Liebert XDV manual Connection Methods and Points, Piping Connections to Liebert XDP or Liebert XDC

Page 26

Piping

Figure 22 Typical Liebert XDV piping—non-interlaced connection

TOP VIEW—NOT TO SCALE

Return

Supply

Liebert

XDP/Lie-

Liebert XDV

Liebert XDV

Liebert XDV

Liebert XDV

A

A

A

A

6.2.1Piping Connections to Liebert XDP or Liebert XDC

Refer to site specific drawings for general locations of the piping connections. For Liebert XDV con- nection locations, refer to Figures 1 and 24.

6.3Connection Methods and Points

The assembly and connection means used for piping in the Liebert XD system are the same as those used in conventional refrigeration systems. Observe all standard practices during installation and startup to prevent damage and contamination. All piping must be ASTM Type "L" copper pipe.

For hard-piped Liebert XDVs, the supply piping connection is 1/2" OD copper pipe, and the return piping connection is 5/8" OD copper. For Liebert XDVs with the pre-charged option, both supply and return fittings are one-shot connections. These fittings contain pressurized R-134a refrigerant inside the Liebert XDV.

20

Image 26
Contents Liebert XDV General Safety Guidelines Fluorinated Greenhouse Gas Requirements-European UnionTable of Contents Specifications Installation Checklist and System Fill for StartupMaintenance ElectricalFigures Page Example XDV10BK Liebert XDV component locationsInstallation Pre-Installation ChecksInstallation Considerations ReferencesGeneral Product Information Product/System DescriptionChecking and Unpacking Equipment Inspection Recyclable PackagingUnit Handling Unpacking the Unit Domestic PackagingExport Packaging Removing export shipping packageRemoving the Liebert XDV from the Pallet Removing Liebert XDV from shipping palletMechanical Considerations Determining Placement in the Conditioned SpaceDimensional data Changing the Air Intake Location Changing the Liebert XDV’s air intake locationBolting Liebert XDV to Top of Cabinet Mounting the Liebert XDV on Top of the CabinetMounting the Liebert XDV Bottom View Using Supplied Clips for Mounting Mounting clip placement11mm 22mm Top View 2 64mm 76mm 102mm DPN000770 Suspension hardware and bracket dimensional dataSuspended Mounting Method Pg , RevSuspending the Liebert XDV from Unistruts Suspending the Liebert XDV from Overhead StructuresSuspending Liebert XDV from the overhead structure Mounting Liebert XDVs in Stacked Setup Stacking configuration offsetHanging Stacked Liebert XDVs from Unistruts Stacked Liebert XDVs suspended from UnistrutsHanging Stacked Liebert XDVs from the Overhead Structure Piping System Connection ConfigurationEuropean Union Fluorinated Greenhouse Gas Requirements Connection Methods and Points Piping Connections to Liebert XDP or Liebert XDCRight Side Liebert XDV Hard Piped Connection Sizes Holding Charge-Hard-Piped UnitsRecommended Piping Size Brazing Preparations-Hard-Piped UnitsConnection Methods-One-Shot Connections Branch piping sizes for refrigerant loopRefrigerant Charge-Pre-Charged Option Field Installation of Liebert Flex Pipe Kit on Liebert XDVConnecting Liebert XD Flex Pipe to Liebert XDV Modules Liebert XD prefabricated piping assembly Tools RequiredWith wrench OvertightenReturn Insulation Piping mains without Liebert XDV and Liebert Flex PipeRear Liebert XDV Connecting High Voltage Cables for CSA/C-US Certified UnitsElectrical Rear of Liebert XDVLiebert XDV electrical connections for CE-approved units Rear View of Liebert Xdvto be N.E.C. Class Connecting Low Voltage Wiring-OptionalCondensate Detection Connections Checklist for Proper Installation Installation Checklist and System Fill for StartupStart the Liebert XDV OperationFluorinated Greenhouse Gas Requirements Internal AccessMaintenance Accessing Internal Electrical Components Accessing internal electrical componentsTo remove the fan tray Specifications Liebert XDV10 specificationsLiebert XDV8 specifications Liebert XD Liebert Flex Pipe assemblies, supply and return Page Ti n Ne tIti That