Liebert manual Specifications, Liebert XDV10 specifications

Page 44

Specifications

11.0SPECIFICATIONS

Table 5

Liebert XDV10 specifications

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

XDV10BK--*; XDV10DK--*

 

XDV10BT--*; XDV10DT--*

 

XDV10BS--*; XDV10DS--*

 

 

 

XDV10BKP-*; XDV10DKP-*

 

XDV10BTP-*; XDV10DTP-*

 

XDV10BSP-*; XDV10DSP-*

 

 

 

XDV10BK-E*; XDV10DK-E*

 

XDV10BT-E*; XDV10DT-E*

 

XDV10BS-E*; XDV10DS-E*

 

 

 

XDV10BKPE*; XDV10DKPE*

 

XDV10BTPE*; XDV10DTPE*

 

XDV10BSPE*; XDV10DSPE*

 

 

 

XDV10BKR-*; XDV10BKRE*

 

XDV10BTR-*; XDV10BTRE*

 

XDV10BSR-*; XDV10BSRE*

 

 

 

XDV10DKR-*; XDV10DKRE*

 

XDV10DTR-*; XDV10DTRE*

 

XDV10DSR-*; XDV10DSRE*

 

Models

 

60 Hz

 

60 Hz

50 Hz

 

50 Hz

 

 

 

 

 

 

 

Cooling Capacity

 

Nominal (98ºF [37ºC] EAT): 10kW / 2.8 Tons

Nominal (98ºF [37ºC] EAT): 8kW / 2.3 Tons

 

Maximum (106ºF [41ºC] EAT): 11.8kW/3.4 Tons

Maximum (116ºF [47ºC] EAT): 11.8kW/3.4 Tons

 

 

 

Conditions

 

Capacity Rating is @ 55ºF (13ºC) Entering Fluid Temperature and

 

50ºF (10ºC) or lower dew point, rear air inlet.

 

 

 

Electrical Requirements

 

 

 

 

 

 

 

Input

 

120V model: 1ph-60 Hz

 

230V model:

230V model: 1ph-50 Hz

 

 

 

1ph-60 Hz

 

 

 

 

 

 

 

 

Input power connections

 

 

2 power connections, each model

 

 

 

 

 

 

 

 

 

 

Full Load Amps

 

120V model: 2.0A

 

 

230V model: 1.0A

 

 

 

 

 

 

 

 

Power consumption,

 

180

 

190

190

 

190

 

nominal, watts

 

 

 

 

 

 

 

 

 

 

 

Dimensions, inches (mm)

 

 

 

 

 

 

 

Height – unit only

 

14 (355) not including pipe connections

 

 

 

 

 

 

 

 

Height – including hard

 

 

18-5/8 (473)

 

 

 

pipe connections

 

 

 

 

 

 

 

 

 

 

 

 

Height – including one-

 

 

19-5/8 (498)

 

 

 

shot connections

 

 

 

 

 

 

 

 

 

 

 

 

 

Width

 

 

22-7/8 (581)

 

 

 

 

 

 

 

 

 

 

Depth – Top

 

 

39-1/2 (1003)

 

 

 

 

 

 

 

 

 

 

Depth – Bottom

 

 

29-5/8 (752)

 

 

 

 

 

 

 

 

 

 

Weight, lb (kg)

 

 

 

 

 

 

 

Unit only

 

 

77 (35)

 

 

 

 

 

 

 

 

 

 

Shipping weight

 

 

125 (57)

 

 

 

 

 

 

 

 

Installed, with refrigerant

 

 

79 (36)

 

 

 

 

 

 

 

 

 

Number of fans

 

2

 

2

2

 

2

Airflow, Nominal,

 

1000 (1699) with rear inlet. Bottom inlet airflow

833 (1415) with rear inlet. Bottom inlet airflow

 

may be less, depending on restrictions inside

may be less, depending on restrictions inside

ft3/ min (m3/ hr)

 

 

cabinet

 

 

 

 

cabinet

 

 

 

 

 

 

 

 

 

 

 

Audible noise

 

78 dBa sound power

73 dBa sound power

Pipe Connections (without Liebert Flex Pipe)

 

 

 

 

