Mounting the Liebert XDV

5.0MOUNTING THE LIEBERT XDV

The Liebert XDV module must be securely attached to the top of the computer cabinet or, alterna- tively, suspended above the cabinet. For mounting atop the computer cabinet, see 5.1 - Mounting the Liebert XDV on Top of the Cabinet; to hang the Liebert XDV above the computer cabinet, refer to 5.2 - Suspended Mounting Method. Be sure to follow all applicable codes.

! WARNING

Risk of top-heavy cabinet falling. Can cause equipment damage, injury or death.

A lightly loaded cabinet may become top-heavy after a Liebert XDV is mounted on it, causing the cabinet to tip over, possibly resulting in serious injury.

Before beginning to place the Liebert XDV on the cabinet, ascertain whether the cabinet or rack requires additional stabilization, and secure the cabinet to the floor if necessary to prevent tip- over.

Always use at least two persons to mount the Liebert XDV on top of a cabinet.

5.1Mounting the Liebert XDV on Top of the Cabinet

The Liebert XDV may be installed on a computer cabinet by securing it with either the two included bolts, the two included clips or both the bolts and clips.

The Liebert XDV has mounting holes below the fans that match holes in the Liebert Foundation com- puter system cabinet. Other cabinets may require that holes be drilled to accommodate the bolts or the clips.

5.1.1Bolting Liebert XDV to Top of Cabinet

To mount the Liebert XDV:

1.With at least one additional person, lift the Liebert XDV and set it down on top of the cabinet. The front edge of the Liebert XDV should be even with the front edge of the cabinet. See Figure 10.

Figure 10 Positioning the Liebert XDV

CORRECT

Liebert XDV is flush with front edge of rack

Computer cabinet or rack

X

INCORRECT Liebert XDV is too

far from

front edge

of rack

Computer cabinet or rack

X

INCORRECT Liebert XDV hangs over front edge of rack

Computer cabinet or rack

2.If your cabinet has mounting holes matching those on the Liebert XDV, align the Liebert XDV properly and insert the bolts from the bottom of the cabinet and secure them to the factory- installed cage nuts (see Figure 11). Tighten the bolts.

If your cabinet’s mounting holes do not match those on the Liebert XDV, drill holes as required. To prevent metal shavings and particles from falling into the equipment in the cabinet or into the Liebert XDV, use a vacuum or other method to collect them while drilling the holes.

After drilling the holes, insert bolts from the bottom of the cabinet and secure them to the factory- installed cage nuts (see Figure 11). Tighten the bolts.

If also using mounting clips in conjunction with bolting method above, see 5.1.2 - Using Sup- plied Clips for Mounting.

10

Image 16
Contents Liebert XDV General Safety Guidelines Fluorinated Greenhouse Gas Requirements-European UnionTable of Contents Installation Checklist and System Fill for Startup MaintenanceSpecifications ElectricalFigures Page Example XDV10BK Liebert XDV component locationsPre-Installation Checks Installation ConsiderationsInstallation ReferencesChecking and Unpacking Product/System DescriptionGeneral Product Information Equipment Inspection Recyclable PackagingUnit Handling Unpacking the Unit Domestic PackagingExport Packaging Removing export shipping packageRemoving the Liebert XDV from the Pallet Removing Liebert XDV from shipping palletDimensional data Determining Placement in the Conditioned SpaceMechanical Considerations Changing the Air Intake Location Changing the Liebert XDV’s air intake locationMounting the Liebert XDV Mounting the Liebert XDV on Top of the CabinetBolting Liebert XDV to Top of Cabinet Bottom View Using Supplied Clips for Mounting Mounting clip placementSuspension hardware and bracket dimensional data Suspended Mounting Method11mm 22mm Top View 2 64mm 76mm 102mm DPN000770 Pg , RevSuspending the Liebert XDV from Unistruts Suspending the Liebert XDV from Overhead StructuresSuspending Liebert XDV from the overhead structure Mounting Liebert XDVs in Stacked Setup Stacking configuration offsetHanging Stacked Liebert XDVs from Unistruts Stacked Liebert XDVs suspended from UnistrutsHanging Stacked Liebert XDVs from the Overhead Structure European Union Fluorinated Greenhouse Gas Requirements System Connection ConfigurationPiping Connection Methods and Points Piping Connections to Liebert XDP or Liebert XDCRight Side Liebert XDV Hard Piped Connection Sizes Holding Charge-Hard-Piped UnitsRecommended Piping Size Brazing Preparations-Hard-Piped UnitsConnection Methods-One-Shot Connections Branch piping sizes for refrigerant loopConnecting Liebert XD Flex Pipe to Liebert XDV Modules Field Installation of Liebert Flex Pipe Kit on Liebert XDVRefrigerant Charge-Pre-Charged Option Liebert XD prefabricated piping assembly Tools RequiredWith wrench OvertightenReturn Insulation Piping mains without Liebert XDV and Liebert Flex PipeConnecting High Voltage Cables for CSA/C-US Certified Units ElectricalRear Liebert XDV Rear of Liebert XDVLiebert XDV electrical connections for CE-approved units Condensate Detection Connections Connecting Low Voltage Wiring-OptionalRear View of Liebert Xdvto be N.E.C. Class Checklist for Proper Installation Installation Checklist and System Fill for StartupStart the Liebert XDV OperationMaintenance Internal AccessFluorinated Greenhouse Gas Requirements Accessing Internal Electrical Components Accessing internal electrical componentsTo remove the fan tray Specifications Liebert XDV10 specificationsLiebert XDV8 specifications Liebert XD Liebert Flex Pipe assemblies, supply and return Page Ne t ItiTi n That