Liebert XDV Checklist for Proper Installation, Installation Checklist and System Fill for Startup

Page 39

Installation Checklist and System Fill for Startup

8.0INSTALLATION CHECKLIST AND SYSTEM FILL FOR STARTUP

8.1Checklist for Proper Installation

___ 1. Liebert XDV module is properly mounted, secured either to the cabinet, overhead structure or to the Unistruts.

___ 2. Power cords connected to electrical supply.

___ 3. Low voltage wiring to optional condensate detection on Liebert XDV.

___ 4. Piping from Liebert XDP to Liebert XDV, with isolation valves piped to each Liebert XDV.

a.Hard-piped units connected to prefabricated headers

b.Flex piping connections to prefabricated header assembly, if flex piping is used.

___ 5. Piping insulated.

___ 6. Start the Liebert XDV to ensure proper operation (see 9.1 - Start the Liebert XDV).

___ 7. Shut down the Liebert XDV.

8.2Charging with Refrigerant and Starting the Liebert XD System

The Liebert XD System must be completely installed before it is charged with refrigerant. After installation is complete, refer to the Liebert XDP or Liebert XDC user manual for instructions on charging the Liebert XD modules with refrigerant and starting the system. The complete Liebert XD system includes all cooling modules, a Liebert XDC or Liebert XDP unit and any other connected equipment.

33

Image 39
Contents Liebert XDV Fluorinated Greenhouse Gas Requirements-European Union General Safety GuidelinesTable of Contents Electrical Installation Checklist and System Fill for StartupMaintenance SpecificationsFigures Page Liebert XDV component locations Example XDV10BKReferences Pre-Installation ChecksInstallation Considerations InstallationProduct/System Description Checking and UnpackingGeneral Product Information Recyclable Packaging Equipment InspectionUnpacking the Unit Domestic Packaging Unit HandlingRemoving export shipping package Export PackagingRemoving Liebert XDV from shipping pallet Removing the Liebert XDV from the PalletDetermining Placement in the Conditioned Space Dimensional dataMechanical Considerations Changing the Liebert XDV’s air intake location Changing the Air Intake LocationMounting the Liebert XDV on Top of the Cabinet Mounting the Liebert XDVBolting Liebert XDV to Top of Cabinet Bottom View Mounting clip placement Using Supplied Clips for MountingPg , Rev Suspension hardware and bracket dimensional dataSuspended Mounting Method 11mm 22mm Top View 2 64mm 76mm 102mm DPN000770Suspending the Liebert XDV from Overhead Structures Suspending the Liebert XDV from UnistrutsSuspending Liebert XDV from the overhead structure Stacking configuration offset Mounting Liebert XDVs in Stacked SetupStacked Liebert XDVs suspended from Unistruts Hanging Stacked Liebert XDVs from UnistrutsHanging Stacked Liebert XDVs from the Overhead Structure System Connection Configuration European Union Fluorinated Greenhouse Gas RequirementsPiping Piping Connections to Liebert XDP or Liebert XDC Connection Methods and PointsRight Side Liebert XDV Holding Charge-Hard-Piped Units Hard Piped Connection SizesBrazing Preparations-Hard-Piped Units Recommended Piping SizeBranch piping sizes for refrigerant loop Connection Methods-One-Shot ConnectionsField Installation of Liebert Flex Pipe Kit on Liebert XDV Connecting Liebert XD Flex Pipe to Liebert XDV ModulesRefrigerant Charge-Pre-Charged Option Tools Required Liebert XD prefabricated piping assemblyOvertighten With wrenchReturn Piping mains without Liebert XDV and Liebert Flex Pipe InsulationRear of Liebert XDV Connecting High Voltage Cables for CSA/C-US Certified UnitsElectrical Rear Liebert XDVLiebert XDV electrical connections for CE-approved units Connecting Low Voltage Wiring-Optional Condensate Detection ConnectionsRear View of Liebert Xdvto be N.E.C. Class Installation Checklist and System Fill for Startup Checklist for Proper InstallationOperation Start the Liebert XDVInternal Access MaintenanceFluorinated Greenhouse Gas Requirements Accessing internal electrical components Accessing Internal Electrical ComponentsTo remove the fan tray Liebert XDV10 specifications SpecificationsLiebert XDV8 specifications Liebert XD Liebert Flex Pipe assemblies, supply and return Page That Ne tIti Ti n