To Shut Down the UPS from Normal Mode:
1.Turn the MODE switch to BYPASS.
The UPS switches to Bypass mode. If the bypass source is not available, the power processor remains on and an alarm sounds.
2.When the transfer is complete (the LCD screen reads “On Bypass”), move the CB1 switch to OFF.
The bypass source supplies the critical load and the power processor
To Start the UPS in Bypass Mode:
If the power processing unit (PPU) of the UPS is not available and you need to energize your critical load right away, you can energize your critical load without the benefit of backup. To turn the UPS on in Bypass mode:
1.Turn the MODE switch to BYPASS. (The remaining switches can be in any position.)
2.Turn the START switch to the right momentarily.
Power to the critical load is supplied by the bypass source. No backup is available.
To Shut Down Power to the Critical Load While in Bypass Mode:
To perform maintenance or service on your critical load, you must shut it down first:
1.Turn off all equipment that is being powered through the UPS.
2.Press the LOAD OFF pushbutton on the Monitor Panel.
Powerware 9315 (200 kVA | 17 |
164201036 Rev. D 041500 |
|