeping Hardware Requirements Configuring the Modem Basic Modem ConfigurationConfiguring the Modem to Call a Remote Computer Configuring the Modem to Call a Numeric Pager Configuring the Modem to Answer Incoming Calls Final Modem Configuration UPS Setup Configuration SaveMessages Alarms User-Selected EventsRectifier Monitor Important Safety Instructions Maintaining the UPS System164201036 Rev. D Performing Preventive Maintenance Maintenance TrainingThis Page Intentionally Left Blank Product Specifications System InputSystem Output Nominal +/-- 5%Environmental Specifications Battery SpecificationsThis Page Intentionally Left Blank Responding to System Events System Event HornsSystem Event Lights Inverter Messages -- Alarms Inverter Messages -- Notices System Event MessagesInverter Messages Inverter Status Messages Commands Rectifier Status Messages Using the Load OFF Pushbutton Resetting the UPS System after Load OffTo Use the Load OFF Pushbutton This Page Intentionally Left Blank