 

 

Refrigerant supply

 

1/2" OD, Cu, (optional 1/2" threaded coupler flex piping)

from Liebert XDP/ XDC

 

 

 

 

 

 

 

 

 

Refrigerant return

 

5/8" OD, Cu, (optional 3/4" threaded coupler flex piping)

to Liebert XDP/ XDC

 

 

 

 

 

 

 

 

Serviceable Parts

 

 

 

Fans and electrical components

 

Cabinet Exterior Finish

 

Black, matte finish, heat-fused powder coat

Options

 

 

 

 

 

 

 

 

Condensate sensing

 

 

 

Dry contact outgoing signal

 

 

(factory-installed)

 

 

 

 

 

 

 

 

 

 

 

 

Pre-Charged Refrigerant

 

R-134a Refrigerant, one-shot connections

 

 

 

 

 

 

 

 

 

Agency

 

 

 

 

 

 

 

 

 

Approvals

 

CSA 60Hz

 

 

CSA 50Hz

 

CE 50Hz

 

 

 

 

 

 

 

 

* = Revision level of unit

 

 

 

 

 

 

38

Image 44
Contents Liebert XDV General Safety Guidelines Fluorinated Greenhouse Gas Requirements-European UnionTable of Contents Installation Checklist and System Fill for Startup MaintenanceSpecifications ElectricalFigures Page Example XDV10BK Liebert XDV component locationsPre-Installation Checks Installation ConsiderationsInstallation ReferencesGeneral Product Information Product/System DescriptionChecking and Unpacking Equipment Inspection Recyclable PackagingUnit Handling Unpacking the Unit Domestic PackagingExport Packaging Removing export shipping packageRemoving the Liebert XDV from the Pallet Removing Liebert XDV from shipping palletMechanical Considerations Determining Placement in the Conditioned SpaceDimensional data Changing the Air Intake Location Changing the Liebert XDV’s air intake locationBolting Liebert XDV to Top of Cabinet Mounting the Liebert XDV on Top of the CabinetMounting the Liebert XDV Bottom View Using Supplied Clips for Mounting Mounting clip placementSuspension hardware and bracket dimensional data Suspended Mounting Method11mm 22mm Top View 2 64mm 76mm 102mm DPN000770 Pg , RevSuspending the Liebert XDV from Unistruts Suspending the Liebert XDV from Overhead StructuresSuspending Liebert XDV from the overhead structure Mounting Liebert XDVs in Stacked Setup Stacking configuration offsetHanging Stacked Liebert XDVs from Unistruts Stacked Liebert XDVs suspended from UnistrutsHanging Stacked Liebert XDVs from the Overhead Structure Piping System Connection ConfigurationEuropean Union Fluorinated Greenhouse Gas Requirements Connection Methods and Points Piping Connections to Liebert XDP or Liebert XDCRight Side Liebert XDV Hard Piped Connection Sizes Holding Charge-Hard-Piped UnitsRecommended Piping Size Brazing Preparations-Hard-Piped UnitsConnection Methods-One-Shot Connections Branch piping sizes for refrigerant loopRefrigerant Charge-Pre-Charged Option Field Installation of Liebert Flex Pipe Kit on Liebert XDVConnecting Liebert XD Flex Pipe to Liebert XDV Modules Liebert XD prefabricated piping assembly Tools RequiredWith wrench OvertightenReturn Insulation Piping mains without Liebert XDV and Liebert Flex PipeConnecting High Voltage Cables for CSA/C-US Certified Units ElectricalRear Liebert XDV Rear of Liebert XDVLiebert XDV electrical connections for CE-approved units Rear View of Liebert Xdvto be N.E.C. Class Connecting Low Voltage Wiring-OptionalCondensate Detection Connections Checklist for Proper Installation Installation Checklist and System Fill for StartupStart the Liebert XDV OperationFluorinated Greenhouse Gas Requirements Internal AccessMaintenance Accessing Internal Electrical Components Accessing internal electrical componentsTo remove the fan tray Specifications Liebert XDV10 specificationsLiebert XDV8 specifications Liebert XD Liebert Flex Pipe assemblies, supply and return Page Ne t ItiTi n That