Liebert manual Suspending the Liebert XDV from Unistruts

Page 20

Mounting the Liebert XDV

5.2.1Suspending the Liebert XDV from Unistruts

The Liebert XDV may be bolted to customer-supplied Unistruts. The height of the Unistruts above the computer cabinet must be adequate to accommodate the combined height of the Liebert XDV and the baffle.

To suspend the Liebert XDV from a Unistrut system:

1.Bolt the hangers to each corner of the Liebert XDV, inserting the Liebert-supplied bolts into factory-fabricated holes in the bottom of the Liebert XDV. See Figure 15.

2.Tighten all bolts firmly, taking care not to overtighten the bolts.

3.Using a lifting mechanism, raise the Liebert XDV with brackets attached, to the proper height and bolt the brackets to the Unistruts.

Figure 15 Suspending Liebert XDV from Unistruts

Bolt 3/8" -16; nut and washer provided in kit

Unistrut (field-supplied)

Bolt a bracket to each corner of the Liebert XDV

5.2.2Suspending the Liebert XDV from Overhead Structures

To suspend the Liebert XDV from the overhead structure using the optional overhead mounting kit and field-supplied all-thread bolts:

1.Bolt the hangers to each corner of the Liebert XDV, inserting the Liebert-supplied bolts into factory-fabricated holes in the bottom of the Liebert XDV.

2.Tighten all bolts firmly, taking care not to overtighten the bolts.

3.Install the field-supplied all-thread bolts into the overhead structure, securing them to components so they will match the layout of the brackets

4.Using a lifting mechanism, raise the Liebert XDV inserting the all-thread bolts through the bolt holes in the brackets

5.Install field-supplied nuts and washers, on the all-thread bolts, placing them on the bolts at the level desired for hanging the Liebert XDV.

6.Again using field-supplied nuts and washers, secure the Liebert XDV to the all-thread bolts.

7.Tighten the nuts until the Liebert XDV is level and well-secured.

14

Image 20
Contents Liebert XDV General Safety Guidelines Fluorinated Greenhouse Gas Requirements-European UnionTable of Contents Installation Checklist and System Fill for Startup MaintenanceSpecifications ElectricalFigures Page Example XDV10BK Liebert XDV component locationsPre-Installation Checks Installation ConsiderationsInstallation ReferencesGeneral Product Information Product/System DescriptionChecking and Unpacking Equipment Inspection Recyclable PackagingUnit Handling Unpacking the Unit Domestic PackagingExport Packaging Removing export shipping packageRemoving the Liebert XDV from the Pallet Removing Liebert XDV from shipping palletMechanical Considerations Determining Placement in the Conditioned SpaceDimensional data Changing the Air Intake Location Changing the Liebert XDV’s air intake locationBolting Liebert XDV to Top of Cabinet Mounting the Liebert XDV on Top of the CabinetMounting the Liebert XDV Bottom View Using Supplied Clips for Mounting Mounting clip placementSuspension hardware and bracket dimensional data Suspended Mounting Method11mm 22mm Top View 2 64mm 76mm 102mm DPN000770 Pg , RevSuspending the Liebert XDV from Unistruts Suspending the Liebert XDV from Overhead StructuresSuspending Liebert XDV from the overhead structure Mounting Liebert XDVs in Stacked Setup Stacking configuration offsetHanging Stacked Liebert XDVs from Unistruts Stacked Liebert XDVs suspended from UnistrutsHanging Stacked Liebert XDVs from the Overhead Structure Piping System Connection ConfigurationEuropean Union Fluorinated Greenhouse Gas Requirements Connection Methods and Points Piping Connections to Liebert XDP or Liebert XDCRight Side Liebert XDV Hard Piped Connection Sizes Holding Charge-Hard-Piped UnitsRecommended Piping Size Brazing Preparations-Hard-Piped UnitsConnection Methods-One-Shot Connections Branch piping sizes for refrigerant loopRefrigerant Charge-Pre-Charged Option Field Installation of Liebert Flex Pipe Kit on Liebert XDVConnecting Liebert XD Flex Pipe to Liebert XDV Modules Liebert XD prefabricated piping assembly Tools RequiredWith wrench OvertightenReturn Insulation Piping mains without Liebert XDV and Liebert Flex PipeConnecting High Voltage Cables for CSA/C-US Certified Units ElectricalRear Liebert XDV Rear of Liebert XDVLiebert XDV electrical connections for CE-approved units Rear View of Liebert Xdvto be N.E.C. Class Connecting Low Voltage Wiring-OptionalCondensate Detection Connections Checklist for Proper Installation Installation Checklist and System Fill for StartupStart the Liebert XDV OperationFluorinated Greenhouse Gas Requirements Internal AccessMaintenance Accessing Internal Electrical Components Accessing internal electrical componentsTo remove the fan tray Specifications Liebert XDV10 specificationsLiebert XDV8 specifications Liebert XD Liebert Flex Pipe assemblies, supply and return Page Ne t ItiTi n That